Model 3169-20/21 Clamp on Power HiTESTER
HIOKI E.E. CORPORATION August 30, 2005 First of all, thank you for joining this seminar. We would like to introduce the new power management tools Model and Clamp on Power HiTESTER. Copyright © 2005 HIOKI E.E. CORPORATION All rights reserved.
2
Clamp on Measurement By measuring the current through clamp on sensors, the 3169 is able to measure the power without cutting the wire. Safe measurement The biggest advantage of clamp on input is that you do not have to cut the wire for measurement. The current can be measured easily by clamping the wire. Also, clamp on input is a safer method than direct input to the instrument.
3
Applications Energy maintenance / control
Energy control under ISO 14000 Saving energy activities Power consumption measurement of specific device / equipment Harmonic analysis Model 3169 is effectively used for various applications. These are just some examples. As you may know, saving energy is very important for addressing environmental measures and cost reduction. Even if the savings you can obtain in a day is small, this can add up to big savings in a year. Model 3169 can help you with your power management of facilities, production lines, machines and so on.
4
Product Overview - 1 Input: 3 voltage + 4 current (able to measure the neutral line) 5 types of clamp on sensors (up to 5000A) Compact and light weight design PC card and internal memory Now, I would like to introduce the main features in brief. Model 3169 offers 3 voltage and 4 current inputs, so that neutral line measurement is possible on 3-phase 4-wire circuits. There are 5 types of clamp on sensors available to meet various applications. The compact and light weight design of the instrument allows the user to conveniently carry it to almost any field. For measurement data recording, 1MB of internal memory is provide, and PC cards are accepted.
5
Product Overview - 2 Reactive power meter method available
Simultaneous integrated power measurement and harmonic analysis Short period interval (1 cycle at the fastest) Multiple circuit measurement by common voltage (4x1P2W, 2x3P3W2M) The reactive power meter method makes the same measurement as a reactive power meter that is often installed for large electric consumers. Harmonic analysis can be made simultaneously during normal power integration measurement. The measurement interval can be set from every cycle, which is equal to 20ms on a 50Hz line, up to to 60 minutes. Also, by using the voltage input commonly, Model 3169 can measure multiple circuits simultaneously for 1-phase and 3-phase installations.
6
Product Overview - 3 Wiring check function Polarity indication
D/A output ( only) 9625 Power Measurement Support Software for data analysis and report editing on a PC Correct wiring of your installation can be confirmed by using the 3169’s wiring check function. The active power and reactive power can be integrated for each polarity separately. For fast response D/A output, the enhanced Model can be selected. Of course, Model 9625 Power Measurement Support Software offers you easy data analysis and report editing.
7
Input / Output / Interface
3 voltage + 4 current Enables to measure the neutral line for 3-phase 4-wire circuit. D/A output ( only) 4 channels, every 1 cycle output at fastest (16 cycles for harmonic) RS-232C Interface Free data transfer software on HIOKI website I would like to explain each feature in more detail. 3 voltage and 4 current inputs enables neutral line measurement as well as helps in multiple circuit measurements. The current input of Model 3169 is a clamp on input with a voltage output clamp on sensor. 4-channel D/A output on Model allows you to output 5V for every cycle at its fastest speed. By recording this output signal, the trend of the load condition can be monitored easily at the site. The built-in RS-232C interface lets you remote control the 3169 from a PC by directly connecting it or via a modem. In addition, data transfer software is downloadable from our website free of charge. Our web address is “
8
Clamp on Sensors 9694 (5A AC) 9660 (100A AC) 9661 (500A AC)
9694, 9660 (15mm) 9694 (5A AC) 9660 (100A AC) 9661 (500A AC) 9669 (1000A AC) 9667 (500/5000A AC) Flexible 9661 (46mm) There are 5 types of clamp on sensors. Model 9694 for 5A, 9660 for 100A, 9661 for 500A, 9669 for 1000A and 9667 flexible type for 500 and 5000A. The range setting is automatically made just by selecting the clamp on sensor type on the 3169. Also, the range can be independently set for CH4 during 3-phase 4-wire measurement. 9667 (254mm) 9669 (55mm)
9
Compact Design Portable design 5.7-inch LCD with backlight
A5 paper size (210 x 160 x 60 mm) 1.2kg 5.7-inch LCD with backlight (320 x 240 dots) Offers easy view and operation Carrying Case Model 3169 is a compact instrument ideal for portable use. Its body is equivalent to an A5-sized paper weighs in at only 1.2kg. Although the design is compact, the instrument still houses a large 5.7-inch LCD with backlight, which makes monitoring and operation easy. Model Carrying Case is large enough to store the meter, accessories and 4 clamp on sensors all together. Therefore, carrying the measurement set to the site in one simple package is very easy.
