1
IECC 2012 Standard 90.1 2010 Lee Brandt, LC, IALD, LEED AP BD+C Principal HLB Lighting Design
2
Update on: Codes in use as of 1/1/2015 Changes from IECC 2009 to 2012 (Commercial) Changes from Std. 90.1 2007 to 2010 (“Commercial”) NY State amendments to the base codes NY City amendments to State items and base codes
3
2010 ECCCNYS [Energy Conservation Construction Code of New York State] IECC 2009 Standard 90.1 2007 2011 NYCECC [ New York City Energy Conservation Code] [Local Law 1 2011] LL48 2010 (occ/vac sensors) LL86 (2005) (LEED Silver for City funded buildings)
4
NYS Residential Energy Code 2010 ECCCNYS IECC 2009 NYC unchanged until NYS changes
5
NYS Commercial Energy Code 2014 Supplement to the New York State Energy Conservation Construction Code Reference Standards: IECC 2012 / Standard 90.1 2010 (alternate path) NYC Energy Conservation Code Modifications to the State supplement
6
NYS http://www.dos.ny.gov/dcea/energycode_code.html NYC http://www.nyc.gov/html/dob/html/codes_and_reference _materials/nycecc_main.shtml
7
Effective Date 1/1/15
9
Changes in IECC 2012 & Standard 90.1 2010 LPD’s decreased – both codes IECC Space by Space is back IECC’s Mandatory Additional Efficiency Package Options 15% under Building Area LPD’s Alterations IECC = 50% threshold Standard 90.1 = 10% threshold
10
NYS Amendments IECC – improved exterior control requirement language IECC – improved track and busway language and wattages to use IECC – slightly altered language for dwelling units within commercial buildings 90.1 - Made some Mandatory control and power requirements Prescriptive
11
NYC Amendments 90.1 – Dwelling Units within commercial buildings now have to comply!!! Reference IECC language IECC and 90.1 – incorporated LL48 language on occupancy and vacancy sensors.
12
NYS - IECC 2012 Prescriptive Efficiency Options NYS - IECC 2012 Performance Building energy cost < 85% of reference building NYS – IECC 2012 Environmental Trade Off Std. 90.1 2010 Prescriptive Std. 90.1 2010 Performance (2 paths) Std. 90.1 2010 Environmental Trade Off New York City NYS - IECC Performance Path removed
13
IECC 2012 – SECTION Mandatory or Prescriptive Code Requirement more STD. 90.1 - SECTION Mandatory or Prescriptive Code Requirement more New York State AND/OR New York City Amendments In these special boxes
15
IECC 2012 – C402.3.1 Prescriptive: 30% Max OR 40% Max when >50% conditioned floor area in daylight zone Automatic daylighting controls installed Certain VT requirements STD. 90.1 - 5.5.4… Prescriptive 40% (5.5.4.2.1) (No change from 2007) Limits fenestration on East & West facing walls (5.5.4.5)
16
Benefits of daylighting = 0
17
Use Performance Paths!
