Existing Conditions Survey/Field Verification For Article 28 Space

Similar presentations


Presentation on theme: "Existing Conditions Survey/Field Verification For Article 28 Space"— Presentation transcript:

1 Existing Conditions Survey/Field Verification For Article 28 Space
Best Practices May 2016

2 Why? DOH Rules and Regulations: FGI guidelines Existing Conditions Existing Conditions and operations shall be documented prior to initiation of renovation and/or new construction….. Best Practices. Goals: Create an accurate basis for developing scope, cost, schedule and design, Identify non-compliant conditions Minimize unknown project conditions Minimize change orders

3 What need to be surveyed/documented?
FGI Existing Conditions Existing conditions…shall include mechanical/electrical…plumbing, fire suppression; detection; alarm.. Existing defects and deficiencies: Compromised/missing barrier walls; Missing dampers; Missing fire stopping.. Program elements per FGI guidelines: Adequate storage space; utility rooms… For projects that require pre-occupancy inspection, all of the above in the entire fire compartment including the egress path to public street. What resources are available? Existing Life Safety plans Statement of Conditions As-built drawings

4 Samples of Deficiencies

5 Sample of SOC Drawing

6 Sample of SOC Report Deficiencies Report (8/24/2015) Building Floor
Building Floor Room No. ID SOC Number Location Standard Deficiency LMB 02 EQ298A R20-LMB1010 EC 2 HR RATED WALL / FLOOR DEFICIENT R20-LMB1011 R20-LMB1012 LMA LMA RC11-LM1099 LS EP10 PREP BUILDING AND FIRE PROTECTION FEATURES ARE DESIGNED AND MAINTAINED TO MINIMIZE THE EFFECTS OF FIRE, SMOKE, AND HEAT. ADD`L LIFE SAFETY CODE "GENERAL REQUIREMENTS" REQUIREMENT(S) IS NOT MET. LMC LMC RC11-LM1142 None found CLEAN MEDICAL GAS RELATED ISSUE 289 RC11-LMA1023 SOILED LINEN OR TRASH RECEPTACLE(S) > 32-GALS. (INCL. RECYCLING CONTAINERS) IS LOCATED IN RM. NOT PROTECTED AS A HAZARDOUS AREA. RC11-LMA1026 210B RC11-LMA1031 LS EP10 WKSTA AMBULATORY: BUILDING AND FIRE PROTECTION FEATURES ARE DESIGNED AND MAINTAINED TO MINIMIZE THE EFFECTS OF FIRE, SMOKE, AND HEAT. LMD 204 RC11-LMD1033-D LS EP19 OR THE HOSPITAL MAINTAINS THE INTEGRITY OF THE MEANS OF EGRESS. TRAVEL DISTANCE 207 C100212 DRAWING DOES NOT MATCH FIELD LMD C100456 5 STOR 02-C200Z RC2-LMA1000 CORR Sample of SOC Report

7 What to do with the findings?
Projects that are moving forward: Record findings in Feasibility Study Documents. Report deficiencies to Facilities Operation and Regulatory Compliance Include corrective measures for defects and deficiencies in project scope. Projects that are not moving forward: Record findings in Feasibility Study Documents Report deficiencies to Facilities Operation and Regulatory Compliance (for follow up)

8 How to conduct Field Survey?
Follow all established NYP Procedures. Coordinate all activates with clients; current occupants of the space; Security; EVS and Facilities Operation For intrusive work - PCRA; Infection Control measures; above ceiling permits, IC Cube/Booth etc. FDC will provide support of a small call-in contractor if needed. Question?


Download ppt "Existing Conditions Survey/Field Verification For Article 28 Space"