Enhancing The Efficiency Of New And Existing Cooling Systems Dr Robert Lamb CEng FInstR Group Sales & Marketing Director Star Refrigeration Ltd.

Similar presentations


Presentation on theme: "Enhancing The Efficiency Of New And Existing Cooling Systems Dr Robert Lamb CEng FInstR Group Sales & Marketing Director Star Refrigeration Ltd."— Presentation transcript:

1 Enhancing The Efficiency Of New And Existing Cooling Systems Dr Robert Lamb CEng FInstR Group Sales & Marketing Director Star Refrigeration Ltd

2 Why Should I Focus On Enhancing Efficiency?

3

4

5

6 Data taken from DECC – 2012 Energy and Emissions Projection Annex F

7 Total Cost Of Ownership EnergyAftercare

8 Start Measuring

9 Cooling Load What Factors Affect Efficiency? Operating Temperature Equipment Selection Equipment Operation Efficiency

10 Cooling Load What Factors Affect Efficiency? Efficiency

11 What Make Up The Cooling Load? Cooling Load Ambient Temperature Insulation Air/Moisture Ingress Product Load Electrical Load PeopleDefrosting

12 Reducing The Cooling Load Eliminate Poor Door Control Ambient Air = +32°C/70% RH Chamber= +2°C 1m 3 /s air ingress = 101kW Refrigeration CoP= 3 Refrigeration Power= 33.7kW Electrical Cost = £17,695/yr @ 6p/kWhr

13 Reducing The Cooling Load Insulation Thickness Panel Thickness (mm)U Value (W/m 2 K) 500.39 600.31 800.25 1000.2 1250.16 1500.13 1750.11 2000.1 2200.09

14 Reducing The Cooling Load Insulation Thickness

15 Reducing The Cooling Load Free Cooling

16 Reducing The Cooling Load Free Cooling

17 Reducing The Cooling Load Switch To LED Lighting Original Install: 7 x 250W lights Continuous Operation 15,330 kWhr/yr LED Install: 7 x 48W lights Intelligent Operation 2,943 kWhr/yr 24/7 Operation 80% Saving 85% to 90% with intelligent control Improved visibility

18 Cooling Load What Factors Affect Efficiency? Operating Temperature Efficiency

19 Evaporating Temperature

20 Case Study - Room Temperature Change

21

22 Measured Saving At 5 UK DCs

23 Case Study - Room Temperature Change

24 Case Study – Data Centre Chillers

25

26 Condensing Temperature

27 Minimising Condensing Temperature Avoid Air RecirculationKeep Condensers Clean Efficiency Electronic Expansion Valves Time Temperature TEV EEV

28 Cooling Load What Factors Affect Efficiency? Operating Temperature Equipment Selection Efficiency

29 Main Electrical Consumers - Refrigeration PLANTROOM Electrical Consumption Compressor = 90% Condenser= 5% Evaporator(s)= 5%

30 Main Electrical Consumers - Chillers PLANTROOM Electrical Consumption Compressor = 75% Condenser=15% Pump(s) = 10% PUMP SECONDARY CIRCUIT

31 Evaporating Temperature

32 Compressor COP Vs Temperature - Chillers

33

34

35 Compressor Selection - Chillers Screw ChillerCentrifugal Chiller 1MW Chiller For Data Centre Cooling

36 Compressor Comparison - Chillers

37 Cooling Load What Factors Affect Efficiency? Operating Temperature Equipment Selection Equipment Operation Efficiency

38 Compressor VSD Case Study Process Cooling Case Study

39 Compressor VSD Case Study Process Cooling Case Study

40 Compressor VSD Case Study Process Cooling Case Study Pre-InstallInstall PeriodPost-Install

41 Condenser Fans Time Compressor head pressureFan control Without VSDs Temperature Without VSDs Off On 16.6kW On 33.3kW VSDs

42 Cooling System Condenser VSD efficiency OnOff Rejected heat OffOn Efficiency VSD Control

43 Cooling System Condenser VSD efficiency OnOff On Efficiency VSD Control

44 Cooling System Condenser VSD efficiency OnOff On Efficiency VSD Control

45 Condenser VSD Case Study Air Vol (%) Time (%/yr) Power (kW) hr/YrkWhr/yr 10030222,62857,816 751216.51,05117,345 501811.01,57717,345 25155.51,3147,227 02502,1900 Total99,733 Example Calculation: Fan Motor 22 kW Days/Yr 365 Days Hr/Yr 8760 Hrs Inverter Loss 5 % Fixed Speed Operation

46 Condenser VSD Case Study Air Vol (%) Time (%/yr) Power* (kW) hr/YrkWhr/yr 1003023.12,62860,707 75129.71,05110,244 50182.91,5774,553 25150.41,314474 02502,1900 Total75,978 Saving23,754 Example Calculation: Fan Motor 22 kW Days/Yr 365 Days Hr/Yr 8760 Hrs Inverter Loss 5 % Variable Speed Operation * Including Inverter Loss

47 Condenser VSD Case Study SiteTotal Fan Power (kW) Install Price SavingsAdditional Saving * Payback A37£34,828£5,094£1,2455.49 B74£37,464£10,188£1,2803.27 C60£33,494£8,260£1,3903.47 D44£34,028£6,058£1,3354.60 Total£139,814£75,978 Total Estate Estimated Savings 4 Sites 8 Condensers Calculations based on 8.5p/kWhr * Maintenance savings – motors, belts, better control

48 Condenser VSD Case Study Measured savings 13% higher than estimates

49 Reduce Load Summary Raise Operating Temperature Careful Equipment Selection Optimise Equipment Control Improving Efficiency

50 Star Refrigeration – From Humble Beginnings to the Natural Choice Pioneering Natural Refrigeration Technology since 1970 Star Refrigeration – From Humble Beginnings to the Natural Choice More than 300 staff in 11 locations across the UK and a number of agents in Europe and Asia Has expanded from an industrial refrigeration company to a multi- faceted engineering group The largest and most successful independent cooling and heating contractor in the UK Pioneering development of sustainable solutions & natural refrigeration technology

51


Download ppt "Enhancing The Efficiency Of New And Existing Cooling Systems Dr Robert Lamb CEng FInstR Group Sales & Marketing Director Star Refrigeration Ltd."