Presentation is loading. Please wait.

Presentation is loading. Please wait.

Free Cooling Application for Energy Savings at Purdue

Similar presentations


Presentation on theme: "Free Cooling Application for Energy Savings at Purdue"— Presentation transcript:

1 Free Cooling Application for Energy Savings at Purdue
Jim Braun Travis Horton Bonggil Jeon Rita Jaramillo September 2012

2 Overview Problem Statement Background Northwest Chiller Plant Overview
Free Cooling Plume abatement Preliminary Findings Free Cooling Approach Free Cooling Modeling Cooling Tower Modeling Northwest Plant Free Cooling Model Results Free Cooling Performance with All CT Free Cooling Performance with Concrete CT Economic comparison Conclusions Next Steps

3 Problem Statement Cooling is required in the winter months at Purdue
2010 Average ~6,000 Ton Peak cooling load for a typical house in Indiana = 3 Ton Outdoor air temperature less than chilled water supply temperature (~47F) ~$3,000 /day

4 Problem Statement Why do we need cooling during the winter?
150+ Buildings on campus Fact: Cooling from October to May is done exclusively at Wade Power Plant.

5 Problem Statement Wade Power Plant

6 80% of winter cooling done by Steam Chillers
Problem Statement Winter Cooling and Heating is provided by Wade Power Plant 80% of winter cooling done by Steam Chillers

7 Northwest Chiller Plant
Problem Statement Northwest Chiller Plant Wade Power Plant

8 Northwest Chiller Plant
Problem Statement Northwest Chiller Plant Plume Effect Northwest Chiller Plant only supplements additional cooling during the summer. Northwest Plant could potentially be utilized for free- cooling during the winter months. Issues related to cold weather operation of cooling towers: Plume effect Water freezing

9 Problem Statement Is it feasible to operate the Northwest Plant in free cooling mode during the coldest months of the year? What are the modifications and costs for implementing free cooling technology at the Northwest Plant? What are the modifications of the cooling towers for cold weather operation? What are the performance characteristics and economic benefits of free cooling implementation at Northwest Plant?

10 Northwest Chiller Plant Overview
Cooling Towers Electric Chillers System Pumps

11 Northwest Chiller Plant Overview
Electric Chillers

12 Northwest Chiller Plant Overview
Concrete Cooling Tower

13 Northwest Chiller Plant Overview
Metal Cooling Towers

14 Northwest Chiller Plant Overview
Chilled Water Flow Schematics

15 Northwest Chiller Plant Overview
Condenser Water Flow Schematics

16 What is Free Cooling? Technology that utilizes low ambient air to cool the water in a chilled water system. Cooling without operating the compressor of a centrifugal liquid chiller (ASHRAE). Favorable Facility Conditions Cooling demand is require throughout the year High Internal Heat gains due to equipment, lighting, Solar glazing, people, etc… 3,700 + hours where outdoor temperature is below chilled water supply (47F). Chiller

17 Plate Frame Heat Exchanger System
Free Cooling Method Plate Frame Heat Exchanger System Simple installation No compromise to chiller operation No contamination of chilled water Easy change over Requires lowest condenser water temperature Larger footprint for additional equipment CWS pump sized to handle additional resistance

18 Plume Abatement Plume prediction using psychrometric chart (ASHRAE 2008) Plume abatement methods Heating the tower exhaust with natural gas burners. Heating the tower exhaust with hot-water or steam coils. Installing precipitators. Spraying chemicals at the tower exhaust . ClearSky and Air2Air (SPX Technologies). Hybrid wet-dry cooling tower (SPX Technologies) Air leaving tower 2 Indicates fog will form Air entering tower 1

19 Preliminary Findings Description Unit 2009 2010 2011
Potential free cooling hours (Twb<45°F) hr 3,862 3,779 3,840 Free cooling potential ton-hr 22,237,252 19,712,398 18,997,609 Total campus cooling load 93,336,089 90,608,510 93,154,092 Free cooling percentage % 23.8 21.8 20.4 Description Unit 2009 2010 2011 Potential free cooling hours hr 3,862 3,779 3,840 Free cooling potential ton-hr 22,237,252 19,712,398 18,997,609 Total campus cooling load 93,336,089 90,608,510 93,154,092 Free cooling percentage % 23.8 21.8 20.4

