University of Calabria, Italy
Dept. of of Mechanical, Energy and Management A dual active bridge dc-dc converter for application in a smart user network G. Barone, G. Brusco, A. Burgio, M. Motta, D. Menniti, A. Pinnarelli, N. Sorrentino 1
2
INTRODUCING TO THE SUN The smart DC powered user Local network network
A SUN essentially is a private network connected to the LV network (the grid) by means of a bidirectional AC-DC power electronic interface (PEI). The local network of the SUN is DC-powered; the distributed energy resources (DERs), the energy storage systems (ESSs) and loads are all connected in parallel to the DC bus by means of appropriate power converters. The SUN is particularly congenial to the integration of various kinds of micro-generation and small storage systems; as an example, small wind turbines, PV panels, Stirling engines, biofuel generators and fuel cells cooperate with batteries in order to ensure uninterruptable power to critical AC loads (UP loads). 2
3
INTRODUCING TO THE SUN The smart DC powered user Local network network
When the SUN is grid connected, the grid participates to satisfy the local demand of electricity; in such a case, the PEI ensures for the power balancing in the SUN, absorbing and supplying electricity to the grid. When the main switch S is opened, the SUN operates in island mode and depends solely by the local DERs and local ESSs. What’s the problem ? Fixing the voltage of the DC bus (VDC) at a constant reference value (VDCref) is a key factor for the proper operation of the SUN; as a consequence, one of the power converters belonging to the SUN must be dedicated to this scope. This power converter is named master converter. 3
4
THE MASTER CONVERTER The PEI is the preferable candidate to operate as master converter when the SUN is grid connected because it regulates a bidirectional power flow and, nearly ever, its rated power is higher than any other converter present in the SUN. Evidently, the PEI cannot operate as master converter when the SUN operates in island mode. In such a case, the DC-DC converter used for the battery ESS is suitable to functioning as master converter. The paper presents a dual active bridge (DAB) converter to charge/discharge the batteries which can operated as master converter when the SUN operates in islanded mode. 4
5
BASIC PRINCIPLES OF A DAB
Direct voltage High frequency square voltage Direct voltage A DAB is an isolated bidirectional DC/DC converter composed of two full-bridge DC/AC converters and an isolation high frequency (HF) transformer. Controlling the direction and magnitude of the current of the inductor L is equivalent to controlling the power flow between the two sides of the DAB converter. At this scope, the full-bridges H1 and H2 generate the two high frequency square-wave voltages, vH1 and vH2, at the terminals of the HF transformer and regulate the direction and magnitude of the current of the inductor L by phase-shifting vH1 and vH2. 5
6
BASIC PRINCIPLES OF A DAB
The transmission power is given by: By defining the phase-shift ratio as D=(ϕ/π) and using the single-phase-shift control, it is possible to control the power P by regulating only the value of D. In the single-phase-shift control, the diagonal switching pairs are turned on simultaneously with a duty cycle of 50% (ignoring the small dead time) and with 180 degrees phase shift between two legs so to provide a nearly square wave voltage across transformer terminals. 6
7
FEEDBACK CONTROL SCHEME
When the SUN is grid connected, the PEI is the master converter. The DAB is as slave converter and it ensures a desired power Pref to the DC bus, i.e. 1000W. In the feedback control scheme: Pref is divided for the measured DC bus voltage VDC so to return a current reference. The difference with respect the actual output current I returns the error eI which is the input signal for a proportional-integral (PI )controller). The PI controller output is D that is the phase-shift ratio for controlling the power transmission; such a value is multiplied by π so to calculate the ϕ angle for the operation of the full bridge H1. 7
8
FEEDBACK CONTROL SCHEME
When the SUN operates in islanded mode, the DAB may operate as master converter so it ensure a stable DC bus voltage; to this aim, power flows from batteries to the DC bus and vice versa. In the feedback control scheme the DC bus voltage VDC is measured and the difference with respect the reference value VDCref is calculated so to return the error ev; such an errore is the input signal for a proportional-integral (PI) controller. The PI controller output is D that is the phase-shift ratio for controlling the power transmission; such a value is multiplied by π so to calculate the ϕ angle for the operation of the full bridge H1. 8
