2 Presented by: Peter Kratochvil Cos Phi Inc.
The Effect of Power Quality on Product Quality in Manufacturing A Case Study Presented by: Peter Kratochvil Cos Phi Inc.

3 Manufacturing Competitive Profitability Product Cost Automation
resolve inconsistencies electrical power quality

4 Automation Solid state technology Based on static power conversion
Number of devices operating on same production line

5 Solid State Devices Characteristic behavior of these solid state devices Draw electric current in spurts or pulses Distort the sine-wave Impact the electrical power within the whole facility Equipment reliability means consistent product

6 Most Common Areas Welding operations Mis-indexing problems of robots
Other areas

7 Case Background The welders involved are 2.2KVA high frequency welders
Previous process used gas flame welder Output of about 6-7 pieces a minute

8 Improving Efficiency A new high frequency welder was introduced
Much faster producing about pieces per minute Scrap rate at 33%

9 Part A Part B A & B Welded Together The Finished Product

10 Good Welds

11 Bad Welds

12 Close-up Over Heated Under Heated

13 Finished Products

14 Trying to improve Quality
Modifications on the new Welders From single phase to three phase More welders were added Situation deteriorated even more

15 Investigations Quality analysis performed
Require individual filter on each welder because the short circuit capacity was 1-4 at best Proposal was uneconomical

16 Move To New Facility Special attention was given to the powering
Isolation transformer was installed to serve only the welders Distribution panel was dedicated to welders Slight improvement

17 Different Problems In the new facility
The distortion was less than half of the distortion in the old premises Welders fired coincidentally at the same time The more Welders the more frequent were the coincidences

18 New Investigation Inrush current when welders fired Voltage drop
Depleted power to the next welder at random

19 Mitigation Resolution
50 Amp Aim Active Filter Possibility of mitigating problem for all welders from one central location with one filter

20 Results No Filter Welding approximately 25 pieces of product per minute, scrap rate of 16%

21 Results With Filter Welding approximately 25 pieces of product per minute, scrap rate of 0.7%

22 Conclusion Power quality or lack of power quality can impact not only the electrical distribution system but also impacts: The final product of a process The profitability of the company

23 Phase A Filter OFF

24 Phase A Filter ON

25 Phase B Filter OFF

26 Phase B Filter ON

27 Phase C Filter OFF

28 Phase C Filter ON

29 Questions?