10
Memory Internal memory: 1MB PC Card Data format: Binary, CSV, BMP
9626(32MB), 9627(64MB), 9726(128MB), 9727(256MB), 9728(512MB) Sufficient for long measurements Data format: Binary, CSV, BMP 1MB of internal memory makes recording easy. However, we would like to recommend using a PC card due to accommodate longer measurement periods and easier data transfer to a PC. The measurement data can be saved to the PC card directly in every cycle at the fastest speed. For your reference, HIOKI assures the correct recording only for our authorized and tested PC cards. There are many PC cards available in the consumer market, but the data writing timing differs from manufacturer to manufacturer. Therefore, to avoid losing important measurement data, please use PC cards sold by HIOKI.
11
Recording Period Under 3P4W4I, 1min interval
Recording normal power values Internal memory: 11 hours 64MB PC card: 30 days Recording normal power values & harmonics Internal memory: 23 minutes 64MB PC card: 23 hours These are examples of the recording period for measurements taken at 1 minute intervals in 3-phase 4-wire 4-current mode. When recording all normal power parameters, you can record 11 hours in the internal memory and 30 days in an empty 64MB PC card. When recording harmonic analysis data simultaneously, 23 minutes can be recorded in the internal memory, and up to 23 hours in the 64MB PC Card.
12
Reactive Power Meter Method
Measures by the same calculation to the reactive power meter often installed for large power consumers. The reactive power is measured directly from voltage and current. The power factor value does not reflect any harmonic component in this method. Model 3169 uses the reactive power meter method which measures the reactive power directly from voltage and current. This method is the same as the one used on reactive power meters that is often installed for large power consumers. On the other hand, the normal method calculates the reactive power from the active and apparent powers. By using this reactive power meter method, the power factor is calculated by the fundamental frequency only without the harmonic component. The normal method calculates the power factor including the harmonic components, so that the power factor becomes worse when the harmonic current becomes bigger.
13
Harmonic Analysis Simultaneous harmonic analysis and integrated power measurement Model 3169 can conduct harmonic analysis up to the 40th order simultaneously for normal power integration measurement. You can change the normal measurement screen and harmonic analysis screen freely during the measurement. In harmonic analysis, you can record the voltage and current waveforms.
14
Harmonic Phase Angle Outflow Inflow Reactive power meter method: ON
90 Load 3169 Source Power phase angle Outflow Outflow Inflow LEAD Reactive power meter method: ON Displayed as 0 to +/-180 degrees “LEAD/LAG” and “Inflow/Outflow” Reactive power meter method: OFF Displayed as 0 to +180 degrees “Inflow/Outflow” only Voltage/Current phase angle +/-180 LAG In harmonic analysis, by referring to the harmonic power phase angle, you can judge if the harmonic inflows to or outflows from the load. In addition, by using the reactive power meter method, you can judge the LEAD or LAG from the harmonic voltage or current phase angle. -90
15
Short Period Interval Normal mode: 1/2/5/10/15/30s, 1/2/5/10/15/30min
Fast mode: 1 cycle, 0.1/0.2/0.5s 1min or longer interval is required to save the harmonic analysis data. Recording is made for the instantaneous values only in the Fast mode. MAX/MIN/AVE values can be recorded for each interval in the Normal mode. Model 3169 can record the instantaneous RMS values in very short intervals. In the fastest interval, you can record for every cycle which is equal to 20ms on a 50Hz line. In normal mode, the maximum, minimum and average values within every interval are recorded. Since the calculation is made for every cycle, the peak value is correctly recorded as the maximum value.
16
Advantages of Fast Interval Measurement
Detailed trend monitoring for the frequently changing load like molding machine, elevator and copy machine, etc. Details of in-rush current measurement On Model 3169, the peak value is correctly recorded as MAX value even in the slower interval. Now, let’s think about the advantages of fast interval measurement. First, detailed fluctuation recording is possible for frequently changing loads like those found on molding machines and elevators. Another piece of familiar equipment that bears the same characteristics is the copy machine. In addition, fast mode is effective for measuring the in-rush current when starting a motor. If the details are not necessary and knowing the maximum value is sufficient, you can record longer by measuring in normal mode which outputs less amount of data to store. As explained previously, Model 3169 can record the maximum value of every interval based on the calculation for every cycle. We will show you the actual data in fast mode during the explanation for the Model 9625 PC software.