9
NUMERICAL EXPERIMENTS
THE TEST SYSTEM The test system: The grid is a 3-phase low voltage electric power system, that is the national grid, operating at the fundamental fequancy of 50Hz The line-to-neutral voltage of the GRID is VGRID=230V A capacitor is placed between the positive and negative terminals the the DC bus The PEI is a 1-phase bidirectional AC-DC converter functioning as power electronic interface so to connect the SUN to the grid The two terminals of the PEI are connected to the line and the neutral of the GRID respectively. Local distributed generators are neglected. A 1-phase load inverter supply the local loads (R=100) 9
10
NUMERICAL EXPERIMENTS
THE TEST SYSTEM - The dc-dc dual active bridge (DAB) connects a battery energy storage system to the DC bus. - The batteries provide 48V DC power. The inductance of the inductor placed between the two full bridges H1 and H2 is 4.5uH; - The high frequency transformer ratio is n=0.1 - The switching frequency of both the full bridges H1 and H2 is 15kHz 10
11
NUMERICAL EXPERIMENTS
THE DINAMIC RESPONSE The dynamic response of the test system under transient condition due to a step change in power balancing has been studied. Simplorer® has been used for schematics and simulations. Description of the step change in power balancing: At the beginning, the SUN is connected to the GRID, the PEI absorbs power from the GRID so to provides the most part of the load demand, the DAB provides the rest. The PEI is turned off suddenly, the DAB fulfills the entire load demand and compensates rapidly for DC BUS voltage variation. 11
12
THE FEEDBACK CONTROLLER
NUMERICAL EXPERIMENTS THE FEEDBACK CONTROLLER In the feedback controller, the measurement of the DAB output voltage and current are filtered by means of a transfer function G(s) operating as low-pass filter. The upper part of the controller determines the angle ϕ useful for the H1 bridge operation when the SUN is grid-connected and the PEI is the master converter; vice versa, the lower part of the controller determines the angle ϕ when the PEI is turned off and the DAB is the master converter. 12
13
NUMERICAL EXPERIMENTS
THE DC BUS VOLTAGE At the beginning, the DAB converter provides the desired power Pref of about 450W. The PEI provides about 100W that is a part of load demand and system losses. The PEI maintains the DC bus voltage at 450V, such a voltage is stable at the reference value; the small oscillation of VDC is due to the current drawn by the single phase load inverter which supply the loads. At t=30ms the PEI is suddenly turned off so causing a variation in power balancing which would cause the fast collapse of the DC bus voltage. The DAB converter is operated as master converter; the value of VDC is quite constant with a very small oscillation. the DC bus voltage 13
14
THE ERROR OF THE DC BUS VOLTAGE
NUMERICAL EXPERIMENTS THE ERROR OF THE DC BUS VOLTAGE Thanks to the DAB action, the value of VDC is quite constant with a very small oscillation between V and V. The DAB converter is able to maintain the error between -0.1 V and 0.15 V (that is the 0.03% of Vref), 14
15
THE ANGLE FOR THE DAB OPERATION
NUMERICAL EXPERIMENTS THE ANGLE FOR THE DAB OPERATION Such a fast response of the DAB converter is evidently due to the fast control of the angle ϕ for the switching of the full bridge H1. 15
16
THE DAB AND BATTERIES CURRENT
NUMERICAL EXPERIMENTS THE DAB AND BATTERIES CURRENT After t=30ms, the DAB converter is the solely power generation unit so the output current coincides with the current drawn by the load inverter; as a consequence, both the DAB and the batteries output currents oscillate at a frequency twice than that of loads (i.e. 100Hz), 16
17
CONCLUSION AND FUTURE AIM
The paper presented the application of a dual active bridge (DAB) converter in a DC-powered microgrid named smart user network (SUN). The SUN was operated in islanded mode abruptly so causing a heavy step change in power balancing condition; in such a case, the DAB provided a high level of reliability and resilience to disturbances, compensating for the DC bus voltage variation and demonstrating a good dynamic response. The realization of a laboratory prototype of a DAB is in progress; Heat sink IRAM136 1063B To DC bus To batt Heat sink and H1 L PWM Tr 2€ V1=24Volt V2=48 Volt P= 50-70Watt 17