Delta’s Contribution for OCP Solution 2014

Similar presentations


Presentation on theme: "Delta’s Contribution for OCP Solution 2014"— Presentation transcript:

1 Delta’s Contribution for OCP Solution 2014
Antony Ren Delta Electronics, Inc. PSBG IDC

2 Facebook Open Rack V2 Key Features:
Fully complied with FB V2 & OCP spec. 1250 Kg loading ability Two power shelves / power zones. Free configuration flexibility.

3 Facebook Open Rack V2 External Size: W: 600 mm H: 2210 mm D: 1067 mm
Internal space: 3 OU for switch 4 OU for power 32 OU for devices Total: 39 OU 3 OU for switches 8 OU for devices 2 OU for power shelf 8 OU for devices Support bar 8 OU for devices 2 OU for power shelf 8 OU for devices

4 Facebook Open Rack V2 DC PDU AC PDU Stingray V2 Power shelf

5 How Delta verify the rack worked?
Facebook Open Rack V2 Testing! How Delta verify the rack worked? Caster test Swivel level feet test Rack Devices Retrofit Test Rack moving test

6 Facebook Open Rack V2 Caster Test
To meet rack total 1385 ( ) kg weight requirement, one single caster can withstand 550 Kg for both static and dynamic conditions (about 40 % of max rack total weight, 4 casters in one rack). a. Static loading test Passed! b. Dynamic moving test

7 Facebook Open Rack V2 Static loading test (659 Kg / 16 hours) Loading
Caster

8 Facebook Open Rack V2 Dynamic moving cross obstacle test
Loading 550 Kg, 2700 meters moving, speed: 0.9 meter / sec, Obstacle height: 3.6 mm, Change moving direction each 3 mins.

9 Facebook Open Rack V2 Swivel level feet Test
To meet rack total 1385 ( ) kg weight requirement, Single swivel level feet can withstand 1200 Kg for both vertical and 10∘angle conditions (about 87 % of max rack total weight, 4 feet in one rack). a. Vertical loading test (1200 kg vertical static) Passed! b. Limit angled loading test (1200 kg 10∘)

10 Facebook Open Rack V2 Vertical Loading Test (1595 Kg / 16 hours tested)

11 Facebook Open Rack V2 Angled Loading Test (1595 Kg / 16 hours tested on two directions) Test on the opposite direction

12 Facebook Open Rack V2 Devices Retrofit Test No. Device Install Remove
1 Empty Cubby chassis OK 2 Knox 3 AC EU 230V PDU (box type) 4 AC NA 277V PDU (box type) 5 AC 208V PDU (plate type) 6 DC PDU (box type) 7 Stingray V II power shelf 8 Rack-mount

13 Facebook Open Rack V2

14 Facebook Open Rack V2

15 Facebook Open Rack V2

16 Facebook Open Rack V2

17 Facebook Open Rack V2 Rack Moving Test
Load up the rack to its maximum loading (1250 Kg) for: Over 6 mm high obstacle 5 times. Passed! Over 1” wide gap 5 times Move rack up and down 10’ / 5° ramp 5 times Moving force test (less than 5% of rack total weight) Rack total weight: = 1385 Kg Tested force on terrazzo floor is 35 kg, 2.52% total weight.

18 Facebook Open Rack V2

19 Facebook Open Rack V2

20 Facebook Open Rack V2

21 Facebook Open Rack V2

22 Facebook Open Rack V2

23 Facebook V2 PDU Key Features: Box on rack top design
On-site serviceability Modularized design support different region power type requirements.

24 Output Connector (with molding)
Facebook V2 PDU AC input plugs Output Connector (with molding) Locking Latches AC PDU 16A 277 / 480 VAC, With surge protection, 2 inputs / 2 outputs

25 Facebook V2 PDU Locking Latches Input connector DC 54V,
Connect to power shelf Signal Ports Output connectors Signal Ports

26 Facebook V2 PDU Type FB P/N Input Power Surge Plug In. / Out. Q’ty
NA, 277/480 277/480, 3P5W Yes L22-20P 2 in / 2 out EU, 240/415 240/415, 3P5W IEC 309 1 in / 2 out NA, 208V 208, 3P4W No L21-30P 2 in / 2 out NA, 277 CS 277, 1P3W L7-20P 1 in / 1 out NA, A L22-30P DC PDU 54Vdc N/A 2 in / 4 out

27 Fidelity Open Bridge Rack
Key Features: OCP and EIA two-way interchangeable rack Easier and quicker conversion Lockable, removable front / rear doors Two independent power shelves for OCP

28 Fidelity Open Bridge Rack
External Size: W: 28” H: 82.3” D: 50.1” H D W

29 Fidelity Open Bridge Rack
Zone 1 16 OU (01~16) for devices Zone 2 6 OU (17~22) for two set power shelves Zone 3 16 OU (23~38) OCP Spacing EIA Spacing EIA standard 19” / 42U Total 38 OU

30 Fidelity Open Bridge Rack
Front / rear door can be removed / installed tool-less. 90∘

31 Transforming time: 25 minutes / 2 operators
Fidelity Open Bridge Rack OCP EIA 1 3 4 2 2 4 3 1 Transforming time: 25 minutes / 2 operators

