Download presentation
Presentation is loading. Please wait.
1
Russian Conference on Lightning Protection
St. Petersburg, May, 17-19, 2016 “Separation Distance for the Electrical Insulation of the External Lightning Protection System” F. Heidler University of the Federal Armed Forces, Munich
2
Lightning Protection System LPS acc. to IEC 62305-3
External Lightning Protection System (External LPS) Air termination system to intercept a lightning flash Down conductor system to conduct the lightning current safely to earth Earth termination system to disperse the lightning current into the earth Internal Lightning Protection System (Internal LPS) Lightning equipotential bonding to prevent dangerous sparking within the structure Separation distance
3
Side flashes and separation distance
1 MV u 250 ns t L PEN Bonding bar Side flashes LPS Installation
4
Damages
5
Separation distance ‚s‘ acc. to IEC 62305-3
The separation distance s is the minimum distance between the external LPS and installations inside the structure to avoid side flash General equation for the separation distance: ki : Induction coefficient kc: Configuration coefficient km: Material coefficient l: Length
6
Material coefficient km and induction coefficient ki
km considers the dielectric strength of air in relation to construction materials, e.g. bricks ki considers the voltage induction due to current steepness of subsequent return strokes Material km Air 1 Concrete, bricks 0,5 Lightning protection level (LPL) imax imax/T1 ki I 50 kA 200 kA/µs 0.08 II 37.5 kA 150 kA/µs 0.06 III and IV 25 kA 100 kA/µs 0.04
7
Configuration coefficient kc and length l acc. to IEC 62305-3
Length l: Total length along the air termination and the down conductors from the point, where the separation distance is to be considered to the nearest equipotential bonding point Coefficient kc: kc takes into account the percental current share through the individual air-termination conductors/down conductors. s l 50 % 100 % Down conductor Installation loop kc = 0,5 PAS Bonding bar
8
Configuration coefficient kc
Evaluation of the configuration coefficient kc is the main problem Therefore, in the standard IEC two different approaches are given with respect to practical application. Simplified approach for the configuration coefficient kc Detailed approach for the configuration coefficient kc
9
Simplified approach for the configuration coefficient kc
Use of pre-defined values for kc (a) Franklin rod (1-dimensional): kc = 1 (b) 2-dimensional: kc = 0.66 (c) 3-dimensional: kc = 0.44 Correction for 3-dimensional meshed air termination and down conductor system with different values of the spacing and of the length of the down-conductors h: Height of the structure c: Spacing between down conductors n: Number of down conductors
10
Detailed approach for the configuration coefficient kc
𝒔= 𝒌 𝒊 𝒌 𝒎 ∙( 𝒌 𝒄𝟏 𝒍 𝟏 + 𝒌 𝒄𝟐 𝒍 𝟐 +…+ 𝒌 𝒄𝒏 𝒍 𝒏 ) At every next junction (joint) of the air-termination mesh the current is reduced to 50 %, but the value of kcn must not be less than 1/n (n: Number of the down conductors). The values of kc have to be considered from the point of strike to the edge of the roof using the shortest path. The arrows indicate the paths from the different injection points (A,B,C) of the current to the edge of the roof. The lengths of the arrows correspond to the length l1, l2 … ln
11
Calculation of the separation distance s
Detailed evaluation of the separation distance is more or less only possible via calculations with computer codes: First step: Calculation of the induced voltage at the proximity with a computer code (used computer code CONCEPT) Second step: Evaluation of the separation distance from the calculated voltage by the use of the “Constant- area-criterion”
12
Examples of induced voltages
LPS type “a”: Air termination: mesh, Point of strike: corner, Induced Voltage: Corner loop (b) LPS type “b”: Air termination: metal roof, Point of strike: center, Induced Voltage: Center wire
13
Spark-over behavior of an air gap
Static onset voltage Uo Voltage-time characteristic for impulse voltages with different steepness Illustration of the constant-area-criterion
14
Meshed wires and Metal Attic
LPS Configuration Motivation for the computer simulations: Comparison of the formula of IEC IEC standard series contains no formulae to determine the separation distance for natural components (metal roofs, metal facades, metal attics, etc.) LPL II/LPS II is applied LPS Type Air Termination Down Conductors a Meshed Wires Wires b Metal Roof c Metal Walls d Meshed wires and Metal Attic
15
