Download presentation
Presentation is loading. Please wait.
Published byMarjorie Daniels Modified over 8 years ago
1
Grounded Wye-Delta Transformer Bank Backfeed Short-Circuit Currents W. H. Kersting & Wayne Carr Milsoft Utility Solutions
2
Introduction Wye-Delta Transformer Bank – Serving a three-phase load A three-phase transformer Or three single-phase transformers – Serving single-phase and three-phase loads One centered tapped lighting transformer Two power transformers Question: To ground or not to ground the Wye connection.
3
Wye-Delta Transformer Connection
4
Ungrounded Wye-Delta Transformer Bank
5
Grounded Wye-Delta Transformer Bank
6
So What? Ungrounded Y-D – No backfeed short circuit current – Lose one phase and bank becomes single-phase Grounded Y-D – Backfeed current possible – Lose one phase and have open Y-D bank – Need to compute all short circuit currents for A-G fault
7
Test System Used to Compute Backfeed SC Currents for Grounded Y-D Bank
8
Overhead Lines
9
Overhead Line Phase Impedances
10
Methods of Analysis Symmetrical Components – Old fashion way to demonstrate backfeed Basic circuit and transformer analysis – Analysis of total three-phase circuit Reduced 8x8 matrix analysis – Reduce total analysis to just what is needed
11
Symmetrical Component Method
12
Overhead Line Sequence Impedances
13
Sequence Networks Connection Phase a-g Fault at Node 12
14
The Minus 3 Error Doc. Crosno (NMSU) was a stickler for accurate calculations when I was a student When he found an error it was an automatic -3 error (red rubber stamp) out of 10 points on the problem When I was preparing for this presentation I found a -3 error on the symmetrical component analysis. I used transformer impedance referred to secondary rather than primary side. Please ignore the results in the paper
15
Correct Sequence Network Analysis Results
16
Now What? The symmetrical component method has demonstrated – There is a backfeed current of 91.48 amps/phase – This method assumes a balanced three-phase system (ignored the off diagonal terms of the sequence impedance matrix) Need to evaluate the short circuit currents with a total unbalanced three-phase system
17
Unbalanced Three-Phase System
18
Observations to Note
19
A-G Fault at Node 12
20
A-G Fault at Node 12 Results
21
Reduced Three-Phase Circuit Analysis Primary concern – Currents in the fault – Currents from the source – Backfeed currents from the transformer bank Recognize the three backfeed currents are equal Apply basic algebra to reduce to 8 equations and 8 unknowns
22
Reduced Analysis 8x8 Matrix
23
8x8 Matrix for A-G Fault at Node 12
24
8x8 Matrix Results
25
Comparisons of Results
26
WindMil Results Using Loop Flow Method
27
Ungrounded Wye-Delta Connection Analysis methods – 7x7 matrix – Set Zg = 999999 Results
28
Short Circuit Current vs. Rated Current Transformer Rated Currents – 100 kVA: 13.8 amps – 50 kVA: 6.9 amps With Zg = 5 ohms backfeed = 91.7 amps – 100 kVA: 564% over rated current – 50 kVA: 1,229% over rated current With Zg = 50 ohms backfeed = 19.3 amps – 100 kVA: 39.9% over rated current – 50 kVA: 79.9 % over rated current
29
Short Circuit Protection
30
Substation Transformer Primary Fuses Primary responsibility is to open on transformer faults Backup responsibility to open if low side breaker fails to open for downstream fault Transformer fuse must lie between inrush current and maximum melt curves
31
Primary A-G Short Circuit Current
32
Substation Transformer Fuses
33
Primary Fuse Curves Referred to Secondary for LG Fault
34
Primary Curves Referred to Secondary For LG Fault
35
Recloser and Xfm Fuses
36
Total Protection
37
Three Downstream Transformers 8x8 equivalent matrix method of analysis doesn’t work Symmetrical component model developed and analysis run WindMil using the loop flow method was developed and analysis run Symmetrical components and loop flow methods match very closely
38
Three Downstream Transformers WindMil Solution
39
Summary Grounded Wye-Delta Short Circuit Analysis – Symmetrical Components – Exact Circuit Analysis – Reduced Circuit Analysis Ungrounded Wye-Delta Short Circuit Analysis Short Circuit Protection – Primary Fuses – Recloser – Distribution Transformer Fuses
40
Conclusions Grounded wye-delta transformer banks provide backfeed currents for upstream faults involving ground Ungrounded wye-delta does not provide backfeed currents Backfeed currents can blow transformer fuses for upstream ground faults
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.