Presentation is loading. Please wait.
Published byPercival Sanders Modified over 8 years ago
2
Elbow Sound Attenuator (UPC-26C) Outlet (UPC-56B) Plenum Supply Tubing (UPC-25) Blower Modules (2430,3642, 4860) Heating Module (MH2430, MH3660) Cooling Modules (MC2430, MC3642, MC4860) Return Air Adapter (UPC- 59-xxxx) Sound Attenuator (UPC-26C) Secondary Drain Pan Return Air Duct (UPC-04-xxxx) Return Air Box (UPC-01-xxxx)
3
Unico vs. Conventional Ducted Systems Roughly half the CFM (200-250 vs. 400) High Static Pressure (Avg. 1.5” w.c.) Refrigeration Coil vs. A/C Coil Greater Temp. Drop in AC 1000 to 2000 fpm velocity Aspiration vs. Diffusion and Throw and Return
4
THREE BIG DIFFERENCES 1. Airflow 2. Aspiration 3. Static Regain
5
Unico vs. Conventional Roughly half the CFM (200-250 vs. 400) Refrigeration Coil vs. A/C Coil Greater Temp. Drop in AC Warmer Temperatures in Heat Pump
6
Lower Airflow & 6 Row Coil Removes 30% More Moisture
7
Higher Discharge Temperature No Need for Electric Heat to Feel Warm 122°F (50°C) Discharge Air Temp At 47° Rating Point Eliminates Cold Blow Complaints
8
Unico vs. Conventional High Static Pressure (1.5” w.c.)* High Velocity (1000-2000 fpm) *NOT consider high static pressure by ASHRAE Ratings
9
Much Higher Discharge Velocity
10
Aspiration Diffusion, Throw, Return
11
Small Space Savings
12
Smaller Supply Outlets
14
Any Condensing Unit
15
SDHV classification
16
Ratings AHRI Ratings In AHRI Directory Under “SDHV”
17
Energy Efficiency Differences SDHVConventional Thermal losses4%8% Duct leakage<5%15-20% Duct efficiency*>80%50% System efficiency, Btuh/W (SEER x duct efficiency) 8.806.50 * Based on ASHRAE Standard 152
18
End of Introduction Please take the ten question test for this module, then proceed to : “Unico Components Part One”