Overview of the configurations
16
Current injection and induction loops
corner side center corner loop center wire
17
Induced voltages for meshed wire air termination (LPS Type “a”)
Structure size Induction to Peak voltage [kV] Point of strike Corner Side Center 20 m x 20 m 10 m high corner loop 1770 628 506 center wire 471 426 1030 20 m high 2150 974 1060 711 678 1440 40 m high 2530 1670 1660 1380 1190 1470 60 m high 2870 2010 2160 1820 1580 1930 60 m x 60 m 1780 155 243 257 247 1120
18
Separation distance for meshed wire LPS (LPS Type “a”)
Base area Height Configuration Separation distance CONCEPT Calculation Simplified approach Detailed approach 20 m x 20 m 10 m Corner loop, corner strike 29 21.8 20.0 Center wire, center strike 23 22.5 20 m 44 38.5 30.0 34 40 m 65 69.2 45.0 60 m 78 98.1 60 52 60 m x 60 m 28 19.2 32 28.8
19
Conclusion for meshed wire LPS (LPS Type “a”)
1. Corner Strike The separation distance is underestimated with the simplified approach of IEC by about 15…30 % for heights up to 20 m. The separation distance is even more underestimated with the detailed approach of IEC 2. Center Strike The separation distance is overestimated with the simplified approach of IEC by up to about 100 % for heights greater than 10 m. The detailed approach of IEC give good results.
20
Studied structures of LPS type ‚b‘ (metal roof)
corner strike side center loop wire
21
Separation distance for metal roof (LPS Type “b”)
Structure size location Separation distance s [cm] Point of strike Corner Side Center 20 m x 20 m 10 m high corner loop 8,4 8,1 7,8 center wire 7,6 20 m high 17 40 m high 34 60 m high 49 48 60 m x 60 m 6,1 2,8 2,2 2,4 2,6
22
Conclusions for metal roofs
Using a metal roof as a natural component in combination with down conductor wires significantly reduces the separation distances (by a factor of 2 and more). The separation distances are fairly independent of the point of strike and the location of the induction loop. The separation distance is predominantly a function of the structure’s height. The separation distance can be calculated by the following formula: LPS I II III / IV k 0,012 0,009 0,006
23
Studied structures of LPS type ‚c‘ (metal walls)
Center strike Corner strike Side strike Corner loop
24
Peak voltages for metal walls (LPS type “c”)
Structure size Location Peak voltage [kV] Point of strike Corner Side Center 20 m x 20 m 10 m high corner loop 441 167 395 center wire 99 60 1010 20 m high 440 110 500 160 75 1430 60 m x 60 m 430 85 190 100 1120
25
Conclusion for metal walls (LPS type “c”)
1. Strike to the corner or rim of the roof Induced voltages were less than 500 kV (for LPL II) Separation distance of s 15 cm is sufficient 2. Strike to the center of the roof and center wire induction Peak voltages are not much different to an LPS type „a“ structure The reduction of ‘s’ compared to a type “a” LPS is ≤ 20 %
26
Meshed wire LPS with an attic (LPS Type “d”)
center strike side strike corner strike LPS type “d” center wire corner loop Base Area 20 m x 20 m: Height 20 m Width of attic: 0,5 m and 1 m
27
Meshed wire LPS with an attic (LPS Type “d”) (Structure size 20 m x 20 m x 20 m)
Separation distance in cm Center strike Side strike Corner strike For the cases of side strike and center strike no significant reduction of the separation distance is found, irrespective of the sheet width Only for the worst-case combination of “corner strike/corner loop” the separation distance is reduced by about 30 % for the sheets width of 0.5 m and by about 40 % for the sheets width of 1 m.
28
Conclusion 1. Meshed wire LPS 2. Metal roof 3. Metal wall
Corner strike: Simplified approach and detailed approach of IEC underestimate the separation distance, but simplified approach gives better results Center strike: Detailed approach gives satisfying results for the separation distance, but the simplified approach may overestimate the separation distance strongly 2. Metal roof The separation distance is reduced by the factor of about The separation distance is proportional to the height over the equipotential plane. 3. Metal wall If the point of strike is at the top of the metal wall, the separation distances are relatively small. About 15 cm are sufficient to keep the required separation distances for class II LPS In case of center strike the use of a metal facade gives only marginal reduction of the separation distances 4. Metal attic The use of a circumferential metal attic is of minor influence, whereat the separation distance is reduced by some tens of percents, at best.
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.