Download presentation
Presentation is loading. Please wait.
Published byBrian Morrison Modified over 8 years ago
1
Variable Speed Fire Pump Controllers - by - James S. Nasby Columbia Engineering
2
C.E.2 Topics to be Covered VFD and Controller Elements VFD Characteristics Primary (Desired) Effects on Motor Secondary (Undesired) Effects On Motor On Power Grid (Mains) System Characteristics & Effects Motor Requirements Applications Testing
3
C.E.3 Model ECV-250-46-* 250 Hp – Single Source A.T.L Start in Bypass
4
C.E.4 Model ECV-250-46-* 250 Hp – Single Source A.T.L Start in Bypass
5
C.E.5 Model ECVRTZ-100-46-*
6
C.E.6 Inside View of Drive Bay D.C. Link Reactor Line Reactor Cooler CPT & Fuses
7
C.E.7 Vocabulary VFD = Variable Frequency Drive AFD = Adjustable Frequency Drive VSD = Variable Speed Drive ASD = Adjustable Speed Drive,“Inverters”, “A.C. Drives”, "Drive" Note: The above are all the same for our purposes. IGBT = Insulated Gate Bipolar Transistor “VFD” will refer to the Drive Unit Proper PWM = Pulse Width Modulation dV/dt = Voltage Rise Time (dU/dt in Europe)
8
C.E.8 Vocabulary – cont’d IGBT "Soft Switching" Reduces = dV/dt Reducing Motor Spikes (GE/Figi) PWM = Pulse Width Modulation (Used on All Modern VFDs) PID = "Proportional – Integral – Differential" Set Point Controller or Control Scheme
9
C.E.9 Vocabulary – cont’d Inverter Duty Motor Higher Winding Insulation Dielectric Strength (Breakdown Voltage), Typically 1200 Vac Extra Thermal Capacity by way of: 1.15 Service Factor and/or Higher Insulation Class (Such as 155°C instead of 130°C) Mitigate Bearing Currents by way of: Insulated Bearings Brushes to Drain (Bypass) Currents Around Bearings
10
C.E.10 Vocabulary – cont’d Constant Torque Rating: For Mills and Take- up Reel Drives and Positive Displacement (Piston) Pumps Where Rated Torque is Needed at Zero (or Near Zero) Speed. Variable Torque Rating: For Fans, Blowers, Centrifugal Pumps & etc. Where the Load Torque Varies with Speed (RPM). E.g.: Low Torque at Zero (and Near Zero) Speeds.
11
C.E.11 Vocabulary – cont’d Set-Point = Desired Outcome (e.g.: Desired Pressure) System Response May Be One: Oscillatory Under Damped Critically Damped (with or w/o Overshoot) Over Damped
12
C.E.12 System Response Curves Under Damped Oscillatory (With Overshoot) Over Damped Critically Damped
13
C.E.13 Required Controller Elements Controller Must be a Full Service Controller Plus a VFD Unit Plus VFD Fuses (at <299% of FLA) Plus Load Side Isolation Contactor (interlocked) Plus Line Side Isolation Contactor Plus By-Pass (Main) Contactor All Fully Rated (Horsepower Rated) Line Reactor - 5% Minimum to: Reduce Line Current Harmonics Reduce Line Transients to the VFD Reduce Capacitor Over-voltage Shutdown due to Line Spikes and/or Surges Note: All line spikes and surges get rectified regardless of where they appear on the Waveform.
14
C.E.14 Required Controller Elements - cont'd Mechanical Interlock Between Bypass Contactor and VFD Output Contactor to Prevent Back Feeding VFD on Controller Defect since this will cause the Main Fire Pump Circuit Breaker (C/B) to Trip. This causes the Fire Pump to be off line (dead). Means to Lock VFD and Starting Parameters Typical VFD has over 150 settable parameters, many of which will cause damage or no fire water if mis-set PID to Control Pressure Must be able to Control Time Constants and Dynamic Characteristics to Avoid Cycling or Hydraulic System Damage
15
C.E.15 Power Circuit Schematic * Was Optional
16
C.E.16 VFD OCP Fuses and view of VFD Sans Cover
17
C.E.17 Schematic Diagram Single Source A.T.L. (D.O.L.) Starting in Bypass Mode Low to Moderate Horsepower Note Mechanical Interlock (Mech Intk) Between R1 and BP Contactors.
