Delta Confidential CP2000 Introduction
2
Delta Confidential Agenda CP2000 Introduction CP2000 Top 10 Features CP2000 Field Application
3
Delta Confidential CP2000 Introduction For Fans/Pumps/HVAC Drive applications. HVAC: Heater, Ventilating, Air Conditioner. V/F control 、 SVC (sensorless vector control) PID control and sleep/wake up function Multi-pumps, circulation pumps control Fire mode + BYPASS function PLC(10K step) + Real Time Clock VFD-soft link and LCD TP editor Built-in BACnet LCD keypad user friendly interface
4
Delta Confidential Energy saving on HVAC From the relations illustrated above, we can reduce the running frequency of the motor according to the load. EX: When the motor’s running speed is reduced from 60Hz to 50Hz by mains electricity… Theoretical Value: (50*50*50)/(60*60*60)=0.5 8 (Only 58% of the electricity is required.)
5
Delta Confidential V/F,SVC TN Curve V/FSVC rpm T-N(Nt/m)
6
Delta Confidential VW RA1 ~ RA2 ~ RA3 ~ Motor 1Motor 2Motor 3 Constant speed U Master Motor Regulated speed ~ Mains Supply RA1 RC1 RC2 RC3 RA2 RA3 M1 control M2 control M3 control FWD/STOP FWD MI1 MI3 MI2 AuxiliaryM1 Run/Maintenance STR AFM Output Frequency Hz DCM PT PID Transducer feedback function select Pressure * Booster pumps of municipal water supply systems * Automatic level control of reservoirs * Pumps and fans of waste water treatment plants * HVAC systems * Cooling tower fan drivers * Combustion air and exhaust gas fans of power plants Pump and Fan Control AuxiliaryM2 Run/Maintenance AuxiliaryM3 Run/Maintenance
7
Delta Confidential CP2000 Power Capability 460V 3 Phase 0.75kW~400kW –Models under 37kW with built-in EMI filter for: VFD007CP4EA-21, VFD015CP4EA-21, VFD022CP4EA-21, VFD037CP4EA-21, VFD040CP4EA-21, VFD055CP4EA-21, VFD075CP4EA-21, VFD110CP4EA-21, VFD150CP4EA-21, VFD185CP4EA-21, VFD220CP4EA-21, VFD300CP4EA-21, VFD370CP4EA-21 –Models under 37kW with built-in braking unit –45kw~400kW with built-in DC reactor , optional for EMI filter 、 optional for braking unit 230V 3 phase 0.75kW~90kW –Models under 30kW with built-in braking unit –Models above 37kW with built-in DC reactor –Optional EMI filter. LCD BUILT-IN~ C2000 same Platform
8
Delta Confidential CP2000 Model name
9
Delta Confidential Ordering information
10
Delta Confidential FRAME size comparison Frame A Frame B Frame C Frame D 1~7.5HP 10~20HP 25~40HP 50~100HP Frame E 125~150HP
11
Delta Confidential CP2000 TOP Features Control method : V/F control & SVC control 、 PID control and sleep/wake up function 、 Multi- pumps control 、 FIRE MODE 、 PLC 、 real time clock. Optional cards : communication cards & I/O extension card, CANopen(DS-402) Built-in : RS-485, MODBUS and BACnet BACnet MODBUS Built-in protocol PLC(10K step) User designed PLC program for sequential control DeviceNet ProfiBUSEthernet IP MODBUS TCP D24AR6AA I/O cardRelay card COP01 CANopen cards
12
Delta Confidential CP2000 TOP 1 Removable Fan Modular design maintain free Plug-in/out terminal
13
Delta Confidential CP2000 TOP 2 Robust design PCB Coating treatment, assure the reliable operation in the harsh environment Suppress harmonic: Built-in RFI filter; Models above Frame D have built-in DC reactor. Comply with EN61800-3 *AFE2000, DC reactor, AC reactor, and EMI filter are options for the models without built-in DC reactor or EMI filter. Designed for environment adaption
14
Delta Confidential CP2000 TOP 3 Control PWB no touch with heat sink Heat sink is isolated with control PWB system for preventing CP2000 from damaging and environmental pollution Isolated Control PWB
15
Delta Confidential CP2000 TOP 3 Flange mounting: Put all heat generated from inverter out. Isolating all the dust from the environment.
16
Delta Confidential CP2000 TOP 4 Plug & Play IP56 Proof level LCD Keypad
17
Delta Confidential CP2000 TOP 4 Quick setting for user common usage, easy and fast to install. Multi-row display, Menu free, user friendly operation interface. Monitoring F (Freq.) 、 H (output Freq.) 、 U (User definition) synchronously. CAN 、 PLC and HAND/OFF/AUTO status display User defined parameter management Real time clock Error log with timing record Multi-language LCD Keypad Features
18
Delta Confidential CP2000 TOP 4 PLC program, Drive Parameter Copy/Backup/Restore to VFD_soft or CP2000. TP Editor for USER defining the display on the screen of keypad. VFD_soft and LCD panel for bi-direction edit function. LCD panel portable, plug & play.
