Download presentation
Presentation is loading. Please wait.
1
New Electric Actuators EA Type 25 - 250
Sales Release New Electric Actuators EA Type J.Sixsmith – 8/1/2016
2
Quick Overview Standard actuators all include
Control options for 3 positions Position feedbacks via relays for: OPEN/CLOSE/’Middle’ + ‘Ready to operate’ Heating Element with selectable temperature Feedback LED via light tube Easy position adjustment via push-buttons Error Code New Electric Actuators | 8/1/2016 | J.Sixsmith
3
Key Specs EA21 / EA31 EA42 New EA25 EA45 EA120 EA250
All types Power supply AC V, AC/DC 24V Supply tolerance +/- 15% IP Protection IP65 (67) Degree of pollution II Ambient Temp. -10°…+50°C Old EA21 / EA31 EA42 New EA25 EA45 EA120 EA250 Nominal Torque [Nm] 10 20 60 100 Peak Torque [Nm] 25 45 120 250 Cycles and nominal torque) 250,000 100’000 100,000 75,000 Control time [s/90°] 5 12 15 L/W/H [mm] 150/122/167 150/122/190 150/122/208 Flanges F05 F07 New Electric Actuators | 8/1/2016 | J.Sixsmith
4
Valve Combinations EA25 EA45 EA120 EA250 ✓ - 2-way ball valves
DN10-DN50 ✓ - DN65 DN80-DN100 3-way ball valves Butterfly Valves DN50/65 DN80 – DN200 DN250/300 New Electric Actuators | 8/1/2016 | J.Sixsmith
5
Inside Benefit Feature
Easy position adjustment for open/ close/ middle Teach buttons allow for tool-less position adjustment Heating element adjustable to ambient conditions, especially for hot and humid environment 5°C Steps possible to set the heating threshold via a dial Easy troubleshooting in case of failure Deviation from standard operation is shown via a 7-segment display inside the actuator with corresponding error codes No effort position feedback for up to three positions and a ‘ready-to-operate’ signal 4 On-board relays included in the standard, can be wired NO or NC New Electric Actuators | 8/1/2016 | J.Sixsmith
6
Old / New Limit Switches
Limit Switches Accessory: Open/Close/Middle/Ready to operate Old Integrated New New Electric Actuators | 8/1/2016 | J.Sixsmith
7
Old vs. New Fail-safe & Heating
Heating integrated in basic version Fail-safe return integrated in housing New New Electric Actuators | 8/1/2016 | J.Sixsmith
8
Old vs. New Fail-safe (new)
Fail-Safe return unit Batteries on board or external 24V DC power supply Self charging battery pack Low power indication – flashing LED if U> 50% Open / Close New Electric Actuators | 8/1/2016 | J.Sixsmith
9
Old vs. New Positioner (new + current monitoring)
Positioner Feedback: 4…20mA Set Value: 4…20mA or 0-10 V (can be inverted) Old One board for all New New Electric Actuators | 8/1/2016 | J.Sixsmith
10
Old vs. New Positioner New
Positioner board: 4…20mA out, 4…20mA/0…10V in Control in Feedback out Signal in options: In: 4-20mA/0-10V Inverted optional Out: 4-20mA Out only (no In): 4-20mA Current monitoring (next slides) 1 2 3 4 5 6 GND 4-20mA 0-10V OUT IN In/Out Mode Current monitoring options New Electric Actuators | 8/1/2016 | J.Sixsmith
11
Old New Old vs. New Monitoring One board for all
New Electric Actuators | 8/1/2016 | J.Sixsmith
12
Old vs. New Monitoring New
Monitoring Board Cycle Counter: Pre-set max no. of cycles to assure e.g. correct maintenance schedule Cycle time extension: Extend cycles to e.g. prevent water hammers etc. 5 – 70s Cycle Time Monitor: To get notification of faulty valve, sealing etc. Set max travelling time 7 – 90s Current Monitor: Set the max motor current to prevent excessive torque 25 – 1800mA New Electric Actuators | 8/1/2016 | J.Sixsmith
13
Old vs. New Profibus New Ready for Profibus
Additional slot for PB card PB-Standard: DP V0 Bd rate: 9600 – 1.5M Connection: M 12 Serial Network New Electric Actuators | 8/1/2016 | J.Sixsmith