Download presentation
Presentation is loading. Please wait.
1
Mark Hydeman, PE of Taylor Engineering
Title and 2008 Nonresidential Mechanical and Acceptance Test Requirements Mark Hydeman, PE of Taylor Engineering The Non-Residential HVAC Lead for the 2001, 2005 and 2008 Standards November 2, 2006
2
Acknowledgements Acceptance Tests
CEC Codes and Standards Lead: Bill Pennington CEC Acceptance Test Lead: Tav Commins Lead Acceptance Consultant: Jeff Johnson, New Buildings Institute Content Contributors 2005: PECI: Larry Luskay (tests) HMG: Jon McHugh (consultant) Farnsworth Group: Chad Dorgan (forms) Taylor Engineering: Mark Hydeman (gadfly) Content Contributors 2008: PECI: Larry Luskay, Kristin Heinemeier & Kirstin Pinit HMG: Jon McHugh Taylor Engineering: Mark Hydeman CCC Meeting Title 24 Acceptance Tests
3
Title 24 Acceptance Tests
Agenda Review of Title 24 Structure Review of Acceptance Tests Detailed Example of an Acceptance Test CCC role for 2008 Discussion CCC Meeting Title 24 Acceptance Tests
4
Title 24 Acceptance Tests
Resources – 2005 Standard The Standard, Title 24 The Non-Residential ACM Manual Appendix NG (duct leakage) Appendix NJ (acceptance tests) The Non-Residential Compliance Manual Examples References Compliance Forms CCC Meeting Title 24 Acceptance Tests
5
Title 24 Acceptance Tests
Resources – 2008 Standard Tav Commins Ram Verma Energy Efficiency Hotline Phone: or Phone: (toll free in Calif.) CCC Meeting Title 24 Acceptance Tests
6
Title 24 Acceptance Tests
Iconographic Key Mandatory Measure Prescriptive Measure Acceptance Test CCC Meeting Title 24 Acceptance Tests
7
Overview of Title 24
8
Title 24 Acceptance Tests
Standards Structure Design Construction CCC Meeting Title 24 Acceptance Tests
9
Title 24 Acceptance Tests
Mandatory Measures Must be done in all projects (no trade off) Things that can’t be modeled or shouldn’t be traded off Examples Equipment efficiencies Ventilation requirements Temperature controls Zoning CCC Meeting Title 24 Acceptance Tests
10
Prescriptive Measures
Can be traded off through the performance method of compliance Examples Economizers Variable air flow Limitations on electric resistance heat and air cooled chillers CCC Meeting Title 24 Acceptance Tests
11
Title 24 Acceptance Tests
Performance Approach Computer simulation of a project Two models made: Budget model meets the mandatory and prescriptive requirements Design model represents your project Project complies if TDV of design is less than or equal to TDV of budget model Can trade off envelope, HVAC and lighting energy CCC Meeting Title 24 Acceptance Tests
12
Acceptance Testing Overview
13
Title 24 Acceptance Tests
2005 Defined in various mandatory Standard’s sections Detailed in the NR ACM appendix NJ 2008 Defined in mandatory Standards section 125 Detailed in the NR Standard’s Appendix NRA7 CCC Meeting Title 24 Acceptance Tests
14
2005 HVAC Acceptance Requirements
ACM Section and Test Standard Section NJ 3.1 Variable Air Volume Systems Outdoor Air Acceptance 121(f) NJ 3.2 Constant Volume Systems Outdoor Air Acceptance NJ 4 Constant Volume Packaged HVAC Systems Acceptance 122(h) NJ 5 Air Distribution Acceptance 125(a) NJ 7 (Air-Side) Economizer Acceptance 125(b) NJ 8 Demand Control Ventilation Acceptance 121(c)5 NJ 9 Supply Fan Variable Flow Controls Acceptance 125(c) NJ 10.1 Variable (Hydronic) Flow Controls Acceptance 125(d) NJ 10.2 Automatic Isolation Controls Acceptance NJ 10.3 Supply Water Temperature Reset Controls Acceptance NJ 10.4 Water-loop Heat Pump Controls Acceptance NJ 10.5 (Pump) Variable Frequency Drive Controls Acceptance CCC Meeting Title 24 Acceptance Tests
15
2005 Lighting Acceptance Requirements
ACM Section and Test Standard Section NJ 6.1 Automatic Daylighting Controls Acceptance 131(f) NJ 6.2 Occupancy Sensor Acceptance NJ 6.3 Manual Daylighting Controls Acceptance NJ 6.4 Automatic Time Switch Control Acceptance CCC Meeting Title 24 Acceptance Tests
16
Title 24 Acceptance Tests
Compliance Process Design is checked and a signed certificate of compliance is submitted for the building permit Tests are performed and a signed certificate of acceptance is submitted for the certificate of occupancy CCC Meeting Title 24 Acceptance Tests
17
When Acceptance Testing Occurs?
