Gas fitting line Sizing
2
Natural / LP Gas fitting line Sizing Information Needed.
Type of Gas = ? Natural / LPG Type of Gas Heat Value = ? Heating Value Mj/m³ & Relative Density (RD) Available Pressure at start of consumer piping The Gas Authority should be consulted to determine the maximum pressure drop Allowed in area. To minimise noise the maximum pressure drop should not exceed 10% of the operating pressure. Type A appliances minimum - inlet pressure Clause No Table 4.1 Natural Gas- minimum - inlet pressure kPa / Min. Inlet Pressure LPG 2.75 kPa Pressure drop = ? 0.075kPa Natural gas / 0.25 LPG
3
Natural / LP Gas fitting line Sizing Information Needed.
Type of Pipe = ? Copper / Steel /Plastic Mj/h each Appliance ? Appliance Data Plate Manufactures Information sheet Main Run = ? Measure plan
4
Natural Gas fitting line Copper
HWS 30Mj/h Gas Appliance Fitting line sizing. Main run is from the meter connection /supply to the gas appliance furthest away. B 1m 1.5m 1m + 13m +1.5m +1m = 16.5m 13m Main run = 16.5m Main run = A B A 1m Meter connection/ Gas Supply
5
Gas fitting line Sizing Ex 1
Main Run = 16.5m Type of Gas = Natural Type of Pipe = Copper Pressure drop = 0.075kPa Mj/h each Appliance 30 Mj/h Place information into Pipe sizing Chart Check gas reg. AG601 Table F1 Natural gas sizing
6
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 30
Gas Flow Mj/hr NominalSize DN A-B 30 Check gas reg. AG601 Table F1 Natural gas sizing
7
Length of straight pipe in metres
TABLE F1 Pressure Drop of kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 18 20 Main Run = 16.5 m next highest 18 m Mj/h = 30Mj/h next highest 67Mj/h Pipe sizing taken right to left 20mm
8
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 30 20
Gas Flow Mj/hr NominalSize DN A-B 30 20 Check gas reg. AG601 Table F1 Natural gas sizing
9
Natural Gas fitting line Sizing.
Job 2 Fitting line with branch. Copper tube.
10
Natural Gas fitting line
HWS 30Mj/h Fitting line sizing. Main run is from the meter connection /supply to the gas appliance furthest away. C 1m D 1.5m 1m Cooker 26Mj/h 5m 10m 1m + 2m+10m+1.5m +1m = 15.5m B Main run = 15.5m A 2m 1m Main run = A - C Meter connection/ Gas Supply
11
Gas fitting line Sizing Ex 2
Main Run = 15.8m Type of Gas = Natural Type of Pipe = Copper Pressure drop = 0.075/kPa Mj/h each Appliance From Chart Place information into Pipe sizing Chart Check gas reg. AG601 Table F1 Natural gas sizing
12
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +30 = 56
Gas Flow Mj/hr NominalSize DN A-B = 56 B-C 30 B-D 26 Check gas reg. AG601 Table F1 Natural gas sizing
13
Length of straight pipe in metres
TABLE F1 Pressure Drop of kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 16 20 Main Run = 15.5 m next highest 16 m A-B Mj/h = 56Mj/h next highest 71Mj/h Pipe sizing taken right to left 20mm
14
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +30 = 56 20
Gas Flow Mj/hr NominalSize DN A-B = 56 20 B-C 30 B-D 26 Check gas reg. AG601 Table F1 Natural gas sizing
15
Length of straight pipe in metres
TABLE F1 Pressure Drop of kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 16 20 Main Run = 15.5 m next highest 16 m B-C Mj/h = 30Mj/h next highest 71Mj/h Pipe sizing taken right to left
16
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +30 = 56 20
Gas Flow Mj/hr NominalSize DN A-B = 56 20 B-C 30 20 B-D 26 Check gas reg. AG601 Table F1 Natural gas sizing
17
Length of straight pipe in metres
TABLE F1 Pressure Drop of kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 16 20 Main Run = 15.5 m next highest 16 m B-D Mj/h = 26Mj/h next highest 71Mj/h Pipe sizing taken right to left
18
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN B-C B-D A-B
Gas Flow Mj/hr NominalSize DN B-C B-D A-B = 56 20 30 20 26 20 Check gas reg. AG601 Table F1 Natural gas sizing
19
LPG fitting line Sizing.
