1 Free cooling on RTAF Chiller
Integrated option

2 Water based free cooling principle.
Use full aluminum (car radiator based) flat channel dry cooler exchangers. Modulate 3 way valve to reach required free cooling capacity. Need low air pressure drop coil to avoid upgrade of fans. Oil Sep. Evaporator

3 Technical proposition
Alternative 1 : no change on condenser fan = lower EER, but no fan impact on cost, almost no impact on sound level Total Free cooling Direct free cooling version (With glycol on customer loop) Total Free cooling Glycol Free version (With water on customer loop) 1 2 Partial Free cooling Direct free cooling version (With glycol on customer loop) Partial Free cooling Glycol Free version (With water on customer loop) 3 4 Trane FreeCool External drycooler 5 External Dry cooler – Standard RTAF With or without glycol on customer loop

4 Optionnal Pump package
Flow chart - Free cooling Direct free cooling version (With glycol on customer loop) 1 3 Service valve (Vent) Dry cooler coils Dry cooler coils Service valve (Vent) Tchill OUT Tevap IN Evaporator Free cooler Modulating 2way valve Free cooler Bypass 2way valve Tchill IN Optionnal Pump package Service valve (Drain)

5 Optionnal Pump package
Flow chart - Free cooling Glycol Free version (With water on customer loop) 2 4 Service valve (Vent) Dry cooler coils Dry cooler coils Service valve (Vent) Tchill OUT Tevap IN Water/glycol BPHE Tfc OUT Evaporator Free cooler Modulating 2way valve Exp.tank Free cooler Bypass 2way valve Tchill IN Optionnal Pump package Tfc IN Service valve (Drain) Service valve (Drain) Circulating pump

6 Free cooling enabling condition
Condition to get free cooling active : Unit is in active cooling mode. Outdoor temperature shall be low enough. Cf. diagram here below Free cooling enabled Proposed default value FC Offset = 3K (Min 0.5°K, max 15°K) FC Hysteresis = 1K (Min 0.5°K, max 3°K) FC Offset Free cooling disabled Water Cooling setpoint Outdoor air temperature FC setpoint = Active chilled water cooling setpoint – FC_offset FC Hysteresis The free cooling function is enabled when outdoor air temperature is below (Active chilled water cooling set point minus FC_offset). An hysteresis shall be applied to avoid short cycling of FC enable logic. FC offset is the parameter adjusted by user to make free cooling active. Free cooling becomes the 1st stage of cooling, whatever the compressor sequence selected: If free cooling is enabled while compressor is running, then unload command of the algorithm shall apply to running compressor . In case of load command, then free cooling capacity shall be increase

7 Free cooling capacity modulation
3 3 Dry cooler coils Dry cooler coils Dry cooler coils Dry cooler coils 2 2 Free cooler Modulating 2way valve Free cooler Modulating 2way valve Free cooler Bypass 2way valve (ON-OFF) Free cooler Bypass 2way valve (ON-OFF) 1 1 FC pump 4 FC disabled FC 1st step FC 2nd step Bypass Valve 100% 100%►0% for TFC 100%►30% for PFC 0% for TFC 30% for PFC FC valve CLOSE 0%►100% (modulating) Condenser fan airflow Follow compressor fan sequence 0% or follow compressor fan sequence if compressor are still running 0%►100% FC pump OFF ON 1 2 3 4

8 Freeze protection (only for Glycol free version)
If Free cooling is active, the pump is ON. At start up or when heat transfer over the drycooler increases, the glycol stored in the system could be very cold, resulting in freezing risk on the BPHE. To avoid this, the strategy is to run the pump with recirculation of the glycol in a short loop (dotted line arrow). The freeze protection mode is targeted to restore positive temperature at BPHE glycol inlet. The heat from return chilled water and from the pump heat loss will try to maintain the BPHE glycol temperature above 0°C. Difficulty here is to have quick enough system response to avoid partial freezing into the BPHE Condition to have freeze protection active: Outdoor air temperature <3°C Free cooling is active : Chiller water flow is present & there is a call for cooling. If Tfc OUT is < chilled water freeze protection setpoint and FC pump is ON then we are in FC freeze protection mode FC Freeze protection limiting mode : Reduce Free cooling capacity to keep TfcOUT > chilled water freeze protection setpoint from 100% to 0% (following accelarated unload sequence). If Tfc IN < chilled water freeze protection then Lockout free cooling operation and report alarm. Auto reset when Outdoor temperature is >3°C. To dry cooler coils Tchill OUT Tevap IN Water/glycol BPHE Tfc OUT Evaporator FC Modulating 2way valve FC Bypass 2way valve Tchill IN Optionnal Pump package Tfc IN Service valve (Drain) Service valve (Drain) Circulating pump

9 Schedule 2015 2016 Q1 Q2 Q3 Q4 Q1 9 IRPDP gates reviews
Jan. Feb. Mar. Apr. May Jun. Jul. Aug. Sep. Oct. Nov. Dec. Jan. Feb. Mar. G1 G2 G3 G4 G2 G4 IRPDP gates reviews Jul-09 Program key steps Mockup build & Test Validation unit Ph1 build & Test Validation unit Ph2 build & Test Industrialization Ph1 Industrialization Ph2 Literature update Ph1 Literature update Ph2 Phase 1 = All RTAF sizes – Direct free cooling version - Partial and Total Free cooling Phase 1 : All RTAF sizes – Glycol FREE version - Partial and Total Free cooling The Schedule & Next steps slide provides a snapshot of the schedule to the next Gate review. Many tools can be used to create this… simple table, Microsoft Project or other schedule tool. For a Gate 1, there should be detail to get to the Gate 2 review and milestones for the balance of the project. A full integrated schedule is not required until Gate 2. Pre-annoucement Topps Release Topps Release 1ST SHIP 1ST SHIP 9

10