Presentation is loading. Please wait.

Presentation is loading. Please wait.

NFPA Circuits & Pathways

Similar presentations


Presentation on theme: "NFPA Circuits & Pathways"— Presentation transcript:

1 NFPA Circuits & Pathways
by Dan Horon Cadgraphics Incorporated RescueLogic.com

2 History In the 2007 Edition, the Style Tables had become outdated. They were prescriptive, and prevented new technologies. Understanding them required a fire alarm engineer. NFPA 72, 2007 Edition

3 History Even though they were less complex than previous Editions, different tables represented types of circuits. NFPA 72, 2007 Edition

4 History Even though they were less complex than previous Editions, different tables represented types of circuits. NFPA 72, 2007 Edition

5 History Throughout the years that Style Tables were in Code, the older terms Class A and Class B never went away. Everyone working in fire alarm knew Class B as being a single supervised circuit, and that Class A has an additional redundant path. NFPA 72, 2007 Edition

6 History In the 2010 Edition, we worked to replace the tables with simple, easy to understand language. Basically, fire alarm tradition: 1) requires a system to monitor itself for integrity; and 2) recommends -- but not requires -- redundant paths. NFPA 72, 2010 Edition

7 History In the 2010 Edition, Class B is described in basic terms. NFPA 72, 2010 Edition

8 History In the 2010 Edition, simple performance-based language also describes circuits that had never fit as Class A or B, even though they had been commonplace in fire alarm systems. NFPA 72, 2010 Edition

9 History Class 7, the most fault-tolerant, but also most expensive type of circuit is now called Class X. Isolator modules are added to prevent a short-circuit from affecting equipment. NFPA 72, 2010 Edition

10 History NFPA 72 Annex, 2010 Edition
The Annex of the 2010 Edition explains the pathway Classes, and gives examples. More dramatically, it explains that a single ground fault does not need to be reported if it does not affect the circuit. NFPA 72 Annex, 2010 Edition

11 Current Then, in the 2013 Edition, we added back the prescriptive requirement to report a single ground. NFPA 72, 2013 Edition

12 Current Wireless or fiber-optic Ethernet does not match up with Class B because two restrictions prevent good network design used for any other type of critically important network. NFPA 72, 2013 Edition

13 Current If wireless or fiber paths are installed without redundant pathways, they comply with Class B today. NFPA 72, 2013 Edition

14 Approved Fire Alarm Pathway
One familiar type of Class B pathway has wires with direct current, and a resistor at the last device. The end-of-line resistor offers a level of assurance that the all wires are connected to the intended device. (+) End-of-Line Resistor (-) (+) End-of-Line Resistor (-) FACP Version Dan Horon © Permission required for distribution.

15 Approved Fire Alarm Pathway
If a short occurs at any point on a Class B notification appliance pathway, the entire circuit becomes inoperable. X (+) End-of-Line Resistor (-) (+) End-of-Line Resistor (-) FACP Version Dan Horon © Permission required for distribution.

16 Approved Fire Alarm Pathway
If an open occurs at any point on a Class B initiating device circuit, every device thereafter is inoperable. This is true even when a smoke detector is removed for maintenance. (+) End-of-Line Resistor (-) (+) End-of-Line Resistor (-) FACP Version Dan Horon © Permission required for distribution.

17 Approved Fire Alarm Pathway
Class B pathways report a single ground connection because, a second ground may connection occur at some point later, and act like a short-circuit. On a Class B IDC, a short-circuit means alarm! (+) End-of-Line Resistor (-) (+) End-of-Line Resistor (-) FACP Wire touching ground Version Dan Horon © Permission required for distribution.

18 Approved Fire Alarm Pathway
Class B pathways report a single ground connection because, a second ground connection may occur at some point later, and act like a short-circuit. On a Class B IDC, a short-circuit means alarm! (+) End-of-Line Resistor (-) (+) End-of-Line Resistor (-) FACP Two wires touching ground Version Dan Horon © Permission required for distribution.

19 Approved Fire Alarm Pathway
Class B pathways report a single ground connection because, a second ground connection may occur at some point later, and act like a short-circuit. And, on a Class B IDC, a short-circuit means alarm! (+) End-of-Line Resistor (-) (+) End-of-Line Resistor (-) FACP Two wires touching ground Version Dan Horon © Permission required for distribution.

20 Approved Fire Alarm Pathway
Up to this point, we’ve seen the required methods of monitoring wires. We don’t know if any device is actually functional, but we can be reasonably certain the intended wires are connected. (+) End-of-Line Resistor (-) (+) End-of-Line Resistor (-) FACP Version Dan Horon © Permission required for distribution.

21 Approved Fire Alarm Pathway
The Class B, multi-drop signaling line circuit gives each device a numerical address, and the control unit can communicate with all attached devices on just two wires in parallel. (+) End-of-Line Resistor (-) (+) End-of-Line Resistor Multi-drop Communications 001 002 003 004 (-) FACP 101 Version Dan Horon © Permission required for distribution.