20 Free Cooling Approach Cooling towers performance modeling
Cold well T = 47F T ~ 54.5F Cooling towers performance modeling NW Plant FC performance modeling Heat Exchanger sizing Economic comparison

21 Cooling Tower Modeling
How much cooling capacity can the cooling towers deliver at different wet bulb temperatures? Data from performance curves Mathematical Model in EES 𝑵𝑻𝑼=𝒇 𝑾𝒂𝒕𝒆𝒓 𝒇𝒍𝒐𝒘 𝒓𝒂𝒕𝒆 𝑨𝒊𝒓 𝒇𝒍𝒐𝒘 𝒓𝒂𝒕𝒆 Performance Modeling in TRNSYS

22 Cooling Tower Modeling
Concrete Counter-flow Cooling Tower Model Fitting

23 Cooling Tower Modeling
Metal Cross-flow Cooling Tower Model Fitting

24 Cooling Tower Modeling
Schema of the model built in TRNSYS Water at 51°F Ambient air Relative Humidity 50% Wet bulb temperature varies Description Concrete CT Metal CT Number of cells 3 9 Inlet water flow rate per cell 6,000 gpm 2,567 gpm Air flow rate per cell 497,012 cfm 250,100 cfm

25 Cooling Tower Modeling
Maximum Capacity of All Cooling Towers

26 Northwest Plant Free cooling model
Schema of the model built in EES Data: CWR Temp CWR flow rate Wet bulb temp e = 85% P P P P P P6 T = 47F Maximum wet bulb temperature for free cooling : 38F Actual data from Wade Power Plant 2009 to 2011 Control towers and pumps to meet campus load up to maximum capacity.

27 Northwest Plant Free cooling model
Cooling tower fans and pumps sequencing 2 sp. fan VSF Off Off Off Off Off Off Off Off Off Off 50% 100% % 0 - 50% 50% 100% Concrete Tower  5 stages for bringing fan capacity online and offline Adjust variable-speed fan (VSF) up to 50% to meet target plant cfm. When VSF reaches 50% speed, set Fan 1 to low speed (50%) Adjust VSF to meet target plant cfm. When VSF reaches 50% speed, Set Fan 3 to low speed (50%) Adjust VSF to meet target plant cfm. When VSF reaches 100% speed, Set Fan 1 to high speed (100%) Adjust VSF to meet target plant cfm. When VSF reaches 100% speed, Set Fan 3 to high speed (100%) Adjust VSF to meet target plant cfm.

28 Northwest Plant Free cooling model
Cooling tower fans and pumps sequencing 2 sp. fan VSF Off 100% % Off Off Off Off Off Off Off Off Off ON ON ON ON ON ON ON ON ON P P P P P P6 Metal Towers Sequencing  9 stages for bringing fan capacity online and offline When VSF reaches 100% sp., turn on Fan 4A. Adjust VSF to meet target cfm. When VSF reaches 100% sp., turn on Fan 4B. Adjust VSF to meet target cfm. Add additional fans for towers #4, 5, and 6 until meeting target plan cfm. Pump Sequencing  Match pump control to tower control

29 Northwest Plant Free cooling model
Plume Abatement Selected method : heating the tower exhaust with natural gas burners. Air entering tower Air leaving tower 1 2 Energy for plume abatement  Energy to heat the air exiting each cooling tower cell to a temperature that avoids the plume. Calculations made for each CT cell each time step (0.5 h) of simulation Tangent to saturation curve 3 Indicates fog will form

30 Results Free cooling performance with all cooling towers
Free cooling performance with concrete cooling tower only Economic comparison

