Download presentation
Presentation is loading. Please wait.
1
POWER FACTOR CORRECTION
WISEMAN NENE EIT – ELECTRICAL ESTON SUGAR MILL
2
POWER FACTOR CORRECTION
AS A MEANS OF COST SAVINGS
3
CONTENT INTRODUCTION OBJECTIVES NATURE OF ELECTRICAL POWER/LOAD
POWER FACTOR THEORY
4
ADVANTAGES OF IMPROVED POWER FACTOR
DISADVANTAGES OF LOW POWER FACTOR METHODS OF IMPROVING POWER FACTOR OVERVIEW OF THE SYSTEM SYSTEM BREAKDOWN
5
POWER AND COSTS SAVINGS
PROJECT COSTS COSTS RECOVERY PERIOD SAFETY AND MAINTENANCE OF THE SYSTEM CONCLUSION
6
INTRODUCTION COSTS SAVINGS IS ONE OF THE MEASURE DRIVERS IN INDUSTRY FOR BUSINESS SUSTAINABILITY POWER FACTOR CORRECTION IS ONE OF THE MEANS THAT CAN BE USED TO REDUCE COSTS
7
NATURE OF ELECTRICAL LOAD
Resistive - I and V peaks are simultaneous The angle between the two is zero Inductive - I lags V The angle between the two is negative Capacitive – I leads V The angle between the two is positive
8
OBJECTIVES TO INVESTIGATE MEANS OF COST REDUCTION FROM THE ELECTRICAL PERSPECTIVE – (POWER FACTOR CORRECTION)
9
POWER FACTOR THEORY PF = ACTIVE POWER / APPARENT POWER = P / S
= kW / kVA ACTIVE POWER (P) = kW APPARENT POWER (S) = kVA
10
POWER TRIANGLE
11
SYSTEM BEFORE PFC PF = 0.68 Lagging
12
DESIRED MINIMUM SYSTEM TRIANGLE
PF = 0.8 Lagging
13
NEW SYSTEM POWER TRIANGLE
PF = 0.92 Lagging
14
ADVANTAGES OF IMPROVED PF
REDUCED APPARENT POWER PRODUCED IMPROVED PLANT EFFICIENCY ADDITIONAL LOADS CAN BE ADDED TO THE SYSTEM REDUCED OVERLOADING OF CABLES, TRANSFORMERS, SWITCHGEAR, ETC. IMPROVED NETWORK VOLTAGE IMPROVED STARTING TORQUE OF MOTORS
15
DISADVANTAGES OF LOW PF
INCREASES ELECTRICITY COSTS CAUSES OVERLOADING OF GENERATORS, TRANSFORMERS AND DISTRIBUTION SYSTEM GREATER VOLTAGE DROPS AND POWER LOSSES LOW EFFICIENCY AND UNNECESSARY WEAR AND TEAR TO INDUSTRIAL ELECTRICAL EQUIPMENT REDUCES LOAD HANDLING OF THE PLANTS’ ELECTRICAL SYSTEM
16
METHODS OF IMPROVING POWER FACTOR
SYNCHRONOUS MOTORS STATIC VAR COMPENSATORS STATIC CAPACITORS
17
METHODS OF IMPROVING POWER FACTOR
SYNCHRONOUS MOTORS Has long service life Can withstand higher short circuit currents High maintenance and installation costs STATIC VAR COMPENSATORS Fast response system System is very expensive
18
STATIC CAPACITORS Simple and easy to install Cannot be repaired
19
CONNECTION TO THE NETWORK
Basic connection diagram for static capacitors
20
SYSTEM CONFIGURATION 4 x 48kVAr + 3 x 50 kVAr = 342 kVAr
FRONT – END SECTION 4 x 48kVAr + 3 x 50 kVAr = 342 kVAr BACK – END SECTION = 6 x 62.5 kVAr = 375 kVAr
21
SYSTEM OPERATION Manual Mode
Uses a selector switch to select a stage Automatic – using Epcos BR6000 PFC Controller Uses a selector switch to automatically select a stage
22
POWER AND COSTS SAVINGS
Electrical saving in terms of the power consumed P = kW P = kW @ 0.68 PF , S = 631 kVA And at: @ 0.92 PF, S = kVA STOTAL = SOLD – SNEW = kVA I = S/√3 x 525 = A P = √3 V I Cos θ = kW
23
RAND VALUE SAVING (ACTUAL)
Assuming 24 hours/day for /kWh and saving kWh, National grid Power Energy Charge Saving = x 24 x 30 x = R 43,821.89/month
24
POWER SAVINGS (BACK-END)
P = kW @ 0.61 PF, SOLD = 1.48 MVA @ 0.8 PF, SNEW = 1.13 MVA STOTAL= SOLD – SNEW = 350 kVA I = S/√3 x 525 = A P = √3 V I Cos θ = 280 kW
25
SAVINGS ( RAND-VALUE, BACK-END)
Assuming 24 hours/day for /kWh and saving 280 kW hourly: Energy Charge Saving = 280 x 24 x 30 x = R 81,023.04/month
26
OVERALL POWER / COST SAVINGS
For 2010 season Eskom used during crushing=331.3 hrs, [ to ] Electrical Power saved; P FRONT-END = kW P BACK-END = 280 kW Total Power Saved (2010 season) = kW kW = kW = kW x 331.3hrs = MWh = kWh x R /kWh = R 57,446.00
27
BUDGET & COSTS RECOVERY PERIOD
Approximately R Source: Electrical Department Budget Recoverable: Within 1 Month on National Grid
28
FINAL SYSTEM PICTURES The following pictures shows the installation locations and the results obtained from the front-end section
29
CONTROLLER Controller - Epcos BR6000
30
CONTROL Auto and Manual Control
31
CAPACITOR BANKS
32
CONTROL PANELS
33
MAIN PANELS
34
DISPLAYS With all banks OFF
35
WITH 6 BANKS ON .
36
PF ALL BANKS ON PF = 0.92 Lagging
37
BACK-END SECTION
38
SAFETY No unauthorized person should switch the system ON/OFF.
Before opening the capacitor banks panels, make sure the main isolator is off and wait for at least 5minutes for the capacitors to discharge
39
CONCLUSION As seen on the pictures in the previous slides, the new system was successful. The power factor was corrected from 0.68 lagging to 0.92 lagging in the front-end and from 0.61 to 0.8 lagging in the back-end section
40
CONCLUSION cont. The costs and power savings were significant at MWh during the 4 months period recorded during the 2010 season
41
ACKNOWLEDGEMENTS ESTON ENGINEERING TEAM
42
THANK YOU!!! ???
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.