22 Approved Fire Alarm Pathway
An open on a Class B multi-drop SLC reports a trouble if the control unit cannot communicate with every device. (+) End-of-Line Resistor (-) (+) 003 004 Multi-drop Communications 001 002 (-) FACP X 101 Version Dan Horon © Permission required for distribution.

23 Approved Fire Alarm Pathway
For decades, smart systems have been sold as an improvement over conventional fire alarm systems. AHJs can see the obvious improvement that communication with each device provides. Yet, minimum Code requirements do not require operational capability of each device to be known. We only require the wires to be monitored. (+) End-of-Line Resistor (-) (+) Multi-drop Communications 001 002 003 004 (-) FACP 101 Version Dan Horon © Permission required for distribution.

24 Approved Fire Alarm Pathway
Shorting the two wires at any point stops communication with every device. Not an indication of alarm as with an IDC, a short on the Class B multi-drop SLC reports a trouble. (+) End-of-Line Resistor (-) (+) Multi-drop Communications (-) 001 002 003 004 FACP X 101 Version Dan Horon © Permission required for distribution.

25 Approved Fire Alarm Pathway
While every device is attached to the same two wires, a single ground reports a trouble. But, the single ground is not allowed to impact communications. (+) End-of-Line Resistor (-) (+) Multi-drop Communications 001 002 003 004 (-) FACP 101 Version Dan Horon © Permission required for distribution.

26 Approved Fire Alarm Pathway
A second ground on a Class B, multi-drop signaling line circuit stops all communication, as it is a short-circuit. (+) End-of-Line Resistor (-) (+) Multi-drop Communications (-) 001 002 003 004 FACP Version Dan Horon © Permission required for distribution.

27 Traditional Fire Alarm
Comparison 1 Every single connection on an Ethernet network is required by IEEE 802 (an ANSI standard) to be galvanically isolated. Traditional Fire Alarm Cat 5/6 Ethernet Report a single ground A single ground must report even if it has no impact on communication. Wireless or fiber optic paths are excepted because they cannot be grounded, but IEEE 802 isolation means nothing. A ground has no impact on IEEE 802 equipment. Every connection is galvanically isolated, which prevents propagation of transients, shorts, and grounds. (IEEE 802 is a verifiable ANSI Standard that can be referenced in Code.)

28 Traditional Fire Alarm
Comparison 2 Class A and X paths have exactly two paths that will work if the other fails. A mesh network usually has more than two paths, not knowing exactly where a failure might occur. Traditional Fire Alarm Cat 5/6 Ethernet Redundant paths Redundant paths do not exist unless they are separately monitored for integrity. We must know the status of opens, grounds, and shorts on every connected wire. A mesh network design remains operational even after segments fail. Critical paths have redundancy, and failures of essential equipment report to responsible personnel.

29 Traditional Fire Alarm
Comparison 3 Buildings are increasingly dependent on the network infrastructure. Traditional Fire Alarm Cat 5/6 Ethernet Building networks No fire alarm equipment should ever be connected to a building network infrastructure. Building networks are not as reliable as traditional fire alarm systems.  Building networks are a new infrastructure. Modern building systems have standardized on LANs, WANs, and VLANs to interconnect intelligent equipment. A pair of parallel wires connected to multiple addresses is inherently unreliable.

30 Traditional Fire Alarm
Comparison 4 Minimum Code requirements do not require the operational capability of endpoints to be supervised. Traditional Fire Alarm Cat 5/6 Ethernet Device / Endpoint Supervision Supervising the wiring is enough assurance that a system will operate as intended. SLCs are nice, with each device being addressed, but to require endpoint operation is beyond the scope of the Code. All endpoints are intelligent, and report improper operation as well as signal path problems. Loss of communication is critical.

31 Traditional Fire Alarm
Wiring Comparison Every single connection on an Ethernet network is required by IEEE 802 (an ANSI standard) to be galvanically isolated. Wiring Traditional Fire Alarm Cat 5/6 Ethernet Terminations Wire nuts, junction boxes, stripped wires, screw terminals Encased cables, RJ45 ends Length Wire length is only limited when voltage drop and capacitance prove communication failure. Segmented every 300 feet or less. Packets are refreshed by forwarding equipment. Paralleled The same wires touch every device in parallel. Like an old party-line telephone system, all devices talk on the same wires. Multi-layer design. Each device is an individually addressable endpoint. Devices are not physically wired in parallel with each other. Version Dan Horon © Permission required for distribution.

32 Proposed Fire Alarm Pathway
Network equipment can be thought of in two basic categories: Data Endpoints and Data Forwarding Equipment. Data Endpoint Data Forwarding Data Endpoints Version Dan Horon © Permission required for distribution.

33 Category 5 Ethernet Cable
In between Data Endpoints and Data Forwarding Equipment, a standardized cable is used. ‘Cat 5’ is an example. 8 7 6 5 4 3 2 1 Transmit Data Receive Data 8 7 6 5 4 3 2 1 Data Forwarding Network hub or switch that forwards data to endpoints Transmit Data + Data Endpoint generates or acts on alarm events Transmit Data - Receive Data + NC NC Receive Data - NC IEEE requires galvanic isolation on each pair of wires NC IEEE requires galvanic isolation on each pair of wires Version Dan Horon © Permission required for distribution.