19
Delta Confidential VFD-soft & TP Editor
20
Delta Confidential CP2000 TOP 5 Built-in PLC (10K step): It can be used with the built-in real time clock for special multi-pumps control.
21
Delta Confidential CP2000 TOP 6 Most common used, various high speed network Built-in BACnet
22
Delta Confidential CP2000 Options List CategoryOption NameModel Number Network CommunicationDeviceNetCMC-DN01 EtherNet/IPCMC-EIP01 Modbus TCP/IPCMC-MOD01 Profibus DPCMC-PD01 CANopenEMC-COP01 CANopen Breakout BoxTAP-CN03 CANopen Communication Cable 500mmTAP-CB03 CANopen Communication Cable 1000mmTAP-CB04 Input/OutputDigital InputEMC-D42A/EMC-D611A Digital OutputEMC-D42A/EMC-R6AA KeypadLED KeypadKPC-CE01 Panel Mounting Kit (MKC-KPPK) Flange Mounting KitFrame AMKC-AFM/MKC-AFM1 Frame BMKC-BFM Frame CMKC-CFM USB/RS-485 Communication Interface IFD6530
23
Delta Confidential Multi-pumps control 1: Fixed Time Circulation (by time) 2: Fixed amount circulation (by PID) 3: Fixed amount control (by PID) 4: Fixed Time Circulation+ Fixed amount circulation 5: Fixed Time Circulation+ Fixed amount control Fixed Time Circulation (Max: 8 pumps) CP2000 TOP 7
24
Delta Confidential Multi-pumps control Fixed amount circulation (Max: 4 pumps)Fixed amount control (Max: 8 pumps)
25
Delta Confidential Application: ventilating of building, tunnel, subway, etc. During fire mode the drive is forced operation. BYPASS mode is selected to AC power (with ac Mains Bypass breaker). Exhausting smoke until drive failure or AC power shut down. CP2000 TOP 8 Fire mode + bypass function
26
Delta Confidential CP2000 TOP 9 Flying start function lets high inertial load situation can run smoothly in start without error happened. (No need to stop the motor) Momentary power off (within 5s on LV), the speed searching function can make the motor continue running without stopping the motor to save start time. start speed tracking Flying start to smooth going
27
Delta Confidential CP2000 TOP 10 Skip frequency function avoids the motor vibration at a specific frequency band and protects the equipment. It offers 3 zones for use.
28
Delta Confidential CP2000 TOP 10 DEB (Deceleration Energy Backup) This function allows the AC motor drive decelerates to stop after power loss. When the momentary power loss occurs, this function can be used for the motor to decelerate to 0 speed with deceleration stop method. When the power is on again, motor will run again after DEB return time.
29
Delta Confidential WHY CHANGE TO CP2000 ? CP2000VFD-FC2000 Special ApplicationApplication on customer side Product Highlights DWELLAvailableN/AAvailable When the acceleration/deceleration of a gear transition is applied at a crane, its remains a fixed frequency output. To prevent non-smoothing at a load during delay time of a gear box acceleration\deceleration DEB (Deceleration Energy Backup) AvailableN/AAvailableDeceleration time setting for spontaneous power down + DC brake + Delay braking time: Keep a crane to have stable fixed output frequency while deceleration and emergency While operating a crane, a deceleration is required to stop loading when there is an spontaneous power down. FIRE MODEAvailable + BYPASS V1.302N/AUse bypass function to switch to the mains power supply. Keep the drive in control without being interrupted by any error when there is an emergency. Keep this drive in control until the mains power supply is out or until this drive’s failure. Available + BYPASS MULTI- PUMPS control1 to 81 to 4N/A Fixed time, Fixed amount control, Fixed time/ Fixed amount circulative control (1 to 8 motors) Multi pumps are setting for fixed amount, fixed time circulative control to increase the effectiveness and product life. BACnetAvailable V1.302, BACnet N/A BACnet, MS/TP has a speed up to 38400bps at COM1 BA/FA control via a Fieldbus Network provides many kinds of application.
