Turbo-Brayton cryogenic systems Refrigeration for scientific applications ICEC – Delhi – March 10 th 2016 - Cécile Gondrand
2
2 Air Liquide, world leader in gases for industry, health and the environment Outline ■Introduction From classical Brayton to Turbo-Brayton ■Turbo-Brayton range ■Turbo-Brayton status References TBF-350 under construction ■Example of use of Turbo-Brayton for thermal shields cooling Solutions proposed Comparison CAPEX/OPEX of solutions ■Conclusion
3
3 Air Liquide, world leader in gases for industry, health and the environment From conventional Brayton to Turbo-Brayton LNG M Eau Water M Eau LNG Water
4
4 Air Liquide, world leader in gases for industry, health and the environment From conventional Brayton to Turbo-Brayton ■The only rotating part of the system is the Moto-turbo- Compressor shaft M Eau LNG High efficiency No maintenance High reliability High lifetime Water
5
5 Air Liquide, world leader in gases for industry, health and the environment From conventional Brayton to Turbo-Brayton
6
6 Air Liquide, world leader in gases for industry, health and the environment Turbo-Brayton - Range ■The product line is composed of standard products for refrigeration TBF : Turbo-Brayton Fridge Product rangeTBF-80TBF-175TBF-350TBF-700TBF-1050 Cold power at 77K kW7,616,550,8101,6152,4 Electrical consumption85kW195 kW390 kW780 kW1 170 kW
7
7 Air Liquide, world leader in gases for industry, health and the environment Turbo-Brayton - Range ■The product line is composed of standard products for refrigeration TBF : Turbo-Brayton Fridge Product rangeTBF-80TBF-175TBF-350TBF-700TBF-1050 Cold power at 77K kW7,616,550,8101,6152,4 Electrical consumption85kW195 kW390 kW780 kW1 170 kW
8
8 Air Liquide, world leader in gases for industry, health and the environment Turbo-Brayton – References Turbo Brayton references ■ISS project : TBF -- 100W@ -80°C installed into ISS 100,000 hours without maintenance nor failures ■LIPA II project: TBF-80 -- 13kW@ 110K ■Institute 401: TBF-80 -- 18kW @ 150K ■Shell STX: TBF-350 – 48kW@110K ■US: TBF-350 – 30kW @ 70K Turbine, magnetic bearing and Brayton references ■600 gas-turbines running on industrial plants, Helium, HyCo, Hydrogen, Natural gas ■50 cryogenic turbomachines on magnetic bearings ■200 cryogenic plants, installed over the world on the past 50 years
9
9 Air Liquide, world leader in gases for industry, health and the environment Turbo-Brayton – Status of TBF-350 Turbomachine 270kW ■Assembly of turbomachine is completed ■Run tests at full speed performed TBF-350 refrigerator ■Manufacture is on-going
10
10 Air Liquide, world leader in gases for industry, health and the environment Case study ■Case study need 800W@4.5K Thermal shields cooling : 23kW@80K ■3 architectures compared Option AHelial* for 4.5K refrigeration and independent LN2 cooled cold box for thermal shields Option BHelial* for 4.5K and independent Turbo-Brayton for thermal shields cooling Option CHelial* for 4.5K + thermal shields cooling * Helium Liquefier/Refrigerator standard range of Air Liquide
11
11 Air Liquide, world leader in gases for industry, health and the environment Case study – Option A – Thermal shields cooled by LN2 - PFD ■Advantages Two independant loops=> high flexibility to deal with different loads at 80K and 4,5K Possibility to add a TBF for LN2 reliquefaction without changing design of thermal shiled CB=> flexibility ■Drawbacks Two cold boxes : one for 4K refrigeration and one for thermal shields Additional circulator
12
12 Air Liquide, world leader in gases for industry, health and the environment Case study – Thermal shields cooled by LN2 ■Possibility to have TBF refrigerator operating as nitrogen reliquefier Possibile retrofit
13
13 Air Liquide, world leader in gases for industry, health and the environment Case study – Option B - Thermal shields cooled by TB - PFD ■Advantages Two independant refrigerators => high flexibility to deal with different loads at 80K and 4,5K ■Drawbacks Two cold boxes : one for 4K refrigeration and one for thermal shields Additional refrigerator including circulator
14
14 Air Liquide, world leader in gases for industry, health and the environment Case study – Option C - Thermal shields cooled by Helial - PFD ■Advantages One single refrigeration system ■Drawbacks Cycle compressor sized on thermal shields flow rate requirement Cold box size much higher Coupling of 80K and 4.5K cold power => lower flexibility
15
15 Air Liquide, world leader in gases for industry, health and the environment Case study – CAPEX+OPEX in 10 years Solution A - Thermal Shields cooled by LN2 Solution B - Thermal Shields cooled by Turbo-Brayton Solution C - Thermal shields cooled by one single refrigerator OPEX Operation time/year8000 h/year Years of operation10 years Cost per kWh0,1 €/kWh Electrical cost2,06 M€3,82 M€6,11 M€ Cost per L of LN20,15 €/L LN2 cost5,50 M€0,00 M€5,50 M€ TOTAL 10 years7,56 M€3,82 M€11,61 M€
16
16 Air Liquide, world leader in gases for industry, health and the environment Case study – Cost in time
17
17 Air Liquide, world leader in gases for industry, health and the environment Turbo-Brayton – Conclusion ■A wide range of Turbo-Brayton refrigerators is available 35 - 150 K 0 - 152 kW @ 77K ■TBF-350 manufacture is on-going Highest power turbomachines ever designed/manufactured by ALAT have been commissioned/validated Test of full integrated refrigerator planned in May 2016 ■Concrete case study shows the advantage of using TBF for thermal shields cooling 80K refrigeration totally independent of 4K refrigeration => flexibility of operation Highly efficient solution with TBF reducing total CAPEX and OPEX Most cost-effective solution after 6-years operation
18
Thank you for your attention cecile.gondrand@airliquide.com