Grounding the Electrical System
Reference: AAVIM “Electrical Wiring” Created May 2007
2
Purpose of the Grounding System
Fundamental to the safety of those installing, using, and servicing the electrical system Assures the system will work properly while preventing damage to the system
3
NEC Requirements All electrical systems serving structure must be bonded together Including the following Electrical wiring system Telephone system Phone system Burgular alarm system Cable or satellite system
4
Grounding The process of making a planned, continuous, connection between NON-CURRENT CARRYING parts of the electrical wiring installation and the earth and some other conducting body
5
Grounded Describes the act of being connected to the earth or some other conduction body that serves in place of the earth
6
Bonding Process in which all NON-CURRENT CARRYING METALLIC parts of the electrical wiring system are permanently joined together to form a CONTINUOUS grounding path
7
Bonding Reduces the differences in potential between each electrical system May be caused by power surges, lightning strikes or other types of ground fault type occurences
8
Parts of the Electrical System
Circuits Service Entrance Panel Metal Water Pipe Metal Gas pipe
9
Materials in Grounding System
Must be approved by NEC
10
The Grounding Electrode System
All materials must be grounded using approved bonding and grounding electrode systems Check with local building code
11
Metallic Pipe Water pipe must always be bonded to the service entrance panel, grounding electrode conductor, or grounding electrode Other metal pipe, such as gas pipe, which may become energized accidentally must be bonded to the electrical system grounded system
12
Use of Bonding Jumper To provide CONTINUOUS grounding path around devices such as water meters installed in metallic water pipe system
13
Types of Grounding Electrodes
14
Metal Underground Water Pipe
Must be bonded to the supplemental grounding system electrode and to the neutral bus bar in the SEP Connection must be made within 5 feet of entering structure Water pipe must be in direct contact with the earth for at least 10 feet
15
Concrete Encased Electrode
Electrode encased in foundation footing covered with at least 2 inches of concrete Electrodes must be at least 20 feet in length and consist of one or more ½” steel reinforcement bars
16
Ground Ring Bare Copper At Least #2 AWG or larger
Encircling residence for a length of 20 feet Buried at least 2 ½”
17
Metal Framework
18
Supplemental Electrodes
Typically made of metal rods, pipes, or plates
19
Rod and Pipe Electrodes
Iron or steel rod electrodes Must be 5/8” in diameter Pipe must be ¾” in diameter Galvanized or metal coated for corrosion resistance 8 feet in length Installed to a depth of 8” in direct contact with earth
20
Nonferrous rods must be listed at no less than ½”
Stainless Steel- ½” diamter Must be at or below ground level Must be protected from physical damage
21
Exceptions If electrode can not be driven more than 4” into the earth b/c of rock or other obstruction May be driven at an oblique and of no more than 45° from vertical At least 8” of the electrode must be in contact with earth
22
Multiple grounding rods
When more than one electrode grounding rod is used: Must be installed not less than 6 feet apart Must be bonded together with an approved bonding jumper to form single grounding electrode system
23
Plate Electrode May be used in areas where it is not possible to use a grounding rod or ring Steel/Iron Plate electrode must be ¼” thick Non-ferrous metal plate must be 0.06” thick 2 feet square Buried at least 2 1/2’
24
Grounding Electrode Conductor
NEC permits Copper Aluminium Copper-clad AL and AL-CU may not be used in contact with masonry, corrosive, or in direct contact with the earth
Similar presentations