1 Western Electricity Coordinating Council
MOD-033 Discussion Kent Bolton Western Electricity Coordinating Council

2 Western Electricity Coordinating Council
MOD-033 Steady-State and Dynamic System Model Validation Building of Planning Models to Analyze the Reliability of the Interconnected Transmission System Western Electricity Coordinating Council

3 Western Electricity Coordinating Council
Model Validation Focus not on Interconnection-wide phenomena but on PCs portion of the existing system. Dynamic local event – produces some measurable transient response Western Electricity Coordinating Council

4 Standard Requirements
Comparison of PCs system to Power Flow model Comparison of PCs system in Planning Dynamic Model to actual system response Western Electricity Coordinating Council

5 Western Electricity Coordinating Council
MVWG Guideline MOD-033 Guideline References NERC MWG “Procedures for Validation of Powerflow and Dynamics Cases” Western Electricity Coordinating Council

6 Western Electricity Coordinating Council
Event Selection Useful disturbances for study produce significant level of MW and MVAr variation. MVWG TF proposed to evaluate disturbances Western Electricity Coordinating Council

7 Western Electricity Coordinating Council
Steady State Data Obtain state estimator (or SCADA and PMU) data – prior to and following event Select WECC Op case that matches actual system conditions as closely as possible Modify w/gen dispatch, topology and load changes Compare parameters: Bus voltages, MW & MVAr on elements and paths, gen dispatch, PS settings Proposal: distribution of updated model to PCs for 3 weeks Western Electricity Coordinating Council

8 Western Electricity Coordinating Council
Dynamics Data Start w/associated dynamics file Adjust governor parameters within reason, add gen models to allow clean dynamic initialization No-disturbance should be flat, ringdown should be damped, etc. Western Electricity Coordinating Council

9 Western Electricity Coordinating Council
Comparison Comprehensive detailed switching sequence necessary (source?????) Run simulation and compare to actual system results. Can include V, MW & MVAr flows, generator behavior, etc. (review MWG document) Western Electricity Coordinating Council