Download presentation
Presentation is loading. Please wait.
1
Improve efficiency of cooling systems
2
Step by step Audit Map cooling system
Identify energy consumption of cooling system Evaluation of existing cooling system Verify cooling load Identify saving measures
3
Energy schema Energy schema of a 2.2 kW freeze facility
4
Map cooling system I
5
Map cooling system II
6
Manufacturers data Cooling capacity (kW) Vaporizer capacity (kW)
Electrical input power (kW) Condenser power (kW) Performance (COP) Mass flow (kg/h) Volume flow of oil cooler, power (m3/h, °C, kW) Operation limits (condensation temperatures max, min), evaporating temperatures (°C)
7
Additional components
8
Temperature levels
9
Additional data to measure
10
Evaporation and condensation charts
Evaporation and condensation charts of individual cooling liquids help to identify evaporation and condensation temperatures at given pressure Most pressure manometer measure gauge pressure in relation to ambient pressure – both pressure levels need to be added to achieve absolute presure On site measurements to be conducted by using Schrader valves Evaporation and condensation charts to be obtained from technology/coolpack.aspx
11
Calculating the energy consumption
Assumption: A cooling plant operates at 60%. ECcooling system = (Pcomp *0.6 + Pp,c,o * 0.9+ PL,c,o * 0.9) * BZ Alternatively it is possible to calculate the full load operating time (part time operations will be calculated in full load operating times, e.g. 2 hrs part load gives one hour full load) ECcooling system = Pcomp*FLH + Pp,c,o*FLHp + PL,c,o * FLH l,c,o A cooling plant operates at 60%. This is an average value and can strongly vary for a concrete plant (+/-50%) ECcooling system = Energy consumption FLH = Full load hours
12
Full load operating times
13
Calculating energy consumption with cooling load
Energy consumption compressor = Qo (Cooling load) / Coefficient of Performance * Running Time
14
Outdoor temperature variation in Austria over one year
Frequency scale temperature
15
Calculating energy consumption with load profile
16
Energy consumption with measurements
17
Example measured energy consumption hotel
2 compressors Deep cooling: compressor 16kW, R404A, -38°C (7,047 h FLO); on/off General cooling: compressor 25kW, R134a, -10°C (4,274 h FLO) (piston bypass) Direct evaporation, pumps: 4kW; fans: 16kW (1,964 FLO); on/off Electricity consumption cooling area includes: Lighting, fans, electrical deicing, heating windows, door heating, heating condensate
18
Break down electricity consumption
19
Coefficient of Performance
Q = the heat supplied to or removed from the reservoir P is the work consumped by the compressor
20
Losses
21
Cooling rooms – area of losses
22
Operating figures
23
Energy saving opportunities I
Switch off cooling chamers not in use Check if cooling temperatures can be adjusted (increased): Storage temperature recommendations Check factors which request max. temperatures Check storage procedures: Cooling chain must not be interrupted Seal pass between lorry and cooling chamber Avoid to intermediate store in warm rooms
24
Energy saving opportunities II
Check for opportunities to use waste heat Free cooling: freshly cooked products not directly in storage rooms; pre-cool with ambient air (check hygiene standards
25
Energy saving opportunities III
Reduce heat input through doors Staff training: close doors Alarm after predefined periods Check, clean and exchange door seals Automatic door closing device (€ 120) Install plastic curtains
26
Insulation Recommended U-values and insulation thickness for storage rooms for general cooling / deep cooling: 80mm and 170mm PUR Continuous termal imaging to identify losses and thermal bridges Avoid cable ducts / ventilation ducts leading through cold rooms
27
Reduce waste heat caused by illumination
LEDs (E27) can replace incandescent lamps used in deep cooling chambers Ballasts to be installed outside the cooling chamber Adjust illumination power to real needs Adjust illumination times (movement sensors, door contacts) T8 lamps have a low light emitting efficiency at low temperatures
28
Reduce waste heat caused by illumination
LEDs (E27) can replace incandescent lamps used in deep cooling chambers Ballasts to be installed outside the cooling chamber Adjust illumination power to real needs Adjust illumination times (movement sensors, door contacts) T8 lamps have a low light emitting efficiency at low temperatures Automatic deicing might cause 2-3% higher costs, manual deicing is an alternative
29
Cooling circuit The lower the temperature at the transfer of cooling energy and The higher the temperature at the transfer of heat The higher is the capacity requirement
30
Increase evaporation temperature
Step 1: Check evaporation temperatures Evaporation temperatures should be as high as possible Step 2: Evaluate design conditions Temperature differences at evaporator
31
Areas of improvement evaporator
Evaporation temperature is too low, caused by unfavourable circulation of air (stapling of goods, moisture in the room) Increase evaporation temperature during nights (3.4K) and during weekends (2.1K) Polluted heat exchanger Deformed fins (proper air circulation in heat exchanger) Iced heat exchanger Fan blads in bad condition, fan does not work Excessive heat at TV or EV
32
Improve evaporation and condensation temperature
Increase the evaporation temperature by 1 Kelvin increases the performance factor up to 3% Decrease the condensation temperature by 1 Kelvin increases the performance factor up to 3 % In case the cooling system has a constant condensation temperature of 40-45°C a variable condensation temperature should be evaluated
33
Variable condensation temperature
34
Example: Variable condensation temperature
35
Recommended condensator temperatures
36
Optimise condensation temperature
Measure the actual condensation temperature or use the temperature indicated in the saturation vapor pressure curve Preasure can be measured between compressor relay and expansion valve
37
Automatic deicing Automatic deicing might cause 2-3% higher costs, manual deicing is an alternative
38
Leaks Monitor yearly top-up quantity
Calculate indicator: yearly top up quantity/total refrigerant quantity in % Benchmark max. < 20%
39
Optimisation
40
Optimisation
41
Example quick-freeze fruits and vegetables to – 40 °C and storage the final products at – 21 °C. Operating figures per product: Before: 750 kWh/t Afterwards: 200 kWh/t. (European standard) 1.875 MWh/a MWh/a Product: t /a Energy needs: MWh Operating time: h/a 2 new chillers á 265 [(2x265)]kW = 530 kW Investment costs: € (European standard) Savings per year: 1,3 GWh Savings per year: €/a Pay-back period: 4 years
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.