34 Category 5 Ethernet Cable
Each Cat 5 cable is galvanically isolated at each end, inside the equipment. The isolation helps prevents transient grounds and shorts on one cable from affecting other components. IEEE requires galvanic isolation on each pair of wires 8 7 6 5 4 3 2 1 Transmit Data Receive Data IEEE requires galvanic isolation on each pair of wires Data Forwarding Network hub or switch that forwards data to endpoints Transmit Data + 8 7 6 5 4 3 2 1 Data Endpoint generates or acts on alarm events Transmit Data - Receive Data + NC NC Receive Data - NC NC Cat 5 Cable Four wires are used for data transmission Data Endpoint generates or acts on alarm events Data Forwarding Network hub or switch that forwards data to endpoints Version Dan Horon © Permission required for distribution.

35 Category 5 Ethernet Cable
If Transmit Data (+) and (–) or Receive Data (+) and (-) are shorted together, communication stops. In fire alarm systems, a fault condition must be reported within 200 seconds. 8 7 6 5 4 3 2 1 Transmit Data Receive Data X 8 7 6 5 4 3 2 1 Transmit Data + Transmit Data - Receive Data + NC NC Receive Data - NC IEEE requires galvanic isolation on each pair of wires NC IEEE requires galvanic isolation on each pair of wires Data Endpoint generates or acts on alarm events Data Forwarding Network hub or switch that forwards data to endpoints Version Dan Horon © Permission required for distribution.

36 Category 5 Ethernet Cable
A ground connection on any one signal wire does not block communication. IEEE requires isolation at each end of every Cat 5 cable. Every data packet is checked for errors and re-transmitted until verified. 8 7 6 5 4 3 2 1 Transmit Data Receive Data 8 7 6 5 4 3 2 1 Transmit Data + Transmit Data - Receive Data + NC NC Receive Data - NC IEEE requires galvanic isolation on each pair of wires NC IEEE requires galvanic isolation on each pair of wires Data Endpoint generates or acts on alarm events Data Forwarding Network hub or switch that forwards data to endpoints Version Dan Horon © Permission required for distribution.

37 Category 5 Ethernet Cable
A second ground connection, on the other wire of a matched pair, will impair communication if it causes a short. A fault condition must be reported within 200 seconds. 8 7 6 5 4 3 2 1 Transmit Data Receive Data 8 7 6 5 4 3 2 1 Transmit Data + Transmit Data - Receive Data + NC NC Receive Data - NC IEEE requires galvanic isolation on each pair of wires NC IEEE requires galvanic isolation on each pair of wires Data Endpoint generates or acts on alarm events Data Forwarding Network hub or switch that forwards data to endpoints Version Dan Horon © Permission required for distribution.

38 Category 5 Ethernet Cable
Again, each Cat 5 cable is galvanically isolated. Grounds and shorts have no direct path of electrical connection to other equipment or devices. 8 7 6 5 4 3 2 1 Transmit Data Receive Data IEEE requires galvanic isolation on each pair of wires 8 7 6 5 4 3 2 1 IEEE requires galvanic isolation on each pair of wires Transmit Data + Transmit Data - Receive Data + Receive Data - NC Data Endpoint generates or acts on alarm events Data Forwarding Network hub or switch that forwards data to endpoints Version Dan Horon © Permission required for distribution.

39 Category 5 Ethernet Cable
Proposed Fire Alarm Network Category 5 Ethernet Cable Again, each Cat 5 cable is galvanically isolated. Grounds and shorts have no direct path of electrical connection to other equipment or devices. 8 7 6 5 4 3 2 1 Transmit Data Receive Data IEEE requires galvanic isolation on each pair of wires 8 7 6 5 4 3 2 1 IEEE requires galvanic isolation on each pair of wires Transmit Data + Transmit Data - Receive Data + Receive Data - NC Data Endpoints Data Endpoint generates or acts on alarm events Data Forwarding Network hub or switch that forwards data to endpoints Version Dan Horon © Permission required for distribution.

40 Proposed Fire Alarm Network
Here you can see a potential vulnerability. If a single path were to become impaired, multiple data endpoints would not communicate with essential equipment. Good network design prevents a fault on any single cable from making more than one device inoperable. Data Endpoint Data Forwarding Data Endpoints Version Dan Horon © Permission required for distribution.

41 Proposed Fire Alarm Network
A proposed Class N path would require alternate communication pathways whenever more than one device would be impacted by a fault. Data Endpoint Data Forwarding Equipment Data Endpoints Version Dan Horon © Permission required for distribution.

42 Class N Ethernet cables do not report grounds. Therefore, to allow Ethernet network wiring in the Code: Any segment of a path that affects more than one device must be the equivalent of Class X. Equivalent of Class B paths may be used when only one device is dependent on the path.


Download ppt "NFPA Circuits & Pathways"

Similar presentations


Ads by Google