Download presentation
Presentation is loading. Please wait.
Published byJoanna Bailey Modified over 7 years ago
1
Natural Gas Production Chapter 8 Instrumentation
PTRT 2323 Natural Gas Production Chapter 8 Instrumentation
2
Instrumentation Related to the control of a gas or liquid
Controlled medium Maintain specific values of these control variables Temperature Pressure Flow rate Liquid level Final control achieved by adjusting orifice size through which the controlled medium (or some related flow) is passing
3
Measurement Value of variable to be controlled must be accurately measured Measurement must be compared to an optimum value (set point) Corrective action to correct offset Manual Automatic Mechanical electrical
4
Pressure Measurement Manometer most commonly used device for pressure from zero to a few psi
5
Manometer U-tube One end connected to tank
Other end open to atmosphere Positive gauge pressure in tank pushes fluid down on the leg next to tank and up on the leg open to atmosphere Negative gauge pressure in the tank does the reverse Difference in height is the gauge pressure measured in inches (Hg or H2O) Used for low pressures where visual indication is required
6
Diaphragm Element Also used for measuring low pressures (a few psi)
Very sensitive to small pressure changes Can provide an indicated reading or movement to operate an automated control device Components Heavy metal base Pressure connection Corrugated diaphragm (thin sheet metal or elastomer for very low pressures) Barometer is this device with pressure connection sealed
8
Bellows Element Similar to diaphragm except corrugations expand in series instead of outwards Movement of bellows is opposed by a spring (extends the range of pressures tolerated) Ranges up to 100 psi or so available
10
Bourdon Tube C-shaped tube, sealed at one end connected to pressure at the other Outer circumference is greater than the inner so pressure tends to straighten the tube Linkage used to amplify the movement Multiple Bourdon tubes connected together make a helical tube
13
Temperature Measurements
Thermometer – common indicating instrument Contains mercury, pentane, toluene, alcohol, etc Volume of fluid in bulb is about 1000 times more than volume in the stem bore. Temperature increase produces a volume increase which moves the fluid column up or down in the stem bore (Vacuum above) Thermometer well protects thermometer from fluid flow
14
Well should be filled with thermal transfer fluid such as a light oil
Well provides seal against pressure or leaks
15
Filled System Thermometer
Sealed unit Increased T produces increased P measured with Bourdon tube Thermal expansion of the fluid in the device is not accounted for in this design Temperature compensation requires a separate Bourdon Loop
16
Temperature Compensation
Second Bourdon tube aligned opposite to sensing element Expands or contracts the same but in opposite direction thereby correcting for the expansion of the fluid inside the tube
17
Bimetallic Temperature Element
Bimetal strip – two strips physically bonded together Bends in response to temperature changes Often seen in Thermostats in the home Helical winding saves space
18
Thermocouple Element Two metals electrically bonded together
Temperature change produces a voltage Sensitive voltmeter can detect the changes and display or transmit temperature
20
Liquid Level Measurements
Most common is the sight glass Transparent Armored Reflex Level in the glass tube matches the level in the tank On pressurized vessels the bottom and top of the sight glass must be connected to the tank (top above the liquid)
23
Float-type Control Bulb or ball floats on liquid
Linkage transmits motion through a packing gland(seal) to move an indicator or trip a valve Generally used for on/off control
24
Pressure Devices Depth of fluid generates a hydrostatic pressure at the bottom of the fluid Pressure device and convert this pressure to a level measurement Vented to atmosphere
25
Pressurized Tank Must compensate for vapor pressure in order to determine liquid level Two bellows oppose one another Pressure DIFFERENCE is measured
26
Flow Controllers Manual control can be achieved in most circumstances by well-informed operator All control functions can be performed automatically: Better control More safety More accurately Lower cost
27
Flow Controllers Automatic system must contain:
Measuring device (detect variation) Controlling element (use variation to produce a control signal) Final control element (use the control signal to produce the control; i.e. valve, heater, etc) Connected in a continuous closed loop Setting the control limits is the only manual step required Measuring and controlling usually in a common instrument that operates the final control element
28
Flow Regulators All flow regulators contain three essential elements
Restricting device (limit flow) Measuring device (measure flow) Loading device (control flow) Self-contained regulator contains all three elements in a single device
29
Spring-loaded Regulator
Loading device Restricting device Measuring device
30
Spring-loaded Regulators
Up to 1000 psi inlet pressure Up to 400 psi outlet pressure Outlet pressure applied to diaphragm (limiting factor) Spring stretches as it’s opened farther causing outlet pressure to drop off as regulator is opened farther
31
Temperature Control Regulators
Diaphragm replaced by bellows Bellows connected to filled system thermometer Temperature changes create pressure changes inside the bellows Orifice opens or closes against the seat Unit ONLY control flow rate pressure is irrelevant. Pressure regulation must be provided separately
32
Temperature Controller
Measuring device Loading device Restricting device
33
Pilot-operated regulator
Similar to temperature regulator Gas pressure replaces the spring Small spring used to help seat the orifice against the seat when closed Constant load independent of the position of the diaphragm (unlike regulator) Eliminates the pressure drop Used to regulate burner fuel supply
34
Motor Valves Diaphragm Loading spring Valve stem and body
