Download presentation
Presentation is loading. Please wait.
1
Hazardous Area Timefiller Pt 2
2
Question 1 a – Ga b – Gb c – Gc d – Gd
An explosive gas/air mixture is ‘Likely’ to occur, what Equipment Protection Level: a – Ga b – Gb c – Gc d – Gd
3
Answer 1 a – Ga b – Gb c – Gc d – Gd
An explosive gas/air mixture is ‘Likely’ to occur, what Equipment Protection Level: a – Ga b – Gb c – Gc d – Gd
4
Question 2 Zone 1 E.P.L.?
5
Answer 2 Zone 1 Gb
6
Question 3 EPL Ga Category?
7
Answer 3 EPL Ga 1G
8
Question 4 Category 1G Zone?
9
Answer 4 Category 1G Zone 0
10
Question 5 Zone 2 EPL?
11
Answer 5 Zone 2 Gc
12
Question 6 Category 2G EPL?
13
Answer 6 Category 2G Gb
14
Question 7 EPL Gc Category?
15
Answer 7 EPL Gc 3G
16
Which Atex Directive removes
Question 8 Which Atex Directive removes ‘Barriers to Trade’? a – Atex 137? b – Atex 95? c – Atex 98? d – Atex 60079?
17
Which Atex Directive removes
Answer 8 Which Atex Directive removes ‘Barriers to Trade’? a – Atex 137? b – Atex 95? c – Atex 98? d – Atex 60079?
18
What are the symbols for a Zone 0 area on a hazardous Area Drawing
Question 10 What are the symbols for a Zone 0 area on a hazardous Area Drawing a – Small Circles b – Hashed lines at 45degrees c – Single lines at 45degrees d – Symbols shown on the drawing key
19
What are the symbols for a Zone 0 area on a hazardous Area Drawing
Answer 10 What are the symbols for a Zone 0 area on a hazardous Area Drawing a – Small Circles b – Hashed lines at 45degrees c – Single lines at 45degrees d – Symbols shown on the drawing key
20
Question 11 Which part of the Standard covers Installation? a – BS EN – 10 b – BS EN – 14 c – BS EN – 17 d – BS EN – 19
21
Answer 11 Which part of the Standard covers Installation? a – BS EN – 10 b – BS EN – 14 c – BS EN – 17 d – BS EN – 19
22
Question 12 Which of the following would I require knowledge of to work in a Hazardous Area? a – How to draw an Area Classification Drawing b – How to identify Protection Types c – How to write a Gas Free Certificate d – How to write a Permit to Work
23
Answer 12 Which of the following would I require knowledge of to work in a Hazardous Area? a – How to draw an Area Classification Drawing b – How to identify Protection Types c – How to write a Gas Free Certificate d – How to write a Permit to Work
24
What does D.S.E.A.R. stand for?
Question 13 What does D.S.E.A.R. stand for? a – Dangerous Site Electrical Arbitrary Rules b – Dangerous Substances Explanations And Regulations c – Dangerous Substances & Explosive Atmospheres Regulations d – Dangerous Substances & Explosive Atmospheres Rules
25
What does D.S.E.A.R. stand for?
Answer 13 What does D.S.E.A.R. stand for? a – Dangerous Site Electrical Arbitrary Rules b – Dangerous Substances Explanations And Regulations c – Dangerous Substances & Explosive Atmospheres Regulations d – Dangerous Substances & Explosive Atmospheres Rules
26
Question 14 What does E.P.L. stand for? a – Electrical Protection Level b – Equipment Protection Level c – Extreme Protection Level d – External Protection Level
27
Answer 14 What does E.P.L. stand for? a – Electrical Protection Level b – Equipment Protection Level c – Extreme Protection Level d – External Protection Level
28
Which letters internationally correspond to
Question 15 Which letters internationally correspond to Atex Categories? x y z A B C a b c I E C
29
Which letters internationally correspond to
Answer 15 Which letters internationally correspond to Atex Categories? x y z A B C a b c EPLs Ga-Gb-Gc I E C
30
Exercise 2 on Gas Group & Temp. Class
Can the llA T1 motor go into the Acetylene gas/vapour?
31
Exercise 2 on Gas Group & Temp. Class
Can the llA T1 motor go into the Acetylene gas/vapour? Acetylene llC Ign. Temp. 305°C
32
Exercise 2 on Gas Group & Temp. Class
Can the llC T1 motor go into the Ethylene gas/vapour?