31 Free Cooling Performance with All Cooling Towers
Free cooling compared to actual campus load

32 Free Cooling Performance with All Cooling Towers
Average free cooling efficiency Average electric chiller efficiency = 0.55 kWh/ton

33 Free Cooling Performance with All Cooling Towers
Electricity Savings (relative to 0.55 kWh/ton)

34 Free Cooling Performance with All Cooling Towers
From 6am to 8pm Energy for Plume Abatement

35 Free Cooling Performance with All Cooling Towers
Annual estimates for free cooling with all cooling towers Description 2009 2010 2011 Average Campus Load (Ton-hr) 93,336,089 90,608,510 93,154,092 92,366,230 Free cooling hours (hr) 2,682 2,913 2,705 2,767 Free cooling energy (Ton-hr) 15,129,230 15,196,931 14,574,313 14,966,824 Free cooling fraction 0.162 0.168 0.156 Free cooling efficiency (KW/Ton) 0.125 0.121 0.131 0.126 Electricity Savings (KW-hr) 6,422,614 6,525,651 6,109,390 6,352,552 Total plume hours (hr) 1,614 2,017 1,495 1,708 Energy for plume abatement (Therm) 99,298 125,216 76,128 100,214 Day-time plume hours (hr) 879 1,117 801 932 Energy for day-time plume abatement (Therm) 50,524 63,724 38,552 50,933

36 Free Cooling Performance with All Cooling Towers
Plate and Frame Heat Exchanger Sizing Side Fluid Flow Rate Inlet temp. Outlet temp. Pressure drop Hot Water 10,000 gpm 55.0 F 45.0 F 15.0 psi Cold 43.0 F 53.0 F Cooling towers maximum flow rate : 41,000 gpm  4 heat exchangers are necessary. Estimated cost of each unit : $223,070 Estimated cost of the system: $2,750,000 Operating in free cooling with only the concrete CT will require 2 heat exchangers  How is free cooling performance affected?

37 Free Cooling Performance with Concrete Cooling Tower Only
Average Annual Free Cooling Estimates ( ) Description Concrete CT Average Campus Load (Ton-hr) 92,366,230 Free cooling hours (hr) 2,767 Free cooling energy (Ton-hr) 13,218,050 Free cooling fraction 0.143 Free cooling efficiency (KW/Ton) 0.092 Electricity Savings (KW-hr) 6,049,371 Energy for plume abatement (Therm) 105,752 Energy for day-time plume abatement (Therm) 53,529 Nr. of heat exchangers required 2 Installed cost estimate $1,375,000 All CT Average 92,366,230 2,767 14,966,824 0.162 0.126 6,352,552 100,214 50,933 4 $2,750,000

38 Economic Comparison All cooling towers Free Cooling with
Concrete tower All cooling towers Alternatives of plume abatement 1. FC without plume abatement 2. Only day-time plume abatement 3. All-day plume abatement 4. Reject day-time hours with plume 5. Reject all-day hours with plume Economic parameters Electricity price = $0.05 per kW-h Natural gas price = 0.65 $/Therm

39 Economic Comparison Annual Cost Savings Payback period

40 Conclusions Free cooling operation with only the concrete tower gets ~13 million Ton-hr of annual free cooling, equivalent to $302,000 electricity savings (95% of the savings obtained with all CTs and only half of the system installed cost). The selected alternative for plume abatement was natural gas burners. The cost of energy is ~$69,000 for plume abatement all day, and ~$35,000 for day-time only (6am to 8pm). The Best alternative is free cooling mode using only the concrete cooling tower and day-time plume abatement  ~$268,000 annual cost savings , and 5 years payback period. During the coldest months (January, February and December) the campus demand can be almost satisfied through free cooling. The savings for the shoulder months (March, October and November) could be increased significantly through the use thermal energy storage.

41 Next Steps… More accurate estimation of installed cost of the system.
Design system to control campus chilled water flow into the system, so maximum flow and cooling capacity are not exceeded. Consider application of thermal storage.


Download ppt "Free Cooling Application for Energy Savings at Purdue"

Similar presentations


Ads by Google