Download presentation
Presentation is loading. Please wait.
Published byMartina Ellen Horn Modified over 7 years ago
1
Announcements Next class is the course evaluation
Final project related additional office hours Tomorrow afternoon from 1 till 4 pm Thursday afternoon Friday by appointment
2
Objectives Discuss the exam problems
Talk about final project report and presentation Learn about automatic control PID and Control terminology Sequence of operation Control optimization
3
Project presentation Timing: 10 minutes for presentation Approximately 1 PowerPoint Slides per minute For example Specify the project Provide some basic floor layout and input variable assumptions Results (form calculation and manufacturer catalogs) Disuses you system challenges and modifications related to your design solutions 3 minutes for Questions and Answers I will need you power point before the class You can it to me.
4
HVAC automatic control
Maintain environmental quality Thermal comfort Indoor air quality Material protection Conserve energy Protect equipment
5
Terminology Sensor Controller Controlled device
Measures quantity of interest Controller Interprets sensor data Controlled device Changes based on controller output Figure 2-13
6
Direct Indirect outdoor Closed Loop or Feedback
Open Loop or Feedforward
7
Set Point Control Point Error or Offset Desired sensor value
Current sensor value Error or Offset Difference between control point and set point
8
Two-Position Control Systems
Used in small, relatively simple systems Controlled device is on or off It is a switch, not a valve Good for devices that change slowly
9
Modulating Control Systems
Example: Heat exchanger control Modulating (Analog) control air water Cooling coil x (set point temperature)
10
Modulating Control Systems
Used in larger systems Output can be anywhere in operating range Three main types Proportional PI PID Position (x) fluid Electric (pneumatic) motor Vfluid = f(x) linear or exponential function Volume flow rate
11
The PID control algorithm
constants time e(t) – difference between set point and measured value Position (x) Proportional Integral Differential For our example of heating coil: Differential (how fast) Proportional (how much) Integral (for how long) Position of the valve
12
Proportional Controllers
x is controller output A is controller output with no error (often A=0) Kis proportional gain constant e = is error (offset)
13
Unstable system Stable system
14
Issues with P Controllers
Always have an offset But, require less tuning than other controllers Very appropriate for things that change slowly i.e. building internal temperature
15
Proportional + Integral (PI)
K/Ti is integral gain If controller is tuned properly, offset is reduced to zero Figure 2-18a
17
Issues with PI Controllers
Scheduling issues Require more tuning than for P But, no offset
18
Proportional + Integral + Derivative (PID)
Improvement over PI because of faster response and less deviation from offset Increases rate of error correction as errors get larger But HVAC controlled devices are too slow responding Requires setting three different gains
19
Ref: Kreider and Rabl.Figure 12.5
20
The control in HVAC system – only PI
Proportional Integral value Set point Proportional affect the slope Set point Integral affect the shape after the first “bump”
21
The Real World 50% of US buildings have control problems
90% tuning and optimization 10% faults 25% energy savings from correcting control problems Commissioning is critically important
22
Practical Details Measure what you want to control
Verify that sensors are working Integrate control system components Tune systems Measure performance Commission control systems
23
HVAC Control Example 1: Economizer (fresh air volume flow rate control) Controlled device is damper - Damper for the air - Valve for the liquids fresh air damper mixing recirc. air T & RH sensors
24
Economizer Fresh air volume flow rate control % fresh air TOA (hOA)
enthalpy 100% Fresh (outdoor) air TOA (hOA) Minimum for ventilation damper mixing Recirc. air T & RH sensors
25
Economizer – cooling regime
How to control the fresh air volume flow rate? If TOA < Tset-point → Supply more fresh air than the minimum required The question is how much? Open the damper for the fresh air and compare the Troom with the Tset-point . Open till you get the Troom = Tset-point If you have 100% fresh air and your still need cooling use cooling coil. What are the priorities: - Control the dampers and then the cooling coils or - Control the valves of cooling coil and then the dampers ? Defend by SEQUENCE OF OERATION the set of operation which HVAC designer provides to the automatic control engineer % fresh air 100% Minimum for ventilation
26
Economizer – cooling regime
Example of SEQUENCE OF OERATIONS: If TOA < Tset-point open the fresh air damper the maximum position Then, if Tindoor air < Tset-point start closing the cooling coil valve If cooling coil valve is closed and T indoor air < Tset-point start closing the damper till you get T indoor air = T set-point Other variations are possible
27
HVAC Control Example 2: Dew point control (Relative Humidity control)
fresh air damper filter cooling coil heating coil filter fan mixing T & RH sensors Heat gains Humidity generation We should supply air with lower humidity ratio (w) and lower temperature We either measure Dew Point directly or T & RH sensors substitute dew point sensor
28
Relative humidity control by cooling coil
Mixture Room Supply TDP Heating coil
29
Relative humidity control by cooling coil (CC)
Cooling coil is controlled by TDP set-point if TDP measured > TDP set-point → send the signal to open more the CC valve if TDP measured < TDP set-point → send the signal to close more the CC valve Heating coil is controlled by Tair set-point if Tair < Tair set-point → send the signal to open more the heating coil valve if Tair > Tair set-point → send the signal to close more the heating coil valve Control valves Fresh air mixing cooling coil heating coil Tair & TDP sensors
30
Sequence of operation (ECJ research facility)
Set Point (SP) Mixture 2 Mixture 3 Mixture 1 DBTSP DPTSP Control logic: Mixture in zone 1: IF (( TM<TSP) & (DPTM<DPTSP) ) heating and humidifying Heater control: IF (TSP>TSA) increase heating or IF (TSP<TSA) decrease heating Humidifier: IF (DPTSP>DPTSA) increase humidifying or IF (DPTSP<DPTSA) decrease humid. Mixture in zone 2: IF ((TM>TSP) & (DPTM<DPTSP) ) cooling and humidifying Cool. coil cont.: IF (TSP<TSA) increase cooling or IF (TSP>TSA) decrease cooling Humidifier: IF (DPTSP>DPTSA) increase humidifying or IF (DPTSP<DPTSA) decrease hum. Mixture in zone 3: IF ((DPTM>DPTSP) ) cooling/dehumidifying and reheatin Cool. coil cont.: IF (DPTSP>DPTSA) increase cooling or IF (DPTSP<DPTSA) decrease cooling
31
Other examples for HVAC:
Heat recovery Dual duct system
32
Other examples Thermal storage UTs CHP
33
Thermal storage for adjustment production to consumption
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.