18
IECC 2012 – C402.3.2 Prescriptive: Directly under roof w/ ceiling >15’ Spaces > 10,000 sq ft Certain space types Daylight zone / area requirements associated with Skylights Multi-level lighting controls (C405.2.2.3.3) STD. 90.1 - 5.5.4.2.3 Prescriptive: Building < 4 stories Spaces > 5,000 sq ft Certain space types Daylight zone / area requirements associated with Skylights Multi-level lighting controls (9.4.1.5)
19
IECC 2012 No requirements STD. 90.1 – 8.4.1 Mandatory: 2% for feeders 3% for branch circuits New York State & NYC PRESCRIPTIVE rather than mandatory
20
IECC 2012 No requirements STD. 90.1 – 8.4.2 Mandatory: 50% in offices (private and open) and computer classrooms New York State & NYC PRESCRIPTIVE rather than mandatory
22
IECC 2012 – C405.1 > 75% of permanently installed light fixtures shall use high efficacy lamps Does not include low voltage lighting! High Efficacy = CFL <T8 linear fluor >60 lumens / watt for > 40 watt lamp STD. 90.1 – 9.1 Excepted New York City DWELLING UNITS ARE NOT EXCEPTED!! They do not have to apply with Lighting Section if they meet IECC language
23
IECC 2012 – C405.7 Individual dwelling units shall have separate meters STD. 90.1 – N/A
24
IECC 2012 – C101.4.3 Exception for <50% replacement of luminaires in a space as long as power is not increased Replacement of lamps + ballasts ok if LPD not increased STD. 90.1 – 9.1.2 Exception for <10% of connected lighting load such that LPD is not increased All other alterations must comply with LPD and auto shutoff (9.4.1.1) Including lamps + ballasts
26
IECC 2012 – C405.2.2.1 Automatic Time Switch controls shall be installed Exception for areas with occupancy sensors. STD. 90.1 – 9.4.1.1 Automatic Controls to shut off interior lighting shall be installed Time of day Occupant sensor Signal from other system indicating unoccupied space
27
IECC 2012 – C405.2.1 Manual lighting controls required in all areas (some exceptions) 50% reduction in each area No change from IECC 2009 Important exceptions STD. 90.1 – 9.4.1.2 Manual lighting controls required in all spaces (some exceptions) Each area with manual control shall have one control step between 30 and 70% in addition to off. Can be accomplished with dimming, step ballast, zoning
28
IECC 2012 – C405.2.2.2 Mandatory – Required in: Classrooms Conference / Meeting Rooms Employee lunch and break rooms Private offices Restrooms Storage Rooms Janitorial Closets Spaces< 300 sq. ft Auto-off within 30 min Manual or Auto ON Auto ON only if <50% power or OK for 100% on in corridors, stairwells, restrooms, entrance areas, and lobbies STD. 90.1 – 9.4.1.2 Mandatory – Required in: Classrooms / Lecture Halls Conference / Meeting / Training Rooms Employee lunch and break rooms Offices up to 250 sq ft Restrooms Storage and Supply rooms (50 – 1000 sq ft) Copy/Print rooms Dressing / Locker / Fitting Rooms Auto-off within 30 min Manual or Auto ON Auto ON only if <50% power or OK for 100% on in corridors, stairwells, restrooms, entrance areas, and lobbies New York City amendments LL48 – next slide
29
NYC – affects both NYS / IECC and Std. 90.1 Mandatory – Vacancy Sensors – manual on, auto off. (No override that can change them to auto on.) Required in: Classrooms (not shop, lab, or preschool) Conference / Meeting Rooms Employee lunch and break rooms Private offices <200 sq.ft. There can be a 30 second grace period to for sensor to turn lights back on automatically if occupancy is detected Auto-off within 30 min Mandatory – Occupancy Sensors – auto on, auto off. Required in: Restrooms Storage Rooms Private offices >200 sq. ft. Janitorial Closets Spaces< 300 sq. ft AUTOMATIC ON SHALL NOT TURN ON MORE THAN 50% POWER Full (100%) on allowed in public corridors, stairways, restrooms, entries and lobbies & where determined manual on would be safety issue IF MANUAL-ON, FIXTURES CAN COME ON TO 100%
30
IECC 2012 – C405.2.2.3 Mandatory Independent control via Manual control OR Automatic control with continuous or stepped dimming (optional unless increased WWR C402.3.1) Daylight control zone <2,500 sq ft area STD. 90.1 – 9.4.1.4 Mandatory Separate control via Automatic control with continuous or stepped dimming (3 steps required) Primary sidelighted areas >250 sq ft Toplighted areas > 900 sq ft New York State & NYC Changes sidelighting requirements to PRESCRIPTIVE. (Toplighting remains mandatory)