33
Exercise 2 on Gas Group & Temp. Class
Can the llC T1 motor go into the Ethylene gas/vapour? Ethylene llB Ign. Temp. 425°C
34
Exercise 2 on Gas Group & Temp. Class
Can the llC T6 motor go into the Hydrogen gas/vapour?
35
Exercise 2 on Gas Group & Temp. Class
Can the llC T6 motor go into the Hydrogen gas/vapour? Hydrogen llC Ign. Temp. 560°C
36
Exercise 2 on Gas Group & Temp. Class
Can the llB T2 motor go into the Cyclohexane gas/vapour (Ign. Temp. 259 C)
37
Exercise 2 on Gas Group & Temp. Class
Can the llB T2 motor go into the Cyclohexane gas/vapour Cyclohexane llA Ign. Temp. 259°C
38
Question 1B Hydrogen Gas Group?
39
Answer 1B Hydrogen - llC
40
Petrol/Gasoline Gas Group?
Question 2B Petrol/Gasoline Gas Group?
41
Answer 2B Petrol/Gasoline - llA
42
Question 3B Ethylene Gas Group?
43
Answer 3B Ethylene - llB
44
Question 4B Propane Gas Group?
45
Answer 4B Propane - llA
46
Hydrogen Sulphide Gas Group?
Question 5B Hydrogen Sulphide Gas Group?
47
Hydrogen Sulphide - llB
Answer 5B Hydrogen Sulphide - llB
48
Question 6B Acetylene Gas Group?
49
Answer 6B Acetylene - llC
50
Question 7B A – Can be used in with llA Gases Only
If the Gas Group BASEEFA marking just has a ll and no A, B or C after it where can it be used? A – Can be used in with llA Gases Only B – Can be used in with llB Gases Only C – Can be used in with llC Gases Only D – Can be used in all Group ll Gas/Vapours
51
Answer 7B A – Can be used in with llA Gases Only
If the Gas Group BASEEFA marking just has a ll and no A, B or C after it where can it be used? A – Can be used in with llA Gases Only B – Can be used in with llB Gases Only C – Can be used in with llC Gases Only D – Can be used in all Group ll Gas/Vapours
52
Question 8B Which Statement is true? A – I can put gas group llA into gas group llB area B – I can put gas group llB into gas group llC area C – I can put gas group llA into gas group llC area D – I can put gas group llC into gas group llA area
53
Answer 8B Which Statement is true? A – I can put gas group llA into gas group llB area B – I can put gas group llB into gas group llC area C – I can put gas group llA into gas group llC area D – I can put gas group llC into gas group llA area
54
Question 1C - What are the three items for Combustion?
1 2 3
55
Answer 1C - What are the three items for Combustion?
1 2 3
56
How many Temperature Classes are there?
Question 2C How many Temperature Classes are there?
57
How many Temperature Classes are there?
Answer 2C How many Temperature Classes are there?
58
What Temperature are the following:
Question 3C What Temperature are the following: a – T1 b – T c – T3
59
What Temperature are the following:
Answer 3C What Temperature are the following: a – T1 – 450 b – T6 – c – T3 – 200
60
Question 4C What is the temperature at which a gas/air mixture will ignite spontaneously? a – Boiling Point? b – Flash Point? c – Ignition Temperature? d – Flash-off Temperature?
61
Answer 4C a – Boiling Point?
What is the temperature at which a gas/air mixture will ignite spontaneously? a – Boiling Point? b – Flash Point? c – Ignition Temperature? d – Flash-off temperature?
62
What is meant by Temperature Class T1 – T6?
Question 5C What is meant by Temperature Class T1 – T6? a – The surface temperature never go over the ‘T’ class stated on it under any conditions! b – The surface temperature will always reach the ‘T’ class stated on it under normal and specified fault conditions. c – The relevant surface temperature will never go over the ‘T’ class stated on it under normal and specified fault
63
What is meant by Temperature Class T1 – T6?