Job 1 Fitting line with branch.
20
LPG fitting line Main run = A - C Fitting line sizing.
HWS 188Mj/h Fitting line sizing. Main run is from the Gas supply to the gas appliance furthest away. C 1m D 1.5m 1m Cooker 26Mj/h 5m 10.3m 1m + 2m+10.3m+1.5m +1m = 15.8m B Main run = 15.8m A 2m 1m Main run = A - C Gas Supply
21
Gas fitting line Sizing Ex 1
Main Run = 15.8m Type of Gas = LP Type of Pipe = Copper Pressure drop = 0.25kPa Mj/h each Appliance From Chart Place information into Pipe sizing Chart Check gas reg. AG601 Table F29 LP gas sizing
22
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +188 = 214
Gas Flow Mj/hr NominalSize DN A-B = 214 B-C 188 B-D 26 Check gas reg. AG601 Table F29 LP gas sizing
23
Length of straight pipe in metres
TABLE F29 Pressure Drop of kPa LP GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 26 19 13 9 57 38 30 27 24 22 21 20 81 54 43 36 84 28 64 25 15 212 142 113 96 281 76 69 223 60 725 491 390 331 659 262 240 504 208 1628 1104 879 747 1283 594 544 984 472 32 3155 2145 1709 1454 2186 1156 1061 1679 920 40 5358 3647 2909 2477 4974 1974 1810 3826 1571 50 12123 8271 6607 5631 9274 4493 4123 7143 3582 65 22519 15389 12305 10495 14936 8382 7694 11514 6689 16 15 Main Run = 15.8 m next highest 16 m A-B Mj/h = 214Mj/h next highest 223Mj/h Pipe sizing taken right to left 15mm
24
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +188 = 214
Gas Flow Mj/hr NominalSize DN A-B = 214 15 B-C 188 B-D 26 Check gas reg. AG601 Table F29 LP gas sizing
25
Length of straight pipe in metres
TABLE F29 Pressure Drop of kPa LP GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 26 19 13 9 57 38 30 27 24 22 21 20 81 54 43 36 84 28 64 25 15 212 142 113 96 281 76 69 223 60 725 491 390 331 659 262 240 504 208 1628 1104 879 747 1283 594 544 984 472 32 3155 2145 1709 1454 2186 1156 1061 1679 920 40 5358 3647 2909 2477 4974 1974 1810 3826 1571 50 12123 8271 6607 5631 9274 4493 4123 7143 3582 65 22519 15389 12305 10495 14936 8382 7694 11514 6689 16 15 Main Run = 15.8 m next highest 16 m B-C Mj/h = 188Mj/h next highest 223Mj/h Pipe sizing taken right to left 15mm
26
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +188 = 214
Gas Flow Mj/hr NominalSize DN A-B = 214 15 B-C 188 15 B-D 26 Check gas reg. AG601 Table F29 LP gas sizing
27
Length of straight pipe in metres
TABLE F29 Pressure Drop of kPa LP GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 26 19 13 9 57 38 30 27 24 22 21 20 81 54 43 36 84 28 64 25 15 212 142 113 96 281 76 69 223 60 725 491 390 331 659 262 240 504 208 1628 1104 879 747 1283 594 544 984 472 32 3155 2145 1709 1454 2186 1156 1061 1679 920 40 5358 3647 2909 2477 4974 1974 1810 3826 1571 50 12123 8271 6607 5631 9274 4493 4123 7143 3582 65 22519 15389 12305 10495 14936 8382 7694 11514 6689 16 10 Main Run = 15.8 m next highest 16 m B-D Mj/h = 26Mj/h next highest 64Mj/h Pipe sizing taken right to left 10mm
28
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +188 = 214
Gas Flow Mj/hr NominalSize DN A-B = 214 15 B-C 188 15 B-D 26 10 Check gas reg. AG601 Table F29 LP gas sizing