Inner valve and seat Normally open (spring tries to hold the valve completely open) Normally closed (spring tries to hold the valve completely closed) Operating pressure (control signal) overcomes the resistance of the spring Typical values for operating pressure 3 psi (start travel) and 15 psi (full travel) – some valves 2x these values In failed condition spring returns the valve to it’s normal position
35
Normally OPEN Normally CLOSED
36
Hydraulic Piston Motor Valve
Diaphragm attached to a hydraulic piston instead of metal stem Hydraulic pressure squeezes on a rubber bladder expanding it against the inside wall of a seat and stopping the flow Streamlined flow since there is little change in direction during operation Can accept a 1000 psi pressure drop and still close (even around trash) Control pressure can usually be must less than the 3 to 15 psi for motor valve
37
Hydraulic Piston Motor Valve
38
Types of Inner Valves Double ported (also called balanced valve) (shown previously) Requires lower opening forces (pressures) Used when process requires extended throttling at less than 10% capacity Difficult to fully close Single ported Requires higher opening forces Used typically for on/off situations
39
Single-ported Valve
40
Valve Forms Selected for specific flow characteristics
Linear (20% travel yields 20% flow, etc.) V-port (40% travel yields only small % flow) Excellent throttling valve Good when upsets in flow can occur Quick opening (small travel yields large flow) Used when control variable is difficult to adjust Good when drastic flow changes occur Motor valves operate equally either normally open or normally closed
41
Valve Plugs Linear Throttling Equal Percentage Quick Opening V-port
43
Final Comment on Valves
Choice depends on application Long transmission lines or distribution lines Never completely shut off Not required to throttle for extended periods Ideal for double-ported with linear plug Flow control Double-ported with throttling plug Controlled variable that is reduced two or three times in a relatively short section of pipe Control variable can be changed easily Dump valves or liquid level control Single ported with quick opening plug is adequate Also can be good in corrosive environments
44
Pneumatic Controllers
Controls operation of motor valve Must be supplied with clean, dry, non-corrosive gas Field gas Compressed air Typical supply pressure about 20 psi Performs the following functions Method of setting the value for the controlled variable (set point) Measure the actual value Detect deviation from set value Transmit control signal to provide correction Select controller matched to system (i.e. don’t use a 600 psi element to control 45 psi system)
45
Principles of Operation
Error detection (on output side) Nozzle and flapper system Acts like orifice and seat Bourdon tube Reacts to pressure changes Pivots flapper over orifice of nozzle Back pressure adjusts position of motor control valve or other pneumatic device
47
Proportional Control Simple ON/OFF (Bang-Bang or Snap Action) often not sufficient Hydraulic hammer System sensitivity Erratic control response Proportional control means that a small error produces a small response while a larger error produces a larger response
48
Proportional Control Generally given in percentage of total control range required to fully open the valve Example: controller with 100-lb full range and a 10% proportional control would require 10-lb error before starting to open the valve. If the control setting is at 50-lb then the pressure would have to drop to 40-lb before the valve would respond to the error Moving the pivot point is one way to accomplish this action
49
Setting Proportional Control
Gauge piping, backpressure, nozzle size, etc define a maximum speed at which the controller can respond and a resulting lag in the response Always set the proportional control starting from a high setting – this allows for the existence of a large error without causing a response leaving the controlled variable in a stable condition Make small reductions in the proportional setting – the response of the valve will reach a level where the controller is trying to respond faster than the system can tolerate Increase the proportional control slightly to eliminate the instability – this yields the maximum response rate
50
More elaborate system Setup such that any pressure in bourdon tube would close the flapper against the nozzle Spring-opposed bellows extends in response to pressure and opens the flapper Position of the pivot point controls the amount of proportional action
51
Reset Action Used when deviation from control setting is not tolerable
Spring is replaced by a second bellows Response of the second bellows is delayed by a needle valve (repeat per minute) 1 Diaphragm
52
Reset Action System response is set to 3 – 15 lb to stroke the valve and 10% proportional setting System is stable at 14 lb Response if system drops off by 1 lb is as follows: Pressure decrease is sensed at the Bourdon tube causing the nozzle to open and the diaphragm to vent This change is sensed immediately at the proportional bellows but delayed by the needle valve to the reset bellows Reset acts like a spring resisting the change but it will slowly vent through the needle valve and allow the change to occur Without reset the system pressure would drop to 12.8 lb by proportional action alone Without reset the system would maintain this value With reset the system returns slowly to the original values Read the text for more details
53
Rate of Response Reset action can only occur at a specific maximum speed defined by tubing and the leak rate of the needle valve During the time the reset action takes to occur the product being produced in the process can be ruined Rate of Response controls can partially eliminate this problem by allowing the controller to operate temporally at 0% proportional action Another needle valve is added to the inlet line for the proportional control bellows This needle must never be closed more than the reset needle or the controller will always function at 0% proportional control
54
Proportional, Reset and Rate Summary
Proportional – sets the range over which the controller will take action – large proportional can generate an offset – small proportional will introduce instability Reset – allows the controller to act with large proportional band in response to a disturbance and then with a small proportional band as control is established eliminating both the offset and the instability Rate – allows the controller to respond to how quickly the error develops – not usually needed for many control applications – most important when large rapid upsets are expected