Answer 5C What is meant by Temperature Class T1 – T6? a – The surface temperature never go over the ‘T’ class stated on it under any conditions! b – The surface temperature will always reach the ‘T’ class stated on it under normal and specified fault conditions. c – The relevant surface temperature will never go over the ‘T’ class stated on it under normal and specified fault
64
Question 6C -30oC to +40oC -10oC to +50oC -20oC to +40oC
What is the Ambient Temperature for T1 – T6 -30oC to +40oC -10oC to +50oC -20oC to +40oC -10 C to +40 C
65
Answer 6C -30oC to +40oC -10oC to +50oC -20oC to +40oC -10 C to +40 C
What is the Ambient Temperature for T1 – T6 -30oC to +40oC -10oC to +50oC -20oC to +40oC -10 C to +40 C
66
Question 8C a – Boiling Point?
What is the temperature at which a gas/air mixture will give off sufficient fumes so can be ignited by an external ignition source? a – Boiling Point? b – Flash Point? c – Ignition Temperature? d – Flash off Temperature?
67
Answer 8C What is the temperature at which a gas/air mixture will give off sufficient fumes so can be ignited by an external ignition source? a – Boiling Point? b – Flash Point? c – Ignition Temperature? d – Flash off Temperature?
68
Which one below is correct?
Question 17 Which one below is correct? Zone 0 / Ga / 1D Zone 2 / Gb / 3G Zone 1 / Gb / 2G Zone 0 / Gc / 1G
69
Which one below is correct?
Answer 17 Which one below is correct? Zone 0 / Ga / 1D Zone 2 / Gb / 3G Zone 1 / Gb / 2G Zone 0 / Gc / 1G
70
Question 1D What is ‘Mark’ No. 1
71
The Atex Explosion Protection Mark
Answer 1D The Atex Explosion Protection Mark
72
Question 5D What is ‘Sign’ No. 5
73
To warn People they are Entering a Hazardous Area
Answer 5D To warn People they are Entering a Hazardous Area
74
Question 2E Which Zones of the following can EExd llA T6 go into:
a – Zone 0 llA T b – Zone 2 llB T4 c – Zone 2 llA T d – Zone 20 lllA T3 e – Zone 1 llC T f – Zone 0 llC T6
75
Answer 2E Which Zones of the following can EExd llA T6 go into:
a – Zone 0 llA T b – Zone 2 llB T4 c – Zone 2 llA T d – Zone 20 lllA T3 e – Zone 1 llC T f – Zone 0 llC T6
76
Question 6E Before I put power onto a Flameproof enclosure what is the minimum number of bolts I must put in the cover? 1 – Every other bolt spanner tight 2 – One bolt opposite the hinge spanner tight 3 – All bolts spanner tight 4 – One bolt at each corner spanner tight
77
Answer 6E Before I put power onto a Flameproof enclosure what is the minimum number of bolts I must put in the cover? 1 – Every other bolt spanner tight 2 – One bolt opposite the hinge spanner tight 3 – All bolts and spanner tight 4 – One bolt at each corner spanner tight
78
Question 7E What can I put on the flameproof faces of EExd equipment to improve the IP? 1 – Non setting grease bearing textile tape 2 – Non setting grease 3 – Hard setting resin 4 – Nothing as EExd equipment has good IP
79
Answer 7E What can I put on the flameproof faces of EExd equipment to improve the IP? 1 – Non setting grease bearing textile tape 2 – Non setting grease 3 – Hard setting resin 4 – Nothing as EExd equipment has good IP
80
Question 8E What is the Minimum IP protection for EExe equipment?
