Enhancing The Efficiency Of New And Existing Cooling Systems Dr Robert Lamb CEng FInstR Group Sales & Marketing Director Star Refrigeration Ltd
2
Why Should I Focus On Enhancing Efficiency?
6
Data taken from DECC – 2012 Energy and Emissions Projection Annex F
7
Total Cost Of Ownership EnergyAftercare
8
Start Measuring
9
Cooling Load What Factors Affect Efficiency? Operating Temperature Equipment Selection Equipment Operation Efficiency
10
Cooling Load What Factors Affect Efficiency? Efficiency
11
What Make Up The Cooling Load? Cooling Load Ambient Temperature Insulation Air/Moisture Ingress Product Load Electrical Load PeopleDefrosting
12
Reducing The Cooling Load Eliminate Poor Door Control Ambient Air = +32°C/70% RH Chamber= +2°C 1m 3 /s air ingress = 101kW Refrigeration CoP= 3 Refrigeration Power= 33.7kW Electrical Cost = £17,695/yr @ 6p/kWhr
13
Reducing The Cooling Load Insulation Thickness Panel Thickness (mm)U Value (W/m 2 K) 500.39 600.31 800.25 1000.2 1250.16 1500.13 1750.11 2000.1 2200.09
14
Reducing The Cooling Load Insulation Thickness
15
Reducing The Cooling Load Free Cooling
16
Reducing The Cooling Load Free Cooling
17
Reducing The Cooling Load Switch To LED Lighting Original Install: 7 x 250W lights Continuous Operation 15,330 kWhr/yr LED Install: 7 x 48W lights Intelligent Operation 2,943 kWhr/yr 24/7 Operation 80% Saving 85% to 90% with intelligent control Improved visibility
18
Cooling Load What Factors Affect Efficiency? Operating Temperature Efficiency
19
Evaporating Temperature
20
Case Study - Room Temperature Change
22
Measured Saving At 5 UK DCs
23
Case Study - Room Temperature Change
24
Case Study – Data Centre Chillers
26
Condensing Temperature
27
Minimising Condensing Temperature Avoid Air RecirculationKeep Condensers Clean Efficiency Electronic Expansion Valves Time Temperature TEV EEV
28
Cooling Load What Factors Affect Efficiency? Operating Temperature Equipment Selection Efficiency
29
Main Electrical Consumers - Refrigeration PLANTROOM Electrical Consumption Compressor = 90% Condenser= 5% Evaporator(s)= 5%
30
Main Electrical Consumers - Chillers PLANTROOM Electrical Consumption Compressor = 75% Condenser=15% Pump(s) = 10% PUMP SECONDARY CIRCUIT
31
Evaporating Temperature
32
Compressor COP Vs Temperature - Chillers
35
Compressor Selection - Chillers Screw ChillerCentrifugal Chiller 1MW Chiller For Data Centre Cooling
36
Compressor Comparison - Chillers
37
Cooling Load What Factors Affect Efficiency? Operating Temperature Equipment Selection Equipment Operation Efficiency
38
Compressor VSD Case Study Process Cooling Case Study
39
Compressor VSD Case Study Process Cooling Case Study
40
Compressor VSD Case Study Process Cooling Case Study Pre-InstallInstall PeriodPost-Install
41
Condenser Fans Time Compressor head pressureFan control Without VSDs Temperature Without VSDs Off On 16.6kW On 33.3kW VSDs
42
Cooling System Condenser VSD efficiency OnOff Rejected heat OffOn Efficiency VSD Control
43
Cooling System Condenser VSD efficiency OnOff On Efficiency VSD Control
44
Cooling System Condenser VSD efficiency OnOff On Efficiency VSD Control
45
Condenser VSD Case Study Air Vol (%) Time (%/yr) Power (kW) hr/YrkWhr/yr 10030222,62857,816 751216.51,05117,345 501811.01,57717,345 25155.51,3147,227 02502,1900 Total99,733 Example Calculation: Fan Motor 22 kW Days/Yr 365 Days Hr/Yr 8760 Hrs Inverter Loss 5 % Fixed Speed Operation
46
Condenser VSD Case Study Air Vol (%) Time (%/yr) Power* (kW) hr/YrkWhr/yr 1003023.12,62860,707 75129.71,05110,244 50182.91,5774,553 25150.41,314474 02502,1900 Total75,978 Saving23,754 Example Calculation: Fan Motor 22 kW Days/Yr 365 Days Hr/Yr 8760 Hrs Inverter Loss 5 % Variable Speed Operation * Including Inverter Loss
47
Condenser VSD Case Study SiteTotal Fan Power (kW) Install Price SavingsAdditional Saving * Payback A37£34,828£5,094£1,2455.49 B74£37,464£10,188£1,2803.27 C60£33,494£8,260£1,3903.47 D44£34,028£6,058£1,3354.60 Total£139,814£75,978 Total Estate Estimated Savings 4 Sites 8 Condensers Calculations based on 8.5p/kWhr * Maintenance savings – motors, belts, better control
48
Condenser VSD Case Study Measured savings 13% higher than estimates
49
Reduce Load Summary Raise Operating Temperature Careful Equipment Selection Optimise Equipment Control Improving Efficiency
50
Star Refrigeration – From Humble Beginnings to the Natural Choice Pioneering Natural Refrigeration Technology since 1970 Star Refrigeration – From Humble Beginnings to the Natural Choice More than 300 staff in 11 locations across the UK and a number of agents in Europe and Asia Has expanded from an industrial refrigeration company to a multi- faceted engineering group The largest and most successful independent cooling and heating contractor in the UK Pioneering development of sustainable solutions & natural refrigeration technology