Presentation is loading. Please wait.

Presentation is loading. Please wait.

ARAC/H/F Air-cooled water chillers, free-cooling chillers and heat pumps Range: kW.

Similar presentations


Presentation on theme: "ARAC/H/F Air-cooled water chillers, free-cooling chillers and heat pumps Range: kW."— Presentation transcript:

1 ARAC/H/F Air-cooled water chillers, free-cooling chillers and heat pumps Range: 120-260kW

2

3 Range

4 Range

5 Layout – Macro Components
Simple maintenance and installation of components Easily accessible electrical panel Simple replacement of components (access from 3 sides) Protected user terminal Anti-vibration supports to avoid vibrations inside the unit

6 Layout – Macro Components
Fans Condensing section Shell & tube evaporator Water tank Expansion receiver (24 l - 10 bar max) Circulation pump Electrical panel

7 Layout – Macro Components
Temperature sensor H2O inlet Second temperature sensor H2O outlet Differential pressure switch Pump shut-off tap Temperature sensor H2O outlet Check valve

8 Accessible dehydration filters
Layout – Macro Components Scroll Compressors in tandem TWIN SYSTEM Expansion valve Expansion valve Accessible dehydration filters

9 Layout – Macro Components
Main characteristics of the hydraulic section: The check valve is downstream from the pumps: this allows easy replacement in the event of pump installation. 1 or 2 circulation pumps (1+1 in stand by) with automatic control Options: 2 possible configurations: standard & high pressure (150 and 300 kPa) Water tank and expansion receiver with safety valve Anti-freeze heaters Algorithm regulation of the inlet water temperature

10 Cooling circuit All of the units are equipped with 4 identically sized compressors placed in parallel in pairs on two refrigerant circuits. For this reason the circuits and the compressors are independent from each other. 4 steps at any given time elevated efficiency at partial loads optimum modulation of the cooling capacity supplied by the unit

11 Compressors All of the models are equipped with four rotary SCROLL compressors, connected in tandem. All of the models have two independent refrigerant circuits, guaranteeing at least 50% of the cooling capacity in the event of problems with one of the two circuits as well as elevated energy performance at partial loads. Electronic protection device on each compressor Internal check valve on the compressor discharge Rubber anti-vibration supports OPTIONS: Compressor discharge tap A cover and other solutions which make the unit Low Noise

12 Cooling circuit Composed of two independent refrigerant circuits
Expansion valve with internal equalisation Accessible dehydration filters Valve on the liquid line and liquid sight glass with humidity sensor OPTIONS: High and low pressure gauges (onboard) High and low pressure transducers

13 Fans The units are equipped with axial fans which have a diameter of 800 mm. There are between 2 and 4 installed on each unit. They are directly coupled to the electric rotary motor which regulates the speed by means of modulating the power supply. If it has been requested, modulating control of the condensing temperature is available with cut off regulation of the fan speed.

14 Condensing coils All of the units are designed to work with maximum external temperatures of up to 45°C. Each unit features two coils which are placed vertically Copper piping and collection trays and aluminium fins (pitch 1.8 mm)

15 Evaporator Removable Shell & Tube chilled water exchanger:
Two gas circuits and a single hydraulic circuit which is able to operate with low head losses The exchanger is completely insulated with closed cell expanded polyurethane to prevent the formation of condensation and to limit thermal dispersion Equipped with anti-freeze sensors OPTIONS: Anti–freeze heaters around the evaporator Hydraulic connection Kit (standard on units with pumps, water tank and ARAF)

16 ARAC/H/F Air-cooled water chillers, free-cooling chillers and heat pumps Range: 120-260kW


Download ppt "ARAC/H/F Air-cooled water chillers, free-cooling chillers and heat pumps Range: kW."