1
Case study the “GEOCOOL” heat pump system in UPV campus
José M. Corberán Instituto de Ingeniería Energética Universidad Politécnica de Valencia Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
2
GEOCOOL Geothermal Heat Pump for Cooling-and Heating
THE FIFTH FRAMEWORK PROGRAMME GEOCOOL Geothermal Heat Pump for Cooling-and Heating along European Coastal Areas Project No: NNE5 – 2001 – 00847, July 2002 Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
3
GEOCOOL Geothermal Heat Pump for Cooling-and Heating
THE FIFTH FRAMEWORK PROGRAMME GEOCOOL Geothermal Heat Pump for Cooling-and Heating along European Coastal Areas UPV UNIVERSIDAD POLITÉCNICA DE VALENCIA Spain GROHOL GROENHOLLAND Holland CIATESA Compañía Industrial de Aplicaciones Térmicas S.A. Spain AUTH Aristotle University of Thessaloniki Greece ENEA Ente per le Nuove Tecnologie, l’Energia e l’Ambiente Italy AEDIE Asociación para la Investigación y la Diagnosis de la Energía Spain Duration: 3 years Feb Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
4
GEOCOOL OBJECTIVES To design, construct and demonstrate a GSHP case system in order to produce fair and rigorous data about the: Energy saving potential in comparison to a realistic nowadays alternative system Economic and technical feasibility of GSHP technology in our area Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
5
Ground Source HE main parameters
BOREHOLE Configuration: 6 : 2 x 3, rectangle Borehole depth m Borehole spacing 3 m Borehole installation SINGLE-U Borehole diameter m U-pipe diameter m U-pipe thermal conductivity W/m·K(Polyethylene) HEAT CARRIER FLUID: Water HEAT PUMP: IZE70 + R (UPV-CIATESA) GROUND(test IN-SITU) Ground thermal conductivity W/m·K Volumetric heat capacity 2.4MJ/m3·K Ground surface temperature °C Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
6
Hydr. switch Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
7
Ground Source HE Backfilling: sand (course and fine) or sand/bentonite
alternative use of spacers Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
8
Ground Source HE Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
9
GeoCool data acquisition system
44 sensors in the loop (PT100, coriolis mass flowmeters and wattmeters) On site automatic meteorological station w. 22 parameters 1 min sampling during 1 year Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
10
Internal hydraulic group
Analysis of data Internal hydraulic group Heat pump system Building Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
11
GeoCoolizer Instantaneous values Cooling/Heating capacity
Absorbed/Transferred capacity from/to the ground Instantaneous COP Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
12
Integrated or averaged values
GeoCoolizer Integrated or averaged values Heating and cooling load Total energy absorbed/ transferred from/to the ground - From 7 a.m to 10 p.m - The selected period (one week, all the season…) Electric energy Seasonal Performance Factor (SPF) Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
13
Dynamic behaviour Cooling Mode
Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
14
System performance in heating mode
Experimental results System performance in heating mode COP – WW SPF – WW COP – AW SPF - AW SUMMER 3.46 73 % 2.00 Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
15
Total electricity savings
Two systems with the same heating load 42 Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
16
Heating mode – Return WT
SUMMER Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
17
Energy distribution in heating
Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
18
COP and SPF in cooling mode
4.36 COP – WW SPF – WW COP – AW SPF - AW 60 % 2.72 Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
19
Total electricity savings
Two systems with the same cooling load Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
20
Cooling mode - Return WT
Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
21
Energy distribution in cooling
Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
22
JANUARY 2005-APRIL 2010
23
SYSTEM OPTIMIZATION Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
24
OPTIMUM FLOW RATES: Cooling mode
20% 25% Pump freq. (Hz) Pump freq. (Hz) Both pumps at same speed 40% Pump freq. (Hz) Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
25
OPTIMUM FLOW RATES: Cooling mode
Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
26
OPTIMUM FLOW RATES: Cooling mode
Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
27
OPTIMUM FLOW RATES: Cooling mode
Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
28
OPTIMUM FLOW RATES: Cooling mode
Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
29
MODELLING WITH TRNSYS Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
30
TRNSYS MODEL Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
31
BUILDING THERMAL LOADS: Calculated vs. experiments
Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
32
DAILY TEMPERATURES: Calculated vs. experiments
Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán
33
Conclusions In heating mode, GSHP saves, in terms of primary energy consumption, 41% compared to the air to water roof top system. In cooling mode a 38% saving was obtained. The impact in electricity consumption of the auxiliary elements of the HVAC system was found to be large and should be taken into account to improve overall system efficiency, Capacity adaptation strategies are needed to improve load factor and efficiency of (both) systems. Improved control strategies are being investigated. Seminar: GSHP Systems of High Efficiency – The Ground-Med case study. Madrid, June 23, José M. Corberán