81
Answer 8E What is the Minimum IP protection for 2 – IP44 3 – IP54
EExe equipment? 1 – IP20 2 – IP44 3 – IP54 4 – IP68
82
Question 1E Which Zones of the following can EExd llC T6 go into:
a – Zone 0 llA T b – Zone 2 llB T4 c – Zone 2 llA T d – Zone 20 lllA T3 e – Zone 1 llC T f – Zone 0 llC T6
83
Answer 1E Which Zones of the following can EExd llC T6 go into:
a – Zone 0 llA T b – Zone 2 llB T4 c – Zone 2 llA T d – Zone 20 lllA T3 e – Zone 1 llC T f – Zone 0 llC T6
84
Question 2E Which Zones of the following can EExd llA T6 go into:
a – Zone 0 llA T b – Zone 2 llB T4 c – Zone 2 llA T d – Zone 20 lllA T3 e – Zone 1 llC T f – Zone 0 llC T6
85
Answer 2E Which Zones of the following can EExd llA T6 go into:
a – Zone 0 llA T b – Zone 2 llB T4 c – Zone 2 llA T d – Zone 20 lllA T3 e – Zone 1 llC T f – Zone 0 llC T6
86
Question 3E Which Zones of the following can EExia llC T6 go into:
a – Zone 0 llA T b – Zone 2 llB T4 c – Zone 2 llA T d – Zone 20 lllC T3 e – Zone 1 llC T f – Zone 0 llC T6
87
Answer 3E Which Zones of the following can EExia llC T6 go into:
a – Zone 0 llA T b – Zone 2 llB T4 c – Zone 2 llA T d – Zone 20 lllC T3 e – Zone 1 llC T f – Zone 0 llC T6
88
Question 4E Which Zones of the following can EExnR llA T6 go into:
a – Zone 0 llA T b – Zone 2 llB T4 c – Zone 2 llA T d – Zone 20 lllA T6 e – Zone 1 llC T f – Zone 0 llC T6
89
Answer 4E Which Zones of the following can EExnR llA T6 go into:
a – Zone 0 llA T b – Zone 2 llB T4 c – Zone 2 llA T d – Zone 20 lllA T6 e – Zone 1 llC T f – Zone 0 llC T6
90
Question 5E Which Zones of the following can EExde llC T6 go into:
a – Zone 0 llA T b – Zone 2 llB T4 c – Zone 2 llC T d – Zone 20 lllC T6 e – Zone 1 llC T f – Zone 0 llC T6
91
Answer 5E Which Zones of the following can EExde llC T6 go into:
a – Zone 0 llA T b – Zone 2 llB T4 c – Zone 2 llC T d – Zone 20 lllC T6 e – Zone 1 llC T f – Zone 0 llC T6
92
Question 9E EExia in brackets - [EExia] Does it mean: a – The equipment is ‘Intrinsically Safe’? b – The equipment is ‘Associated Equipment’? c – The equipment cannot be installed in the Hazardous Area?
93
Answer 9E EExia in brackets - [EExia] Does it mean: a – The equipment is ‘Intrinsically Safe’? b – The equipment is ‘Associated Equipment’? c – The equipment cannot be installed in the Hazardous Area?
94
Question 10E What Dimensions are the following; Distance from Live Parts of IS Circuits to Non-IS Terminals?
95
Answer 10E What Dimensions are the following; Distance from Live Parts of IS Circuits to Non-IS Terminals? 50mm
96
Question 11E What Dimensions are the following; Distance from Live Parts of IS Circuits to Earthed Metal?
97
Answer 11E What Dimensions are the following; Distance from Live Parts of IS Circuits to Earthed Metal? 3mm
98
Question 12E What Dimensions are the following;
Distance from Live Parts of IS Circuits to other IS Circuits?
99
Answer 12E What Dimensions are the following; Distance from Live Parts of IS Circuits to other IS Circuits? 6mm
100
Question 13E Where should the screen be connected on an IS System? 1 – To Earth at the Hazardous Area? 2 – To Clean Earth at the Non-Hazardous Area? 3 – To Dirty Earth at the Non-Hazardous Area? 4 – As shown on the Loop / Hook up Diagram?
101
Answer 13E Where should the screen be connected on an IS System? 1 – To Earth at the Hazardous Area? 2 – To Clean Earth at the Non-Hazardous Area? 3 – To Dirty Earth at the Non-Hazardous Area? 4 – As shown on the Loop / Hook up Diagram?