18
C.E.18 Line Reactor and 2nd Cooler
19
C.E.19 Two Coolers for 300 Hp VFD Note: this unit sees regular service a pump company pump test facility.
20
C.E.20 Must Include a Complete Full Service Fire Pump Controller Standard Full Service Circuitry and Components Standard Mechanical Manual Operator Mode Switch for Full Speed Bypass Operation Easier Commissioning, Servicing and for Back-up Automatic Fire Protection Standard Pressure Switch/Transducer Bypass and Start use the Same Switch -or- Separate Swtiches used (some Mfrs) Separate (2nd) Transducer for Recording (one Mfr.)
21
C.E.21 Close-up of Pressure Switch and Both Pressure Transducers
22
C.E.22 External Wiring Diagram
23
C.E.23 Optional Controller Elements Line Side EMI / RFI (EMC) Filter Load Side (Motor) Output Reactor Load Side (Motor) dV/dt Filter D.C. Link Reactor (Standard with Some) Advanced Operator Display Panels Network Connection
24
C.E.24 VFD – Principles of Operation Three Main Sections: Three Phase Rectifier Section (AC/DC) D.C. Filter Section - D.C. Bus Capacitors (Bus Cap’s) Inverter Section (DC/AC): Pulse Width Modulator (PWM) Modern VFD’s use IGBT’s for Inverter Inverter Typically Runs at 2 to 6 Kilohertz
25
C.E.25 VFD = Motor Running Only (No Motor Starting Region) Typical Motor Torque and Pump Torque Curves
26
C.E.26 Lower Frequency Shortens Curve This point Moves Left Relative to Frequency 100% = 60 Hz or 59 or 30 or any Frequency
27
C.E.27 3 Phase Line Freq. AC / DC Smoothing DC / AC At “X” Khz VFD – Principles of Operation Modulation Frequeny Typically 2 to 10 Khz
28
C.E.28 PWM Basic VFD Voltage Waveform Pulse Mode Modulation at 2.0 to 10.0 Khertz 2 Khz One Cycle
29
C.E.29 PWM Motor Voltage Waveform with No Filtering
30
C.E.30 PWM Motor Voltage Waveform with Load (Motor) Reactor
31
C.E.31 PWM Motor Voltage Waveform with Motor Filter
32
C.E.32 Motor Electrical Measurements Special Metering Required due to the High Voltage and Frequency
33
C.E.33 Controller Operation 1) Pressure Switch Trips 2) Contactor R1 and R2 Close 3) Signal VFD to Start 4) Begin Timing for VFD Ready Signal (3-5 Sec.) 5) Begin Pressure Switch Tripped Timing (approx. 20 Seconds) 6) VFD Sends “Drive Ready” Signal -or-
34
C.E.34 Controller Operation – cont’d 7) Bypass Operation Begins after Restart Delay -- or -- 8) VFD Begins Motor Acceleration 9) VFD adjust motor speed to Achieve Desired Pump Pressure Set-Point 10) Pump Builds Up Sufficient Pressure to Reset the Pressure Switch within 20 Seconds -or- 11) Begin Bypass Operation (Same as # 7 above)
35
C.E.35 Controller Operation – cont’d 12) VFD Modulates Motor Speed Using its PID to Maintain System Pressure at Desires Set- Point Even with Flow and Suction Pressure Fluctuations -or- 13) Pressure Switch Re-Trips and Pressure Switch Tripped Timer Begins Timing Cycle (Again) 14) After 20 Seconds, By-Pass Operation Begins (same as #7 above) 15) By-Pass Operation is Manual Reset
36
C.E.36 Bypass Starting Methods Full Voltage (A-T-L) Primary Reactor Soft Starter Some Controllers also Provide Soft Stop (extra circuitry needed for the Soft Stop Function) Some Units will Ramp Up to at Lease an Idle Speed and continue to increase speed until the pressure demand is met.
