BASIC ELECTRICAL TECHNOLOGY Chapter 3 - Three Phase System
DET 211/3 Chapter 3 - Three Phase System
2
INTRODUCTION TO THREE PHASE SYSTEM
In general, three phase systems are preferred over single phase systems for the transmission of the power system for many reasons, including the following: Thinner conductors can be used to transmit the same kVA at the same voltage, which reduces the amount of copper required (typically about 25% less) and turn reduces construction and maintenance costs. The lighter lines are easier to install, and the supporting structures can be less massive and farther apart. In general, most larger motors are three phase because they are essentially self starting and do not require a special design or additional starting circuitry.
3
Three phase voltages A 3-phase generator basically consists of a rotating magnet (called the rotor) surrounded by a stationary winding (called the stator). Three separate windings or coils with terminals a-a’, b-b’ and c-c’ are physically placed 120o apart around the stator.
4
Generated Voltages The three phase generator can supply power to both single phase and three phase loads
5
The sinusoidal expression for each of the phase voltages
6
The phasor diagram of the phase voltages
The effective value of each is determined by
7
If the voltage sources have the same amplitude and frequency ω and are out of the phase with each other by 120o, the voltages are said to be balanced. By rearranging the phasors as shown in figure below, so Where
8
Generator and Load Connections
Each generator in a 3-phase system maybe either Y- or D-connected and loads may be mixed on a power system. Z Z
9
Wye Connected Generator
Applying KVL around the indicated loop in figure above, we obtain
10
Wye Connected Generator
For line-to-line voltage VAB is given by:
11
Wye Connected Generator
Phasor Diagram
12
Wye Connected Generator
The relationship between the magnitude of the line-to-line and line-to-neutral (phase) voltage is: The line voltages are shifted 300 with respect to the phase voltages. Phasor diagram of the line and phase voltage for the Y connection is shown below. VAB VAN VBC VBN VCA VCN Line-to-line voltages Phase voltages Rearrange
13
Delta Connected Generator
For line-to-line voltage VAB is given by:
14
Delta Connected Generator
The relationship between the magnitude of the line and phase current is: The line currents are shifted 300 relative to the corresponding phase current. Phasor diagram of the line and phase current for the Y connection is shown below. IA IAB IBC IB ICA Line-to-line currents Phase currents IC
15
Phase sequence The phase sequence is the order in which the voltages in the individual phases peak. VA VB VC VA VC VB abc phase sequence acb phase sequence
16
Power relationship-phase quantities
The power equations applied to Y-or D- load in a balanced 3-phase system are: Real power Unit=Watts(W) Reactive power Unit=Volt-Amps-Reactive (VAR) Apparent power Unit=Volt-Amps (VA) q - angle between voltage and current in any phase of the load
17
Power relationship-Line quantities
The power equations applied to Y-or D- load in a balanced 3-phase system are: Real power Reactive power Apparent power q - angle between phase voltage and phase current in any phase of the load
18
Y-Y connections (i.e: Y-connected source with a Y-connected load).
Since both the three-phase source and the three-phase load can be either Y- or - connected, we have 4 possible connections: Y-Y connections (i.e: Y-connected source with a Y-connected load). Y- connection. - connection -Y connection
19
(i) Y connected generator/source with Y connected load
20
D- must consists of three equal impedances
(ii) Y-D Connection A balanced Y- system consists of a balanced Y-connected source feeding a balanced -connected load Z/3 Z D- must consists of three equal impedances
21
(iii) ∆-∆ Connection A balanced ∆- system consists of a balanced ∆-connected source feeding a balanced -connected load Z Z
22
(iv) D-Y Connection A balanced -Y system consists of a balanced -connected source feeding a balanced Y-connected load Z/3 Z
23
Example 1 A 208V three-phase power system is shown in Figure 1. It consists of an ideal 208V Y-connected three-phase generator connected to a three-phase transmission line to a Y-connected load. The transmission line has an impedance of 0.06+j0.12W per phase, and the load has an impedance of 12+j9W per phase. For this simple system, find The magnitude of the line current IL The magnitude of the load’s line and phase voltages VLL and VfL The real, reactive and apparent powers consumed by the load The power factor of the load The real, reactive and apparent powers consumed by the transmission line The real, reactive and apparent powers supplied by the generator The generator’s power factor
24
Example 1 Figure 1 0.06 i0.12 V Vcn=120-2400 Van=12000 208V
Z Z=12+ i9 - + 0.06 _ i0.12 V Van=12000 Vbn=120-1200 Vcn=120-2400 208V Figure 1
25
The magnitude of the line current IL
Solution Example 1 The magnitude of the line current IL So, the magnitude of the line current is thus 7.94 A
26
and the magnitude of the load’s line voltage is
Solution Example 1 (b) The magnitude of the load’s line and phase voltages VLL and VfL The phase voltage on the load is the voltage across one phase of the load. This voltage is the product of the phase impedance and the phase current of the load: Therefore, the magnitude of the load’s phase voltage is and the magnitude of the load’s line voltage is
27
Solution Example 1 (c) The real power consumed by the load is
The reactive power consumed by the load is The apparent power consumed by the load is
28
(d) The load power factor is
Solution Example 1 (d) The load power factor is (e) The current in the transmission line is and the impedance of the line is or per phase. Therefore, the real, reactive and apparent powers consumed in the line are:
29
Solution Example 1 (f) The real and reactive powers supplied by the generator are the sum of the powers consumed by the line and the load: The apparent power of the generator is the square root of the sum of the squares of the real and reactive powers:
30
Solution Example 1 (g) From the power triangle, the power factor angle is Therefore, the generator’s power factor is
31
Assignment 2 A 208V three-phase power system is shown in Figure 2. It consists of an ideal 208V Y-connected three-phase generator connected to a three-phase transmission line to a -connected load. The transmission line has an impedance of 0.06+j0.12W per phase, and the load has an impedance of 12+j9W per phase. For this simple system, find The magnitude of the line current IL The magnitude of the load’s line and phase voltages VLL and VfL The real, reactive and apparent powers consumed by the load The power factor of the load The real, reactive and apparent powers consumed by the transmission line The real, reactive and apparent powers supplied by the generator The generator’s power factor
32
Assignment 2 Figure 2