102
Question 14E On an EExnR Bulkhead Fitting an IP Washer is: 1 – Not required at all 2 – Fitted between the Gland and Earth Tag 3 – Fitted next to the Fitting
103
Answer 14E On an EExnR Bulkhead Fitting an IP Washer is: 1 – Not required at all 2 – Fitted between the Gland and Earth Tag 3 – Fitted next to the Fitting
104
Question 16E 1 – EEx d 2 – EEx m 3 – EEx p 4 – EEx q
Which protection below allows the gas to enter without compromising safety: 1 – EEx d 2 – EEx m 3 – EEx p 4 – EEx q
105
Answer 16E 1 – EEx d Flameproof! 2 – EEx m 3 – EEx p 4 – EEx q
Which protection below allows the gas to enter without compromising safety: 1 – EEx d Flameproof! 2 – EEx m 3 – EEx p 4 – EEx q
106
Question 17E 1 – EEx d 2 – EEx p 3 – EEx i 4 – EEx n
Which protection below is specifically designed to keep the gas out: 1 – EEx d 2 – EEx p 3 – EEx i 4 – EEx n
107
Answer 17E 1 – EEx d 2 – EEx p Pressurisation! 3 – EEx i 4 – EEx n
Which protection below is specifically designed to keep the gas out: 1 – EEx d 2 – EEx p Pressurisation! 3 – EEx i 4 – EEx n
108
Question 18E 1 – EExnA – EExnB – EExnC – EExnD
Which of the following are the 4 sub-divisions of EEx’n’: 1 – EExnA – EExnB – EExnC – EExnD 2 – EExnV – EExnW – EExnX – EExnY 3 – EExnA – EExnC – EExnL – EExnR 4 – EExno – EExnq – EExne – EExnd
109
Answer 18E 1 – EExnA – EExnB – EExnC – EExnD
Which of the following are the 4 sub-divisions of EEx’n’: 1 – EExnA – EExnB – EExnC – EExnD 2 – EExnV – EExnW – EExnX – EExnY 3 – EExnA – EExnC – EExnL – EExnR 4 – EExno – EExnq – EExne – EExnd
110
Question 19E 1 – pw 2 – px 3 – py 4 – pz
Which is the higher Pressurisation Sub-Division? 1 – pw 2 – px 3 – py 4 – pz
111
Answer 19E Which is the higher Pressurisation Sub-Division? 1 – pw 2 – px 3 – py 4 – pz Zone 1 outside, sparking non classified inside! If Purge is lost then: Auto. Isolation of Electrical Equipment & Alarm
112
Question 2F Cable sheath & filler Non-Hygroscopic does it mean:
1 – The cable is not round 2 – The cable sheath & filler is not water absorbent 3 – The cable sheath & filler is acid resistant 4 – The cable sheath & filler is impact resistant
113
Answer 2F Cable sheath & Filler Non-Hygroscopic does it mean:
1 – The cable is not round 2 – The cable sheath & filler is not water absorbent 3 – The cable sheath & filler is acid resistant 4 – The cable sheath & filler is impact resistant
114
Question 3F Which Statement is true? Intrinsically safe cable has to :
1 – Be Blue 2 – Withstand a 500Volt ac or 750Volt dc test 3 – Be PVC Covered 4 – Withstand a 500Volt ac and 750Volt dc test
115
Answer 3F Which Statement is true? Intrinsically safe cable has to :
1 – Be Blue 2 – Withstand a 500Volt ac or 750Volt dc test 3 – Be PVC Covered 4 – Withstand a 500Volt ac and 750Volt dc test
116
Question 6F The cable is limited to 16mm2 minimum if: 1 – It is fibre optic 2 – It is Copper 3 – It is Aluminum 4 – It is Intrinsically safe
117
Answer 6F The cable is limited to 16mm2 minimum if: 1 – It is fibre optic 2 – It is Copper 3 – It is Aluminum 4 – It is Intrinsically safe
118
Question 7G What is the least number of threads of a Flameproof gland that have to be inserted into the equipment: 1 – 3 2 – 4 3 – 5 4 – 6
119
Answer 7G What is the least number of threads of a Flameproof gland that have to be inserted into the equipment: 1 – 3 2 – 4 3 – 5 4 – 6 The equipment has to be 6 threads to allow you to get your 5 on the gland!
120
Question 9G Which Statement below is NOT true: 1 – Pre-January 2008 I could use an uncertified two seal gland in an EExe Junction Box 2 – Pre-January 2008 I could use an uncertified two seal gland in an EExn/N Junction Box 3 – Pre-January 2008 I could use an uncertified two seal gland in an EExd Junction Box
121
Answer 9G Which Statement below is NOT true if any: 1 – Pre-January 2008 I could use an uncertified two seal gland in an EExe Junction Box 2 – Pre-January 2008 I could use an uncertified two seal gland in an EExn/N Junction Box 3 – Pre-January 2008 I could use an uncertified two seal gland in an EExd Junction Box It was never the case that uncertified glands could be used in Flameproof equipment!
