Download presentation
Presentation is loading. Please wait.
1
Unit Ampacity for Wire Sizing
UTC Building & Industrial Systems Confidential & Proprietary Information – Not for Further Distribution
2
Common complaint: Background:
Current -20 models need a 20 amp breaker and the “old” (pre-A90) models didn’t Background: This conclusion was based on confusion related to differences in rating plate amps and unit ampacity used for wire sizing.
3
What and Why What is “Rating Plate Amps”?
What is “Unit Ampacity For Wire Sizing”? Why are they different? How do I properly size a fuse or circuit breaker? Why do I have to use a 20 amp breaker?
4
Rating Plate Amps Shows minimum electrical loads
Does not include accessory loads Does not add 1.25 factor to largest load Required for wire sizing Additional factors could be overlooked in the field Could results in undersized field wiring
5
From *9MVX specifications:
6
Unit Ampacity for Wire Sizing
Shows all electrical loads tied to the furnace Including accessory loads Adds 1.25 factor to largest load Required for wire sizing per NEC Provides correct wire size to be used Wire is then matched to the correct breaker Eliminates field calculations !!
7
From (F/G)9MVT:
8
Unit Ampacity for Wire Sizing
Based on Three items: Unit load Motor safety factor Accessories/additional loads
9
Unit Ampacity for Wire Sizing
1 – Unit load The ampacity of the circuit board, transformers, ignitor, gas valve, etc are all totaled and adjusted to a 115 Volt rating. This gives us the worst-case amp rating for the control circuits and components
10
Unit Ampacity for Wire Sizing
2 - Motors The highest rated motor worst case ampacity is multiplied by 1.25* for a safety margin. All other motor values are taken at their respective highest load amp rating. These values are all totaled for a total motor ampacity
11
Unit Ampacity for Wire Sizing
3 – Accessories Any accessories that could be hooked to unit must be considered. We can not predict what model/brands could possibly hooked up, so we use the max current rating at the connection point on the control board. These values are all totaled to come up with a total accessories amp rating.
12
*9MVX0100-20 Rating Plate Amps Unit Ampacity Trans & Circuit Board
0.34 Gas Valve 0.76 Inducer Motor 0.7 Blower FLA 12.8 Total 14.6 Can I use a 14 ga wire? NO Unit Ampacity Trans & Circuit Board 0.34 Gas Valve 0.76 Inducer Motor 0.7 Blower FLA x 1.25 16 EAC 0.12 Humidifier 1 Total 18.92 MCA of required 12 ga. wire
13
Sizing a Fuse/Circuit Breaker (OCPD)
OCPD is Over Current Protective Device Another name for a fuse or circuit breaker OCPD’s protect the circuit, not the equipment OCPD’s are sized for two types of electrical loads 100% of the non-continuous load amp draw 125% of continuous loads amp draw Continuous load is 3 hours (or more) of operation A furnace can run more than 3 hours A furnace is considered a continuous load
14
For continuous loads: OCPD rating is reduced by 80%
80% is the reciprocal of 125% 1 / 1.25 = .80 or 80% For a 15 amp breaker 15 amps x .80 = 12 amps For a 20 amp breaker 20 amps x .80 = 16 amps
15
For *9MVX0100-20 Rating plate amps = 14.6
15 amp OCPD x .80 = 12.0 amps max Furnace requires a 20 amp circuit breaker Minimum wire size for 20 amp breaker 12 ga.
16
Questions
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.