55
Proportional Only Proportional plus Reset Upper control limit 100% 10% Lower control limit Proportional plus Reset plus Rate
56
No-Bleed Relay Controller of the previous types are best suited for controlling processes change slowly Air relays are used when faster response and better control are required The back pressure from the nozzle is applied to an air relay instead of the diaphragm of the motor valve The air relay amplifies the response of the back pressure from the controller using a pair of diaphragms that have a 12:1 area ratio This means that only a 1 lb back pressure signal from the controller is sufficient to provide 12 lb to stroke the motor valve
57
(20 lb inlet)
58
Valve Positioner Pressure from controller may not provide enough force to overcome friction at the motor valve stem Signal from controller is passed to a bellows mechanically connected to a second orifice/nozzle and an air relay Position of valve stem is not the controlling input for passing supply air to the motor valve diaphragm Typically used on large motor valves
59
Electric Controllers Electric Valve Controller (ON/OFF)
Proportional Controller
60
Control Methods Controlled variables
Flow rates Liquid levels Pressures Temperatures In almost all situations control is effected by the use of regulating valves
61
Control of Process Variables
Measure the variable Compare the measurement to the set point Use the error to adjust the position of the regulating valve Provide feedback to the controller
62
Flow rates Control generally accomplished by changing the output of a pump of compressor Control installed on the output side Three examples: Centrifugal pump controlled with throttling valve PD pump controlled using throttling valve and a bypass loop Plunger pump (steam drive) controlled using throttling valve to control the supply of steam to the pump
63
Centrifugal Pump Closing throttling valve (control valve) will change the flow from A to B Back pressure between the pump and valve will rise along the performance curve to point B No bypass is required because the pump can spin on closed line without damage Flow Recorder Controller
64
Positive-displacement Pumps
Pump output is constant for each stroke Control is still effected by throttling the output from the pump but the unused flow must bypass back to the suction side of the pump to avoid damage due to excess pressure VFD can also be used to reduce the pump cycling rate
65
Plunger Pump Control is established by controlling the flow of steam to the pump piston The same system can be used with a variety of air-operated pumps
66
Level Control Level control – float or diaphragm element regulating flow Into the tank Out of the tank
67
Pressure Control Regulating the flow of vapor leaving a tank
Separate from a level controller in a closed system
68
Process Temperature Controlled by regulating the amount of sensible heat added to a system Note once again the flow control is on the output side of the flow
69
Process Control Efficiency
Influenced by system response – time required for process variables to adjust to the set point after a disturbance Time delay caused by Signal path – detect the error, adjust the flow, interpret process feedback Process time – heat created or lost by reactions, volume changes, fluid flow limitations
70
Process Control Effect of Proportional Band
100% = more stable process but larger variation 40% = tighter control but less stable process Proportional only will also typically introduce an offset from the set point Offset can be minimized by using reset in addition to proportional control Some controllers (especially temperature control) use a rate function to increase the response to large disturbances
71
Cascade Control Two measured variables are interlocked into one control loop Objective is to provide precision by overcoming time lag in control response Uses a primary control loop to adjust the set point of a secondary control loop Adjustment of set points should always be made gradually when manual changes are made
72
Control System Examples
Absorber tower Flow indicating controller (FIC) – regulate flow of lean oil into absorber tower Level controller (LC) on the output side regulates rich oil leaving system Low level alarm (LLA) installed in the tower as back up in case of failure of the level controller or its control valve Scrubber Level controller along with a high-level alarm (HLA) indicating that the level controller is activating High Level shutdown (HLSV) is a simple float-type switch Absorber pressure (in fact entire system pressure) is maintained with a pressure control (PC) on the residue gas outlet The tower has a pressure safety valve (PSV) as a back up to this primary device Feedback loop in some plants links the lean oil flow to the inlet gas flow using a ratio relay (RR) Freezing problems can be detected using a differential pressure indicator (DPI)
74
Fractionator Temperature and pressure control were covered in Chapter 3 (keep in mind for final exam) Pressure control using a hot-gas bypass PC – A controls the tower pressure Pressure in the accumulator varies with the temperature of the condenser outlet temperature
75
Fractionator Without intervention the pressure can become so low that the reflux pump could not pump reflux back to the tower Another pressure control loop is used to send hot gas bypass to the output side of the condenser The hot gas maintains the accumulator pressure
77
Control when output is vapor
Pressure control regulating the amount of vapor leaving the accumulator
78
Flooded-condenser Pressure Control
Flow control on the product output line Control valve closes until condenser tubes are flooded with liquid product This reduces the heat transfer surface and raises the temperature Problems can occur is some of the product does not condense to liquid – can be corrected with the addition of a level controller and three-way valves to prevent the accumulator from running dry
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.