122
Question 10G 1 – By putting an earth clip on the plastic
How do we deal with the risk of static on plastic covered cable tray? 1 – By putting an earth clip on the plastic 2 – By putting in the largest size tray possible 3 – By limiting the surface area of the tray 4 – Not taking any action at all
123
Answer 10G 1 – By putting an earth clip on the plastic
How do we deal with the risk of static on plastic covered cable tray? 1 – By putting an earth clip on the plastic 2 – By putting in the largest size tray possible 3 – By limiting the surface area of the tray 4 – Not taking any action at all
124
Question 11G What Insulation Resistance does plastic covered cable tray not have to exceed? 1 – 1 Micro-Ohm 2 – 1 Ohm 3 – 1 Meg-Ohm 4 – 1 Gig-Ohm
125
Answer 11G What Insulation Resistance does plastic covered cable tray not have to exceed? 1 – 1 Micro-Ohm 2 – 1 Ohm 3 – 1 Meg-Ohm 4 – 1 Gig-Ohm
126
Question 3H a – Visual b – Initial c – Sample d – Close
When Commissioning Equipment before it is brought into service which Type of Inspection? a – Visual b – Initial c – Sample d – Close
127
Answer 3H a – Visual b – Initial c – Sample d – Close
When Commissioning Equipment before it is brought into service which Type of Inspection? a – Visual b – Initial c – Sample d – Close
128
Question 4H What would I have with me on a Lighting Circuit Visual Inspection? 1 – The Lighting Schematic Diagram 2 – The Area Classification Drawing 3 – The Manufacturer’s Equipment Data Sheets 4 – The Light Fitting Repair Manual
129
Answer 4H What would I have with me on a Lighting Circuit Visual Inspection? 1 – The Lighting Schematic Diagram 2 – The Area Classification Drawing 3 – The Manufacturer’s Equipment Data Sheets 4 – The Light Fitting Repair Manual
130
Question 5H Which inspection below would tools NOT be required? 1 – Visual 2 – Close 3 – Detailed 4 – Initial
131
Answer 5H Which inspection below would tools NOT be required? 1 – Visual 2 – Close 3 – Detailed 4 – Initial You would only have an Area Classification Drawing with you!
132
Question 6H Which part of the Standard covers Inspections? a – BS EN – 10 b – BS EN – 14 c – BS EN – 17 d – BS EN – 19
133
Answer 6H Which part of the Standard covers Inspections? a – BS EN – 10 b – BS EN – 14 c – BS EN – 17 d – BS EN – 19
134
Question 7H Which Grade of inspection would I Isolate, open up and check internal connections? 1 – Visual 2 – Close 3 – Detailed
135
Answer 7H Which Grade of inspection would I Isolate, open up and check internal connections? 1 – Visual 2 – Close 3 – Detailed
136
Question 9H Which Grade of inspection would I use tools, but could do it whilst the circuit was live? 1 – Visual 2 – Close 3 – Detailed 4 – Initial
137
Answer 9H Which Grade of inspection would I use tools, but could do it whilst the circuit was live? 1 – Visual 2 – Close 3 – Detailed 4 – Initial
138
Question 1I 1 – Be wearing rubber gloves
When you are working live in a Hazardous Area without a gas free certificate, would you: 1 – Be wearing rubber gloves 2 – Be working on 110 Volts or less 3 – Be working on an IS Circuit 4 – Have roped off the area for safety
139
Answer 1I 1 – Be wearing rubber gloves
When you are working live in a Hazardous Area without a gas free certificate, would you: 1 – Be wearing rubber gloves 2 – Be working on 110 Volts or less 3 – Be working on an IS Circuit 4 – Have roped off the area for safety
140
Question 2I 1 – Remove the fuse from the distribution board
What is the minimum isolation when working on electrical equipment in a hazardous area: 1 – Remove the fuse from the distribution board 2 – Operation of an on load double pole switch & locked in the off position 3 – Operation of an off load double pole switch & locked in the off position 4 – Operation of a single pole switch & locked in the off position
141
You must cut the Neutral also to stop Neutral – Earth Sparks!
Answer 2I What is the minimum isolation when working on electrical equipment in a hazardous area: 1 – Remove the fuse from the distribution board 2 – Operation of an on load double pole switch & locked in the off position 3 – Operation of an off load double pole switch & locked in the off position 4 – Operation of a single pole switch & locked in the off position You must cut the Neutral also to stop Neutral – Earth Sparks!
142
Document Control (This slide may be hidden from your presentation, but is required to be the final slide.) Revision History Document Title: Hazardous Area Timefiller part 2 Revised by: K Knight Approved by: P Clark Document Number: TRPP.37 Revision: A Approval Date: 11/04/16 Revision: Revision Date: Reason for Revision: (Complete Document Change Request, QL02F.01 with details of changes) A 11/04/16 Initial Release B C