Download presentation
1
What makes up a Unico System
Understand What to Ask How to Place an Order
2
Sound Attenuator (UPC-26C) Outlet (UPC-56B) Elbow
Plenum Blower Modules (2430,3642, 4860) Heating Module (MH2430, MH3660) Supply Tubing (UPC-25) Cooling Modules (MC2430, MC3642, MC4860) Return Air Adapter (UPC-59-xxxx) Secondary Drain Pan Sound Attenuator (UPC-26C) Return Air Duct (UPC-04-xxxx) Return Air Box (UPC-01-xxxx)
3
The Load What is Cooling/Heating Requirement Remember, a BTU is a BTU
Unico has sizes from One to Five Tons of cooling Unico can provide up to 20 KW of electric heat Unico can provide up to 150,000 btu output of hot water heat
4
Sizing the Job Use the ACCA Manual “J” or ASHRAE equivalent
A Load calculation is the same for Unico as for all other HVAC systems Unico provides a Bulletin which contains a very simple sizing guide based on older building construction
5
Remember a Btu is still a Btu This is the CONTRACTOR’S responsibility
Ask for the size in Tons Remember a Btu is still a Btu This is the CONTRACTOR’S responsibility Remember to let them know that we are the same as a conventional system when it comes to sizing
6
Unico Sizes M1218 M2430 M3036 M3642 M4860 1 to 1 ½ Tons 2 to 2 ½ Tons
Explain a little bit about how we go about naming part numbers
7
Air Handler Position Vertical or Horizontal If Vertical:
Order Vertical Stand Don’t order Return Air If Horizontal: Order Return Air Assembly Order Secondary Drain pan If horizontal is hard, ask “Attic Installation”?
8
Return Air Assembly Return Air Box: UPC1XX* Return Air Duct: UPC4CXX*
Return Air Adapter: UPC59BXX XX=Size in Tons Explain again how our parts numbering system operates
9
Return Air Box
10
Return Air Duct
11
Return Air Adapter
12
Unico Air Handlers
13
Air Handlers 5 Sizes All modular except for M1218 1 to 1 ½ Tons
Five Sizes: 1 to 1 ½, 2 to 2 ½,2 ½ to 3, 3 to 3 ½, 4 & 5 Tons
14
M1218 One –Piece Unit
15
Parts match-up with the A/C and Hot water coil
Parts match-up with the A/C and Hot water coil. Notice that when you order the M4860 coil it comes with a 6” spacer.
16
Vertical Application
17
Vertical Air Handler Explain the parts of this: Blower Module, Spacer, Coil Module, MVXX Stand
18
Modular Unit – Vertical Config.
MV2430 One-piece AHUs
19
The Unico Blower Module
20
Today we use an EC Blower Motor
Features and Benefits The History of the Unico System Blower Module and Motor Today we use an EC Blower Motor
21
ECM … PSC Side by side comparison of the old PSC motor (on right) with the new ECM. Silver item at the bottom is the controller, these are very sensitive to high heat, therefore don’t use a hot water coil with entering water temperature of greater than 140 degrees
22
How does it work? Uses the Emerson EC motor, a very common industry motor The control for the motor is specific for the designs of the Unico system. Sets a constant CFM by adjusting the RPM to conform with the Unico System fan curve
23
New SMART Board
24
LED Lights Default Settings
LED Lights: Power, indicated 24v supply; Heat, unit in heating mode, PCB Control, something on the board’s software is causing the fan to run. Fan: flashes long for 100 CFM, short for 50 CFM Default The preset speeds for all units, allows you to program without a computer
25
How to Connect Use a laptop to connect
26
Percentage (of high cool airflow)
Unico System Software Mode Percentage (of high cool airflow) Fan Recirculation (G) 50 Low Cool (Y1) 75 Low Heat (W1) High Heat (W2) 100 Emergency Heat (E)
27
The Cooling Module DX or Chilled Water Cooling only or Heat Pump
28
Coil Module
29
INSTALLING THE TXV TXV is shipped taped to condensate pan (Not factory installed) “Chetleff” Fitting
30
Unico Condensate U-Trap (Included in the Coil Module)
Unico Part No. Description A00924-G01 U-Trap, Modular A00924-G02 U-Trap, M1218 A00924-G U-Trap (Float Switch), Modular A00924-G U-Trap (Float Switch), M1218
31
Heating Options Electric Furnace Hot Water Heating Module
Geothermal (not shown)
32
Plenum Type 26 gauge Single Wall K/D pipe
Use full flow tees and elbows NOT Unico supplied We only make pre-fabricated fiberglass, metal is supplied locally
33
Supply Tubing Rules Make sure you use a MINIMUM of five outlets per ton Outlets are sold: Boxes of 2 ½” tubing (five pieces per box) Boxes of Installation Kits (five pieces per box)
34
Small Duct Connectors UPC-228 Flanged Takeoff, for round metal (UPC-228F for square metal) frame-in
35
Outlet Kits 2 1/2” tubing (5 per box)
Installation Kit UPC289F (5 pieces each)
36
Installation Kit Components
Winter Supply Shut-Off C lamps, Black & Silver Metal Take-Off
37
Installation Kit Components
Toggle Bolts & Screws White Plastic Outlet
38
Tools Turbometer Measures wind speed in Knots Knots x 2.37 = CFM
UPC 54 Clamp Pliers New prod.
39
Need to Complete Unico System
Condensing Unit or Heat Pump Tape (UL 181A rated) Line set, disconnect, etc.
40
Unico Installation Overview
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.