PV100&PV200 Solar Pumping VFD

Similar presentations


Presentation on theme: "PV100&PV200 Solar Pumping VFD"— Presentation transcript:

1 PV100&PV200 Solar Pumping VFD

2 CONTENTS Solar Pumping System Model No. Functions and Applications

3 Features: Solar Pumping System Green Power Full-auto Running
Directly drive pump up water

4 PV100&PV200 Features Solar Pumping System
DC Drive Solar Power Max Power Point MPPT Algorithm (no need to set voltage range) Support AC/DC input Support water-overflowing dormancy auto-control Full-auto start

5 CONTENTS Solar Pumping System Model No. Functions & Applications

6 PV100 Model No. Power Single Phase 220V: 0.2KW~2.2KW Terminal
5*Digital Input (DI1~DI4,DI7) 2*Analog Input(0~10V,0~20mA) 1*Digital Output(Y1) 1*Relay Output(R1)

7 PV200 Model No. Power Three Phase 220V: 0.75KW~75KW
Terminal 7*Digital Input(DI1~DI7) 3*Analog Input(0~10V,0~20mA, -10V~10V) 2*Digital Output(Y1,Y2) 2*Relay Output(R1,R2)

8 Model No. Model Number

9 Power & Voltage Configuration
Model No. Power & Voltage Configuration 380V Input Maximum Input DC Voltage 800VDC Recommended Open Circuit Voltage for Solar Panel 600~700VDC 220V Input Maximum Input DC Voltage 400VDC Recommended Open Circuit Voltage for Solar Panel 300~370VDC

10 Model No. Installation Installation: support din rail mounting, wall mounting, and cabinet mounting. Wirings: wires plug through the whole, wirings connected by top-enter and bottom-exit from 90kw, easy for cooper buswork wirings, built-in DC reactor, save space, save wirings.

11 CONTENTS Solar Pumping System Model No. Functions & Applications

12 Wirings Functions & Applications
220V ≤15KW or 380V ≤30KW Wirings Drawing 220V ≥18KW or 380V ≥ 37KW Wirings Drawing

13 Weak-light Voltage Setting
Functions & Applications Full-auto Running After solar pumping inverter finish power-off, when solar panel restore voltage, solar inverter need to do setting as below: 1)Set F02.00=1, started by terminal ; 2)DI1 and COM terminal been Shortened Weak-light Voltage Setting System weak-light voltage set by H00.25 1)380V inverter lowest voltage to 250VDC 2)220V inverter lowest voltage to 120VDC

14 Switch between Solar and Grid
Functions & Applications Switch between Solar and Grid Method 1: Parameter Control 1)disconnect Q1, and then close Q2, set H00.01=0, now power supplied by grid 2) disconnect Q2 , and then close Q1 , set H00.01=1, now power supplied by solar panel Method 2: Terminal Control Set H00.01=0, F04.01=51 1) disconnect Q1 , and then close Q2, disconnect DI2 , now power supplied by grid 2) disconnect Q2 , and then close Q1, and shorten DI2, now power supplied by solar panel

15 Control Mode Functions & Applications
1、Constant Voltage Adjustment Methods H00.02=0, voltage set by H 、Voltage Range Setting MPPT H00.02=1, search voltage range H00.04~H 、Auto- MPPT H00.02=2, system will auto-search the max power point according to solar panel voltage and sunlight intensity

16 Floater detect of full-water and dry-run
Functions & Applications Floater detect of full-water and dry-run H00.15 choose AI channel H00.17 is the value set to detect water level H00.24 is direction for floater detecting water level. When water level higher, and the detect value larger, set H00.24=1; when water level higher, and detect value smaller, set H00.24=0 。 When water level higher than H00.17, after delay H00.18, system enter dormancy; when water level lower than H00.17, after delay H00.16, system will start automatically.

17 Switch Detect Full-water and dry-run
Functions & Applications Switch Detect Full-water and dry-run F04.02=52, DI3 selects water level dormancy terminal input When DI3 valid, after delay H00.18, system enter dormancy; when DI3 invalid, after delay H00.16, system will start automatically.

18 Current detect of pump dry-run
Functions & Applications Current detect of pump dry-run ·Advantage: No require water sensor ·Need to set proper ampere level(H00.21) of pump dry run H00.21(0-100%): 100% corresponds to rated current of pump Setting of H00.21 1) Check current value of each pump when dry run, then set this value(%) in H00.21 2) If can not check current value of each pump when dry run, we recommend H00.21= 40% in 2.2kW and H00.21=45% in 4kW~7.5kW as dry run detected current value. For example PV100-2S-2.2B, pump rated current should be 10A. Set H00.21=40%, means dry run detected current value 4A; When pump dry run, inverter output current (Detected pump running current) lower than 4A, inverter will stop automatically after delay time H00.20 (Recommended to be 20S) When inverter stop, after delay time H00.22(Default setting 600s), inverter will restart again automatically.

19 Auto Switch Grid & Solar
Functions & Applications Auto Switch Grid & Solar H00.27=1

20 Auto Switch Grid & Solar
Functions & Applications Auto Switch Grid & Solar