Presentation is loading. Please wait.

Presentation is loading. Please wait.

Planning The Electrical System

Similar presentations


Presentation on theme: "Planning The Electrical System"— Presentation transcript:

1 Planning The Electrical System
4 Requirements for a well planned system: Safe Adequate for convenience Efficient Expandable

2 Types of Branch Circuits
Individual General Purpose Small Appliance Laundry Bedroom Def: Branch Circuit- circuit conductors between the final overcurrent device protecting the circuit and the outlets installed.

3 NEC Requirements

4 Individual Circuits Motors ½ horsepower and larger
Equipment in which operation and/or temperature is critical All 240 volt equipment NEC:

5 Small Appliance Circuits
Two or more small appliance circuits required Must be 20 amp No other outlets may be supplied (Lighting) May supply other outlets in the same kitchen or specified room ( pantry, breakfast room, dining room, other similar area). Cannot serve more than one kitchen. NEC: & (B)

6 Laundry Circuits At least one laundry circuit is required by NEC
Must be 20 amp The circuit shall not serve any other outlets NEC: & (F)

7 Bathroom Circuit At least one laundry circuit is required by NEC
Must be 20 amp The circuit shall not serve any other outlets except in same bathroom. NEC: & (D)

8 General purpose circuits
All lighting outlets must be served with general purpose circuits All receptacles not on an appliance, laundry, or individual circuit May be 15 or 20 amp Bedroom circuit must be Arc-Fault protected NEC: ,

9 Types of Outlets Lighting Outlets Convenience Outlets
Special Purpose Outlets Def: Outlet- a point in the wiring system at which current is taken to supply equipment

10 Lighting Outlet Requirements
At Least one wall switch controlled lighting outlet shall be installed in each: habitable room, bathroom, hallway, stairways (at both levels if over 6 steps), attached garage detached garage with electrical power exterior light at grade level. NEC:

11 Lighting Outlet Requirements
At least one lighting outlet containing a switch or controlled by a switch is required in Attic Under floor space Utility room Basement NEC:

12 Lighting Load A unit load of not less than that specified in 05 NEC Table

13 Lighting Location No NEC recommendations
Good lighting is a practical combination of: Lamp height Light output (lumens) Lamp spacing Correct color Fixture style (directed lighting) See 14th Edition Agriculture Wiring Handbook for specific agricultural applications

14 Switch Location No NEC recommendations Common Practices:
Install Switch on latch side of door Install switch in same room as light Locate switches about 48 inches above floor normally Locate switches as high as can be reached conveniently for buildings housing livestock. Install switches at each principle entrance (use of three-way switches is recommended for multiple entrances to same room) See 14th Edition Agriculture Wiring Handbook

15 General Receptacle Outlet Requirements
IN EVERY KITCHEN,FAMILY ROOM, DINING ROOM, PARLOR, LIBRARY,DEN SUNROOM, BEDROOM, RECREATION ROOM, OR SIMILAR ROOM RECEPTACLES SHALL BE INSTALLED ACCORDING TO 05 NEC ARTICLE No point measured horizontally along the floor line in any wall space can be more than 6 feet from a receptacle outlet Wall space- any unbroken space of 2 feet or more NEC (A)

16 Receptacle Outlet Requirements
SEE 05 NEC (B) Small Appliance (1) Receptacle Outlets Served (2) No Other Outlets (3) Kitchen Receptacle Requirements SEE 05 NEC (C ) Countertops Wall Counter Spaces Island Counter Spaces Penninsular Separate Spaces Receptacle Outlet Location

17 SEE 05 NEC (D ) Bathrooms SEE 05 NEC (E ) Outdoor SEE 05 NEC (F) Laundry


Download ppt "Planning The Electrical System"

Similar presentations


Ads by Google