37
C.E.37 VFD Starting Characteristics All VFDs provide Soft Starting (Ramp-up) Max. Torque/Current can be set 150% Starting and 110% Running are Typical System Must be Suitable for Bypass Mode Starting Some Controllers also Provide Soft Stop (extra circuitry needed for the Soft Stop Function) Some Units will Ramp Up to at Lease an Idle Speed and continue to increase speed until the pressure demand is met.
38
C.E.38 Design Considerations Capacitor Overvoltage Shutdown This is a Lockout Condition, Manual Reset is always Required. 480 Vac x 1.414 = 678 + 10% = 747 Vac. Better VFD's don't shut down until the capacitor voltage exceeds 800 Vac. Lesser ones shutdown at 750 Vac or less. VFD Shutdown Temperature. Better VFDs don't shutdown until 70ºC and can be restarted with no damage or degradation VFD Pollution Degree Requirements must be met. Cooling should be Closed Loop (no Venting Pump Room Air into Controller.
39
C.E.39 Design Considerations - cont'd VFD OCP Must be Fully Selectively Coordinated with the Main Fire Pump Circuit Breaker (C/B) Said OCP will Most Likely be Fuses Coordination with the is Critical to Avoid Tripping which Kills the Bypass Mode. Fuses (OCP) must trip before the 300% point Fuses must trip in less than 8 seconds at Locked Rotor Current Fuses must still be large enough to hold with the Maximum normal VFD input current including harmonic content. The Fuse curve must never touch the C/B curve to avoid any risk of tripping. Fuse tolerance must also be considered. The plus tolerance on the fuse curve can lead to tripping of the F.P. C/B.
40
C.E.40 Design Considerations - cont'd Fuses must be calculated for Each and Every controller Hp and Voltage (E.g.: Each nominal FLA). Controller cooling must keep the VFD within is maximum rated temperature. A 50ºC VFD will require the cooling to keep the temperature rise to no more than 10ºC for a Controller Rated Maximum Temperature of 40ºC. A VFD rated at only 40ºC will require de-rating unless refrigeration is allowed.
41
C.E.41 Design Considerations - cont'd Polution Degree Rating of the VFD must not be exceeded. This will typically require a non- vented NEMA 12 (U.L. Type 12) or better enclosure and cooling means. Internal Controller Wiring in the VFD input path must be sized for the harmonic content of the VFD. Successful Installations the Mfr. to ascertain and check the system hydraulic time constants and set the PID parameters accordingly.
42
C.E.42 Application Considerations Additional Considerations: * The controller is UL listed for fire pump applications. * The enclosure is rated for NEMA 12. * Maximum ambient must not exceed controller (marked) rating. * Mfr's vent air clearance spaces and service spaces must be adheared to. * The motor must be suitable for use with a variable speed drive. * Motor current draw must not exceed 100% of FLA, even though the motor may have a 1.15 or higher service factor * A gen-set must be suitable for use with a variable speed drive. * The power source must be capable of bypass mode Starting method. * The pump and motor must be rigidly coupled. * The pump and motor must be properly grouted. * A relief valve is required for emergency operation unless system pressure can not be exceed at churn and full speed and max. suction pressure.
43
C.E.43 Multi-Acre Multi- Building Campus …
44
C.E.44 …and Back-up Distant Water Supply…
45
C.E.45 Lead to Multiple System Time Constants Note 253 Second Chart Span
46
C.E.46 Note 151 Sec. Chart Span Lead to Multiple System Time Constants
47
C.E.47 Note 86 Sec. Chart Span Lead to Multiple System Time Constants
48
C.E.48 Note 63 Sec. Chart Span Lead to Multiple System Time Constants Estimated 25s, 20s, 4s, 2s & ?? Hydraulic Time Constants
49
C.E.49 Unit Testing Small Unit after High and Low Temp. Testing: Ta < 0ºC and Ta > 60ºC Thermocouple Switch Box on top of unit.
50
C.E.50 Unit Testing
51
C.E.51 Unit Testing - 350 Hp Unit
52
C.E.52 Unit Testing - 350 Hp Unit
53
C.E.53 Unit Testing - 350 Hp Unit
54
C.E.54 Unit Testing - 350 Hp Unit
55
Questions?
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.