30
Delta Confidential PLC (10k steps)AvailableN/AAvailable Position Machine and PLC (Programmable Logic Controller) let you do sequencing control. You save money on buying Position machine PLC. Motor’s Parameters AUTO-TUNING AvailableN/AAvailable Auto energy saving, auto acceleration/deceleration, time setting, Primary Motor start up, Best performance adjustment Optimization of energy saving LCD+TP editor Available N/AAvailable Start up screen and switching between related physic screens are user-defined. Simple Customer Logo, Editing of physical quantity VFD_softAvailable Administration of PC Link parameters, copy, download and upload to CP2000 Administration of parameters, and monitoring of related curves FLYING START (tracking starting speed) Available To track start up speed of Air blower, Punch press and High inertia load flywheel. To ensure safety of high inertia load machine such as air blower and safety of the machine operator at start up. Derating (Over Load protection) AvailableN/AAvailable FC and Over Load capacity changes as the operating environment changes. Provide a stable and safe output power in a hot and bad environment. Auto acceleration /deceleration Available N/A Available Auto adjust acceleration/deceleration time in accordance to the loading rate. Energy saving Emergency Stop or Force to Stop function AvailableN/AAvailable Parameter07-20, Forces to stop or do EF input. Lock the machine when emergency to ensure both the machine and its operator are safe. WHY CHANGE to CP2000 ? CP2000VFD-FC2000 Applications Applications on Customer Side Product Highlights
31
Delta Confidential WHY CHANGE CP2000 ? CP2000 YASKAWA E1000 Danfoss FC102ABB ACH550 Product Highlights DWELLAvailable N/A DEB (Deceleration Energy Backup) Available N/AAvailable (FLUX BRAKING ) FIRE MODEAvailable + BYPASSN/AAvailableN/A MULTI PUMP FUNCTION1 to 8Available1 to 4Available BACnet communication protocolAvailableN/AAvailable PLC (10k steps)AvailableN/A Motor's Parameters AUTO-TUNINGAvailable LCD+TP editorAvailableN/ALCD VFD_soft (PC link software)Available Available energy monitoring FLYING START (tracking starting speed) Available Derating (Over Load protection)Available Auto acceleration /decelerationAvailable Emergency Stop or Force to Stop function Available
32
Delta Confidential Comparison of different brands Comparison Chart on Functions DELTA_CP2000YASGAWA E1000Danfoss_FC102ABB_ACH550 Power Range 230V0.75kW~90kW0.75~110KW1.1 - 45 kW (200 - 240 V)0.75~75kW 460V0.75kW~400kW0.75 kW to 630 kW1.1 -250 kW (380 - 480 V)0.75~355kW 575V 1.1 -250kW (525 - 600 V) Control ModeVF, SVCV/F,FOC sensorless+PMV/F,VVC plus PWM Sensorless Vector, V/F Scalar control Operating Temperature Light duty: -10 ~ +40 ℃ Normal duty: -10 ~ +50 ℃ Above 30 kW: -10°C to +50 °C Below 22 kW: -10 °C to +40 °C ambient 50 °C -15 °C to +40 °C (+5 °F to +104 °F), +50 °C with derating EMC filter 460V 37kW and below with optional EMI filter built-in 7.5 kW to 90 kW: With internal filter Class A BUILT-IN EMC FilterBuilt-in EMC filter International Standard & Certifications UL, cUL, CE, RoHS CE marking UL, cUL, RoHS CE, UL, RoHS,WEEECE, c-tick, UL, cUL, RoHS
33
Delta Confidential Overload Tolerance Normal Duty: 120% for 1 minute; 160% for 3 seconds; Light Duty: 120% for 1 minute. Normal duty: 120% for 1 minute 130% break away torque 110% torque for 60 seconds 110% of rated current for 1min every 10 mins through all speed range Output Frequency Range 0.00~600.00Hz 230V 55KW and above are 0.00~400.00Hz 440V 90KW and above are 0.00~400.00Hz 7.5~90 kW: 0 Hz to 650 Hz 110~250 kW: 0 Hz to 267 Hz 0 to 1000Hz0~500Hz Operating InterfaceLCD KPC-CC01LEDLCD Communication Options RS485, PROFIBUS, DeviceNet, CANOpen, Modbus-TCP Slave, EtherNet/IP Slave, BACnet MODBUS RS485, PROFIBUS, DeviceNet, CANopen,CC- LINK Mosbus RTU, FC protocol, Profibus, DeviceNet, LonWorks,N2,BACnet DeviceNet, LONWORKS, PROFIBUS DP, CANOpen, ControlNet, CC-Link, Modbus TCP, Ethernet/IP, PROFINET IO, Power Link, EtherCat, BACnet Preset speed15, programmable 8, programmable7, programmable Comparison of different brands Comparison Chart on Functions DELTA_CP2000 YASGAWA E1000Danfoss_FC102ABB_ACH550
