Presentation is loading. Please wait.

Presentation is loading. Please wait.

SOP of the Third-party Devices Configuration

Similar presentations


Presentation on theme: "SOP of the Third-party Devices Configuration"— Presentation transcript:

1 SOP of the Third-party Devices Configuration
for IOI Project January 2014

2 Third-party Devices Sunten TTC-313, Modbus Protocol
Protection Relay: Argus 7SR12, Modbus Protocol Power Meter: SIMEAS P50, Modbus Protocol Reference: 7SR11 and 7SR12 - Argus Complete Technical Manual.pdf SIMEAS P_Complete_Manual_250204_us.pdf SIMEAS_Pxxx_Com_Modbus_A4_EN.pdf TTC Seriors Transformer Temperature controller Communication Software.pdf

3 Drivers Protocol Driver: AnyPolling (DrvAnyPolling.dat) Device Driver:
TTC-313 (TTC-313.dat, TTC-313.cfg) Argus 7SR12 (Argus 7SR12.dat, Argus 7SR12.cfg) SIMEAS P50 (SIMEAS P50.dat, SIMEAS P50.cfg)

4 Step 1: Install the drivers
Run DeviceInstall.exe from D:\CET\iEMS\Common folder. Select Install and click Next. Select English as language and click Next:

5 Step 1: Install the drivers
Click Explore and select the folder where the drivers are located and click Next. The driver version is shown. Click Next to continue.

6 Step 1: Install the drivers
Click Install. Check devices and click Next.

7 Step 1: Install the drivers
When the progress is finished, click Next. The drivers are installed successfully. Click Complete. Then quit the program.

8 Step 2: Configure TTC-313 Start PecConfig. Add a site:
expand Station SetupStation, right-click on Communication Setup and select New. The Site Properties window appears. Enter Site Name, Driver Type is Polling Protocol Master Site Driver, then click OK.

9 Step 2: Configure TTC-313 Add a device: right-click on the site and select New from the pop-up menus. The Device Properties window appears. Enter Device Name, Device Type is TTC-313, enter Comm ID of the device, then click OK.

10 Step 2: Configure TTC-313 Right-click on the device and select Properties… from the pop-up menus.

11 Step 2: Configure TTC-313 Click INF File>> and then the Edit Text File window appears. Open the TTC-313.cfg file, copy all content and paste it to the end of the INF file. Then click OK.

12 Step 2: Configure TTC-313 Click OK to return.
The configuration of TTC-313 is done. Click Save to save changes to database.

13 Step 3: Configure SIMEAS P50
Add a site: enter Site Name, Driver Type is Polling Protocol Master Site Driver, then click OK.

14 Step 3: Configure SIMEAS P50
Add a device: enter Device Name, Device Type is SIMEAS P50, enter Comm ID of the device, Data Map is SIMEAS P50, then click OK.

15 Step 3: Configure SIMEAS P50
Edit INF File: right-click on the device and select Properties… from the pop-up menus. Open the SIMEAS P50.cfg file, copy all content and paste it to the end of the INF file. Then click OK.

16 Step 3: Configure SIMEAS P50
Click Save to save changes to database.

17 Step 4: Configure Argus 7SR12
Add a site: enter Site Name, Driver Type is Polling Protocol Master Site Driver, then click OK.

18 Step 4: Configure Argus 7SR12
Add a device: enter Device Name, Device Type is Argus 7SR12, enter Comm ID of the device, Data Map is Argus 7SR12, then click OK.

19 Step 4: Configure Argus 7SR12
Edit INF File: right-click on the device and select Properties… from the pop-up menus. Open the Argus 7SR12.cfg file, copy all content and paste it to the end of the INF file. Then click OK.

20 Step 4: Configure Argus 7SR12
Click Save to save changes to database.

21 Thank you !!!


Download ppt "SOP of the Third-party Devices Configuration"

Similar presentations


Ads by Google