32 Fidelity Open Bridge Rack
Step 1: Exchange the location of column 1 & 2. Step 2: Exchange the location of column 3 & 4. Step 3: Rotate column 1 & 4 by 90 degrees counterclockwise. Step 4: Rotate column 2 & 3 by 90 degrees clockwise. Step 5: Fix to Rack 1 3 4 2 EIA OCP

33 Fidelity Open Bridge Rack

34 Fidelity Open Bridge Rack

35 Fidelity Open Bridge Rack

36 Fidelity Power System Two independent power shelves and copper bus bar sets.

37 Output Bus Bar Connection
Fidelity Power System Output Bus Bar Connection Upper side vertical Bus Bar Busbar connection between shelf and Rack AC PDU *2 Down side vertical Bus Bar

38 AC PDU Design – Delta 208V/ 230V
Fidelity Power System AC PDU Design – Delta 208V/ 230V AC input plug NEMA L22-30P AC output breaker; 2 PCS AC outlet C13; 4 PCS (2 PCS on top, 2 PCS on bottom) AC I/P power cord UL2586 #10 5C AC output cord For shelf

39 Fidelity Power System AC PDU Design – WYE 400V/415V AC output breaker;
2 PCS AC outlet C13; 4 PCS (2 PCS on top, 2 PCS on bottom) AC input plug ME460P9W -1109A AC I/P power cord SOOW #4 4C AC output cord For shelf

40 Power Shelf Key Specifications
Fidelity Power System Power Shelf Key Specifications Application 12V Power shelf PSU installation 3 PSUs + 3 PSUs Input Voltage AC: Delta 200 – 240 VAC AC: WYE 346V – 415VAC Vout 12.5 V Max.Iout 600 A P max 7.5 KW KW Safety UL, CB Operation Temp. Cooling Fan cooling by PSU EMI EN55022 Class A Size W: 450; H: 113; D: 592 (mm) RMC 3pcs PSUs + 3pcs PSUs, maximum power 7.5KW

41 Fidelity Power System Power Shelf’s Block Diagram– Delta Connection
3 phase 208Vac L3 PSU3_B L2 PSU2_B L1 PSU1_B DC+ DC- L3 PSU3_A L2 PSU2_A L1 PSU1_A I2C& Alert Signals

42 Delta Connection Shelf Outward Drawing
Fidelity Power System Delta Connection Shelf Outward Drawing RMC slot 3 PSUs + 3 PSUs, maximum power 7.5KW Front View Main 12.5V with 3 pair Bus bar Rear View Dual AC 208V inputs

43 Fidelity Power System Power shelf’s block diagram – WYE Connection
3 phase 400Vac L3 PSU3_B N L2 PSU2_B L1 PSU1_B DC+ DC- L3 PSU3_A N L2 PSU2_A L1 PSU1_A I2C& Alert Signals

44 Delta Connection Shelf Outward Drawing
Fidelity Power System Delta Connection Shelf Outward Drawing RMC slot 3 PSUs + 3 PSUs, maximum power 7.5KW Front View Main 12.5V with 3 pair Bus bar Rear View Dual AC 400V inputs

45 Fidelity Power System PSU Photo – AC: DPST-2430AB B

46 PSU Key Specifications
Fidelity Power System PSU Key Specifications DPST-2430 DPST-2430AB Vin Range AC: 200Vac ~ 240Vac Max. Pout 2530 W Vout 12.5 VDC Max. Iout 200 A Communication PMBUS Safety UL, CB Operation Temp. -5-45 ℃ Size 40.9*101.6*436 Power Density 22 W / in3 Cooling Fan Cooling EMI EN55022 Class A H: 40.9mm D: 436mm W: 101.6mm

47 Fidelity Power System PSU Block Diagram -- DPST-2430AB

48 Tested Efficiency of AC&DC Input PSU
Fidelity Power System Tested Efficiency of AC&DC Input PSU PSU Eff. Efficiency Load The efficiency result can meet he platinum level of 80plus requirement. 48

49 Power Shelf – RMC Functions
Fidelity Power System Power Shelf – RMC Functions RMC functions – FW/SW management Both RMC and PSU’s Firmware can be upgrade via serial port or GbE port Network RS232 Cable CPMS Browser RMC FW/SW management PSU ATS PSU FW PSU FW Memory 49

50 RMC Block Diagram and Interface
Fidelity Power System RMC Block Diagram and Interface Interface: Gigabit Ethernet (RJ45) USB , support OTG function (Micro-USB) RS-232_COM0 + CAN_0 (RJ45) RS-232_COM1 + CAN_1 (RJ45) Reset Button LED indicator (Red and Green light)

51 Delta Standard RMC Package Design
Fidelity Power System Delta Standard RMC Package Design Interface ports RMC module Interposer board

52 Fidelity Power System RMC Function (1) 52

53 Fidelity Power System RMC Function (2) 53

54 Delta Can Offer You the Best Solution!
Why Delta? Delta Can Offer You the Best Solution! Total solution for rack, PDU and power system. Flexible design to accommodate rack + power customization. Supporting teams available for both Commercial / Technical aspects Delta Contact Windows: USA: Taylor Tsai -> Taiwan: Richard Chan-> 54

55 Smarter. Greener. Together.