EET 325 Oct. 14, 2005 Lecture Power factor correction
2
Recall from ac circuits P = VICos( ) Q( for the circuit) = VISin( ) jQ (for an inductor) = jI 2 X L =jV 2 /X L -jQ (for a capacitor) = -jI 2 X C = -jV 2 /X C
3
Example Number 1 Given : a 240 volt supply voltage 13 kW load 0.65 lagging power factor
4
= Cos -1 (0.65) = 49.458 o I L = I L = 83.333/ -49.458 o P = VICos( ) = 13 kW Q = VISin( ) = j15.198 KVars
5
Determine the capacitor Value for Unity Power Factor Let’s Add a capacitor as shown -jQ = -j15.198 KVars = -jV 2 /X C X C = 3.789 = 1/( C) Where = 2 f = 2 60 = 377
6
X C = 3.789 = 1/(377 C) C = 700 uf
7
I C = 240/(-jX C ) = 63.327 /90 o I L = 83.333 / -49.458 o I S = I L + I C I S = 54.17/0 o