Download presentation
Presentation is loading. Please wait.
Published byMarshall Hutchinson Modified over 8 years ago
1
Parameter's Approach to Relative Humidity Control August 25, 2011 by Clay Hile
2
Main Concepts Different methods of humidity control Air flow requirements PGC’s two-temperature method Advantages and limitations
3
Steam Injection DI Water Source Water Boiler To Room or Chamber
4
Desiccant Dryer Dry applications (set points with below freezing dew points)
5
Two Pressure System Precise calibration applications for small volumes NIST method Can generate low dew points
6
Classic Two- Temperature Control
7
Accurate Precise control Uniformity The need for uniformity in larger areas requires more air flow.
8
Control areas from 2 cu.ft. to 45,000 cu.ft.
9
Uniformity Requires elevated air flows Typical Application: Dew point is constant Humidity differences across a room or chamber are generally temperature driven
10
Constant Dew Point Temp. goes up, RH goes down Temp. goes down, RH goes up
11
Walk-in Plan View Return 73°F/50%RH Supply 300 CFM 10 x 12 x 10 Room (1200 cube)
12
Room with Load 73°F/50%RH Supply Return 3000 BTU Heat Source 82°F
13
Constant Dew Point (53.3°F) / 15 Air Changes per Hour 73°F/50%RH Supply Return 3000 BTU Heat Source 82°F/37% RH
14
Improving Uniformity Reduce internal load Location of load Increase air flow
15
Increased Air Flow
16
Parameter’s Two-Temperature Control (PGC’s Method)
17
Dehumidification 53° DP
18
Humidification
19
RH Compensation
20
Two-Temperature Control Control dew point by controlling water spray temperature Control relative humidity by maintaining a tight air temperature control
21
Accurate – Sensor Dependent Precise Control – Two- temperature method Uniformity – Higher air flow and good distribution
22
Ability of Two-Temperature Control
23
Calibration PGC provides the control and uniformity Chilled Mirror or other reference sensor provides accuracy.
24
Limitations to the Parameter “two temperature” Range – dew point must be above freezing. Ramp Rates – larger saturator water volumes stabilize control but increase the time to ramp dew points. Requires a humidity sensor. Is not a primary standard.
25
Conclusion Two temperature method is a proven method to maintain precise humidity control in larger areas.
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.