31
STD. 90.1IECC Daylighting Zone Depth = 15’ Width = window width +2’ on each side Or to nearest partition Primary Daylight Zone Depth = Window Height (floor to header) Width = window width +2’ on each side Or to nearest partition
32
STD. 90.1IECC http://lightingcontrolsassociation.org/
33
STD. 90.1IECC Daylighting Zone Area = skylight dimension + floor to ceiling height Or nearest partition Or half way to adjacent skylight or vertical fenestration Toplighting Zone Skylight area + 0.7 x ceiling height Or to nearest obstructing partition Or to sidelighted zone
34
STD. 90.1IECC http://lightingcontrolsassociation.org/
35
STD. 90.1 - 9.4.1.6IECC - C405.2.3 Mandatory - Same as IECC 2009 – Dedicated control for Display/Accent, Case, Guest Rooms, Task, Non- visual and Demonstration Mandatory - Same as 90.1 2007 – Dedicated control for Display/Accent, Case, Guest Rooms, Task, Non- visual and Demonstration New: Stairwells = automatically reduce lighting to 50% power within 30 min of inactivity
36
IECC 2012 – C405.2.4 Mandatory – controlled via photosensor and time switch OR astronomical time switch. STD. 90.1 – 9.4.1.7 Mandatory – automatic control to keep lights off when sufficient daylight available Façade and landscape lighting Auto shut-off b/t midnight or business closing and 6am or business opening All other exterior lighting including signage shall be controlled automatically to reduce connected load by 30% From midnight to 6am (or within one hour of business close / open) Any period of inactivity > 15 min New York State and NYC Use Standard 90.1 2010 language
37
DOE Lighting Development, Adoption and Compliance Guide
38
Std. 90.1 only – 9.4.1.3 Daylight Transition Zone 20’ Daylight Control Zone 3,600 sq ft max control zone Mandatory – Garage must have automatic shut off controls (9.4.1.1) Occupancy sensor to decrease power of each luminaire by 30% <3600 sq ft zone Daylight transition zone, separate control – auto on at daylight, off at sunset Daylight responsive lighting zone within 20’ of perimeter wall
39
IECC 2012 - C408.3STD. 90.1 – 9.4.4
40
No change, still required STD. 90.1 – N/AIECC - C405.3 New York State & NYC Requirement is deleted
41
Reduced LPD’s from 2009 Space by Space table is back! Includes some wattage for decorative fixtures No decorative allowance STD. 90.1 – 9.5 AND 9.6IECC - C405.5.2 Reduced LPD’s from 2007 Added Room Cavity Ratio allowance for tall and unique shaped rooms
42
STD. 90.1 – TABLE 9.6.2IECC – N/A Additional control methods – in addition to Mandatory controls = extra wattage Specific conditions and applications NYS and NYC prescriptive items on controls may help here!
43
Efficacy of luminaire >60 lumens / watt for all fixtures >100 watts Unless controlled by motion sensor STD. 90.1 – N/AIECC - C405.6.1 New York State & NYC Requirement is deleted
44
New table Lighting Zones Tradable / Non-tradable Matches Std. 90.1 STD. 90.1 – 9.4.3IECC - C405.6 Same table as Addendum I to Std. 90.1 2007 Lighting Zones Has LZ0 Tradable / Non-tradable
45
STD. 90.1 – 9.4.2IECC - C405.4 Internally illuminated <5 watts per face Internally illuminated <5 watts per side
46
IECC 2012 – C406 Mandatory for New Construction (?) Additional Efficiency Package Options! Project must chose 1 Efficient HVAC equipment ($$) Efficient Lighting System On-site renewable energy ($$$$$) Lighting may be the common choice Building Area Type table with 15% reduction STD. 90.1 No requirement
47
Changes in IECC 2012 & Standard 90.1 2010 LPD’s decreased – both codes IECC Space by Space is back IECC’s Additional Efficiency Package Options 15% under Building Area LPD’s Alterations IECC = 50% threshold Standard 90.1 = 10% threshold
48
NYS Amendments IECC – improved exterior control requirement language IECC – improved track and busway language and wattages to use IECC – altered language for dwelling units within commercial buildings 90.1 - Made some Mandatory control and power requirements Prescriptive
49
NYC Amendments 90.1 – Dwelling Units within commercial buildings now have to comply!!! IECC language IECC and 90.1 – incorporated LL48 language on occupancy and vacancy sensors. IECC’s Additional Efficiency Package Options 15% under Building Area LPD’s
50
Lee Brandt, LC, IALD, LEED AP BD+C Principal HLB Lighting Design