17
MAX/MIN/AVE Recording
Inst. 1 Inst. 2 MAX 2 Inst. 3 Inst. 4 MAX 1 MAX 3 Instantaneous value AVE 2 AVE 1 AVE 3 MIN 2 MIN 3 MIN 1 Elapsed time This figure shows you the recording timing of normal mode which records the maximum, minimum and average values. As you can see, all data within the interval is output in the timing of auto output. Interval time Interval time Interval time Auto output 1 Auto output 2 Auto output 3 Auto output 4 Start time series measurement End time series measurement
18
Multiple Circuit Measurement
Multiple circuit measurement possible with common voltage. 4 x 1P2W circuit 2 x 1P3W circuit 2 x 3P3W circuit (in 2 meter method) By using the voltage input commonly, Model 3169 can be utilized to measure multiple circuits. Simultaneous measurement is possible for 4 circuits in 1-phase 2-wire, 2 circuits in 1-phase 3-wire and 3-phase 3-wire 2-meter mode.
19
3P3W2M or 3P3W3M 3P3W2M (2-meter method) 3P3W3M (3-meter method)
Use 2 current inputs only. Power and power factor of each phase are meaningless. 3P3W3M (3-meter method) Use 3 current inputs. Both value of each phase and sum value are effective for power. I just mentioned the 3-phase 3-wire 2-meter method. In fact, Model 3169 also provides a 3-meter method for a 3-phase 3-wire circuit. What is the difference between the 2-meter method and 3-meter method? In the 2-meter method, Model 3169 is connected to 2 phases. Then, the SUM value is obtained by vector calculation. By this method, SUM value is correct even on an unbalanced circuit, but we must recognize that the values for each phase is meaningless although they are displayed. On the other hand, 3-meter method requires that you connect to all 3 phases. With this measurement method, the values of each phase are correctly measured.
20
Wiring Check Wiring diagram is displayed for easy wiring
Check wiring using vector diagram. Model 3169 offers a wiring check function as you can see. You can check the wiring using the vector diagram after completing the wiring. By using this function, you can be sure that you are making the wirings correctly to avoid the loss of data caused by incorrect wiring. However, please note that this function is not perfect for all. Therefore, please pay careful attention when you make wiring.
21
Polarity Indication Independent integration for WP+(consumption) and WP- (regeneration) as well as WQ+ (lag) and WQ- (lead). Integration of active power and reactive power can be made for each positive and negative polarity separately. You can then identify the consumption or regeneration of active power as well as lead or lag of reactive power.
22
9625 Power Measurement Support Software
Easy analysis and report editing Handle multiple data files simultaneously Model 9625 Power Measurement Support Software helps your data analysis and report editing on a PC. The details will be introduced in the demonstration later, so that I would like to introduce its main features in brief now. First, Model 9625 can handle multiple data files simultaneously. This helps when comparing the data recorded at the same time but at difference places is necessary.
23
Functions of Model 9625 Able to handle the data of 3166 and 3169 (Binary or CSV data). Create the time-plot, summary report, daily/weekly/monthly report. Model 9625 can process measurement data taken with Model 3169 as well as its popular predecessor Model 3166. Some of you may already have Model Model 9625 is an effective data analysis tool for that model as well. The software provides time series graphs, summaries as well as daily, weekly or monthly reports. In addition, a harmonic list, harmonic graph, harmonic waveform and unit settings can be displayed on the PC.
24
What happens at a power outage?
There is no power consumption under the “Power outage” situation. Model 3169 acts as follows under this situation. Clock: Keeps running Settings: All settings retained Data retained right up until power outage. (before 10s for fast interval mode) After power recovery, measurement resumes and records “0” during outage Some of you may wonder what happens if a power outage occurs, because Model 3169 uses an AC power supply. As there is no power consumption during a power outage, the important question is whether or not Model 3169 can still store the data before the outage took place, and then resume measurement after power recovery. The answer is “YES” for both. The data before the outage is retained and the measurement is automatically re-started upon power recovery. However, we cannot assure that data is stored if the power outage occurs just when Model 3169 is accessing to its internal or PC Card memory.
25
Summary Model 3169 is an ideal portable clamp on power meter for saving energy and power management activities. Saving energy is kind to the environment as well as benefits for cost saving. Model 3169 is ideal for power measurement in various situations. It is effective for power management for environment protection. In addition, it is a powerful tool for saving energy activities which is directly connected to cost reduction.
26
Thank you Thank you for listening.