34
Delta Confidential Analog Input AVI 1: 4~20mA/0~10V(AVI Switch), Factory setting is 0~10V ACI: 4 ~ 20mA/0~10V(ACI Switch) Factory setting is 4~20mA AVI 2: 0~10VDC 3 programmable analog inputs A1: 0 V to 10 V A2: 0 V to 10 V and 4 mA to 20 Ma A3: 0V TO 10V 3, programmable 0V to 10V(Scaleable) 0/4 mA to 20 mA (Scaleable) 2 programmable analog inputs AI1: 0 V to 10 V/ 0(4) mA to 20 mA AI2: 0(4) 20 mA/ 0V to 10V Digital Input 8 fully programmable isolated digital inputs; switchable PNP/NPN 3 fully programmable isolated digital inputs; switchable PNP/NPN 6 fully programmable isolated digital inputs; switchable PNP/NPN Analog Output AFM1: 0~10V → - 10~+10V(AFM Switch Factory setting is 0~10V) AFM2: 0~10V → 4~20mA(AFM Switch Factory setting is 0~10V) 1, programmable (0/4 mA to 20 mA) 2, programmable (0/4 mA to 20 mA) Digital Output RA1/RB1/RC1/RA2/RC2/RA3 /RC3: Resistive Load 5A(N.O.)/3A(N.C.) 250VAC 5A(N.O.)/3A(N.C.) 30VDC Inductive Load (COS 0.4) 2.0A(N.O.)/1.2A(N.C.) 250VAC 2.0A(N.O.)/1.2A(N.C.) 30VDC 4, programmable 30 V DC/5 A (resistive load), 250 V AC/2 A (inductive load) 2, programmable 240VAC, 2A and 400VAC, 2A 3 relays 3 relay output 30 V DC/2 A 250 V AC/2 A Comparison of different brands Comparison Chart on Functions DELTA_CP2000 YASGAWA E1000Danfoss_FC102ABB_ACH550
35
Delta Confidential Braking system DC Braking, AFE2000, Braking unit, Braking Resistor DC Braking, REGEN braking DC Braking, Brake units, AHF (Active Harmonic Filter) DC braking, 0.75~7.5kW: built-in braking chopper others: Compact-size brake units Degree of protection IP20, NEMA1 IP00, UL open type Above 30KW IP00, below 22KW IP21 IP00/IP20/IP21/NEMA1/NEM A12/ IP66 available IP21 or IP54 Protection features Under voltage, Over Voltage, Over Load, GFF, Over Current, Stall prevention, Over heat, Over torque, Under current, Base Block, DEB, auto restart, phase lose, short, fly start. Under voltage, over voltage, overload, earth faults, short- circuits, stall prevention, locked motor protection, over heat, parameter change protection Under voltage, Overvoltage, Overload, Earth faults, Short- circuits, Stall prevention, Over heat, Fly start, PHL, Over current, Auto restart Overvoltage, under voltage, Earth-leakage supervision, Motor short-circuits, Output and Input supervision, Over current, Phase loss, Under load supervision, Belt loss, Over load supervision, Stall prevention LCD DISPLAYBUILT-IN LED BUILT-IN, LCD Optional built-in Setpoint resolution Digital command: 0.01Hz Analog command: 11 bits Digital: 0.01 Hz Analog: 11 bits Digital: 0.003Hz Analog: 10 bits Digital: 0.01Hz energy saving parameterAvailable Comparison of different brands Comparison Chart on Functions DELTA_CP2000 YASGAWA E1000Danfoss_FC102ABB_ACH550
36
Delta Confidential market ECONOMICAL FELXIABLE FOC APPLICATION CASE Variable Torque FANS PUMPS HAVC Normal usage V/F FEEDER Machinery field EXTRUDER ELEVATOR CRANS torque control WINDER TENSION CONTROL Servo characteristic POSITION CONTROL S/M B VL EL F E VFD-CP2000 position VFD-CP2000 VE VJ
37
Delta Confidential CP2000 FIELD APPLICATIONS COOLING PUMP Build Automation (HVAC) BLOWER TOWER FANS COOLING SYSTEM
38
Delta Confidential HVAC
39
Delta Confidential HVAC Drive power segment ApplicationLoadingPower HVACCooling pump2.2 - 37 kW Circulating pump3.7 - 75 kW Fan7.5 - 220 kW Water supplyWater pump2.2 - 75 kW Water circulatingWater pump of atmospheric cooling tower2.2 - 37 kW Water pump for constant pressure7.5 - 220 kW ChillerWater pump7.5 - 75 kW Spray pump1.5 -3.7 kW Thermodynamic systemPump for water supply7.5 - 220 kW Water treatmentWater pump3.7 - 75 kW Applications of public works
40
Delta Confidential Industrial tower blower Main Application: V/F control, energy saving
41
Delta Confidential Exhausted gas treatment system Main application :V/F variable torque control
42
Delta Confidential Air Treatment application Main application :V/F variable torque control
43
Delta Confidential Tunnel Blower Main application :V/F variable torque control
44
Delta Confidential Water Treatment Main application :V/F variable torque control
45
Delta Confidential Thanks