Specified during the design phase Implemented during construction After start-up (except for duct leakage) Before occupancy CCC Meeting Title 24 Acceptance Tests
18
Who Does Acceptance Testing?
Can be done by Engineer, or Contractor, or 3rd Party Different parties can do different tests, but… Someone has to sign the final certificate of acceptance CCC Meeting Title 24 Acceptance Tests
19
How to Specify the Acceptance Tests
Where do they go in the specifications? Under TAB Section? Under Controls? Under Commissioning? Throughout several sections? Wherever you put it you must be clear about: Who does the work (roles and responsibilities) What work they must do When it must be done Submittal requirements Who signs the forms CCC Meeting Title 24 Acceptance Tests
20
Title 24 Acceptance Tests
Acceptance forms end in “–A” CCC Meeting Title 24 Acceptance Tests
21
Title 24 Acceptance Tests
AHU-1 MECH-2-A TAB AHU-2 MECH-2-A TAB CCC Meeting Title 24 Acceptance Tests
22
Title 24 Acceptance Tests
Deleted in 2008 CCC Meeting Title 24 Acceptance Tests
23
Air-Side Economizer Acceptance
24
Title 24 Acceptance Tests
Purpose Check economizer installation and provision for exhaust or relief Test economizer operation CCC Meeting Title 24 Acceptance Tests
25
Title 24 Acceptance Tests
Overview (2005) References Standard Sections §144(e) and §125(b) Non-Residential ACM Manual NJ 7 Scope All new systems with air-side economizers No testing required if economizer is factory installed and certified operational CCC Meeting Title 24 Acceptance Tests
26
Base Requirement in Title 24
§144(e) Economizers. Each individual cooling fan system that has a design supply capacity over 2,500 cfm and a total mechanical cooling capacity over 75,000 Btu/hr. shall include either: An air economizer capable of modulating outside-air and return-air dampers to supply 100 percent of the design supply air quantity as outside-air; or A water economizer … [Be] capable of providing partial cooling even when additional mechanical cooling is required to meet the remainder of the cooling load. Air-side economizers shall have high limit shutoff controls complying with TABLE 144-C. Only where 144(e) applies CCC Meeting Title 24 Acceptance Tests
27
Title 24 Acceptance Tests
Related Tests NJ 3.1 Variable Air Volume Systems Outdoor Air Acceptance NJ 3.2 Constant Volume System Outdoor Air Acceptance NJ 8 Demand Control Ventilation Acceptance This test should be combined with minimum OSA to reduce time and costs CCC Meeting Title 24 Acceptance Tests
28
Construction Inspection
High limit lockout switch type and setting Location and installation of outside air sensor Wiring of economizer controls Provision for exhaust or relief CCC Meeting Title 24 Acceptance Tests
29
Title 24 Acceptance Tests
Test Procedure Simulate cooling load with high-limit switch disabled Simulate cooling load with high-limit switch enabled Return system to normal CCC Meeting Title 24 Acceptance Tests
30
Title 24 Acceptance Tests
Project information (typical) Construction inspection (measure specific) CCC Meeting Title 24 Acceptance Tests
31
Title 24 Acceptance Tests
Certification (typical) In 2008 a second block with signature will be added for review of documentation by licensed contractor or engineer CCC Meeting Title 24 Acceptance Tests
32
Title 24 Acceptance Tests
Equipment tests (measure specific) Testing results (measure specific) Final result (typical) CCC Meeting Title 24 Acceptance Tests
33
Title 24 Acceptance Tests
What’s New in 2008 All tests will be in Standards Clean up of known conflicts New tests will be added with new measures Economizer tests for manufacturers will be detailed Possible testing of fenestration systems Expansion of lighting tests to signage and outdoor lights CCC Meeting Title 24 Acceptance Tests
34
Example Economizer Issue
Economizers only required for 2-stage AC units (>65,000 Btuh AND >2,500 cfm) Testing for all economizers Tests need to be different for one and two stage units: Integration High limit switches CCC Meeting Title 24 Acceptance Tests
35
Title 24 Acceptance Tests
Hot Issues How/whether to test high limit switches for electronic controllers (like the Honeywell H705)? Defining a test that a TAB technician can do Avoiding warranty issues with controllers/AC units What to do when a unit fails the test Should we require 2-stage thermostats for economizers on single stage units? CCC Meeting Title 24 Acceptance Tests
36
Title 24 Acceptance Tests
Questions CCC Meeting Title 24 Acceptance Tests
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.