1 Building Energy Code Requirements
Presented by: The leader in metal building insulation

2 Florida – ASHRAE

3 ASHRAE Commercial Code: State developed code, Chapter 13 of the Florida Building Code, meets or exceeds ASHRAE , mandatory statewide; can use Energy Gauge FLACOM to show compliance.

4 ASHRAE 90.1 2004 Florida Heated (condition buildings)
Roofs and Ceilings: U value of .065 Walls: U value of .113 In “R” value terms it means the following: Roofs and Ceilings: In place R-15.3 Walls: In place R-9

5 Insulation compression and reduction of R-Values
A loss in R-Value occurs when the insulation is compressed between the roof and walls structurals and the exterior metal skin.

6 Metal Building Roof Requirements Conditioned Building
In order to achieve a U-Value of .065 (in place R-15.3) in the roof the following is required 6” of R-19 metal building fiberglass insulation Thermal Blocks – are required This will achieve an in place R-value of R-15.4

7 Metal Building Wall Requirements Conditioned Building
In order to achieve a U-Value of .113 (in place R-8.9) in the walls the following is required 4” of R-13 metal building fiberglass insulation Thermal Blocks – not required This assembly will achieve an in-place R-Value of R-8.9

8 ASHRAE 90.1 2004 Florida Semi-Heated
Roofs and Ceilings: U value of .167 Walls: U value of .184 In “R” value terms it means the following: Roofs and Ceilings: In place R-6 Walls: In place R-5.5

9 Metal Building Roof Requirements Semi-Heated Building
In order to achieve a U-Value of .184 (in place R-6) in the roof the following is required 3” Thick of R-10 metal building fiberglass insulation Thermal Blocks – are not required This will achieve an in place R-value of R-6.5

10 Metal Building Wall Requirements Semi-Heated Building
In order to achieve a U-Value of .184 (in place R-5.5) in the walls the following is required 3” of R-10 metal building fiberglass insulation Thermal Blocks – not required This assembly will achieve an in-place R-Value of R-7

11 Summary If you have any questions you can consult your local building code official.