29
To Exit press button To continue press enter or Space bar key
Fitting line with more then one branch
30
Natural Gas fitting line Sizing
Job 3 Fitting line with more then one branch
31
Natural Gas fitting line
1m Cooker 26Mj/h Space heater 35Mj/h 1.m 6m F HWS 188Mj/h 3.5m D 1m 2.5m 1.5m C 1m 5m 10m 1m + 2m+5m+1m+2.5m +5m+1m = 17.5m B Main run = 17.5m A 2m 1m Main run = A - E Meter connection/ Gas Supply
32
Gas fitting line Sizing Ex 3
Main Run = 17.5m Type of Gas = Natural Type of Pipe = Copper Pressure drop = 0.075kPa Mj/h each Appliance From Chart Place information into Pipe sizing Chart Check gas reg. AG601 Table F1 Natural gas sizing
33
Length of straight pipe in metres
TABLE F1 Pressure Drop of kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 18 32 Main Run = 17.5 m next highest 18 m A-B Mj/h = 249Mj/h next highest 257Mj/h Pipe sizing taken right to left
34
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN B-E C-F A-B
Gas Flow Mj/hr NominalSize DN B-E C-F A-B = 249 32 B-C = 223 C-D 188 26 35 Check gas reg. AG601 Table F1 Natural gas sizing
35
Length of straight pipe in metres
TABLE F1 Pressure Drop of kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 18 32 Main Run = 17.5 m next highest 18 m A-C Mj/h = 223Mj/h next highest 257Mj/h Pipe sizing taken right to left
36
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN B-E C-F A-B
Gas Flow Mj/hr NominalSize DN B-E C-F A-B = 249 32 B-C = 223 32 C-D 188 26 35 Check gas reg. AG601 Table F1 Natural gas sizing
37
Length of straight pipe in metres
TABLE F1 Pressure Drop of kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 18 32 Main Run = 17.5 m next highest 18 m C-D Mj/h = 188Mj/h next highest 257Mj/h Pipe sizing taken right to left
38
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN B-E C-F A-B
Gas Flow Mj/hr NominalSize DN B-E C-F A-B = 249 32 B-C = 223 32 C-D 188 32 26 35 Check gas reg. AG601 Table F1 Natural gas sizing
39
Length of straight pipe in metres
TABLE F1 Pressure Drop of kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 18 20 Main Run = 17.5 m next highest 18 m B-E Mj/h = 26Mj/h next highest 67Mj/h Pipe sizing taken right to left
40
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN B-E C-F A-B
Gas Flow Mj/hr NominalSize DN B-E C-F A-B = 249 32 B-C = 223 32 C-D 188 32 26 20 35 Check gas reg. AG601 Table F1 Natural gas sizing
41
Length of straight pipe in metres
TABLE F1 Pressure Drop of kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 18 20 Main Run = 17.5 m next highest 18 m B-E Mj/h = 35Mj/h next highest 67Mj/h Pipe sizing taken right to left
42
Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN B-E C-F A-B
Gas Flow Mj/hr NominalSize DN B-E C-F A-B = 249 32 B-C = 223 32 C-D 188 32 26 20 35 20 Check gas reg. AG601 Table F1 Natural gas sizing
43
Gas fitting line sizing
Sizing of Fitting Line is quite easily with the right information etc :- Type of Gas / Type of Pressure drop / Type of Piping Gas Reg. AG601 Questions ? B Makin 18/5/2005 RMIT