MODULAR DATA CENTER PUE 1.07 1 1
2
- EATON power infrastructure (UPS + electrical infrastructure)
MODULAR DATA CENTER Container Park with: - EATON power infrastructure (UPS + electrical infrastructure) - AST Containers and Modular Natural Free Cooling MNFC® technology 2 2
3
About THOR: MODULAR DATA CENTER - Based in Reyjkavik (Iceland).
- Hosting and Cloud Storage provider 100% Carbon Neutral Data Center (all power generation is geothermal and hydro). Maximum resiliency: Tier 3 18 x IT Container 40´ with 280 racks in total and 4MW IT power. Natural Free Cooling. Ultra low TCO: due to low PUE and very cheap kw/h (€ 0,03), about 70% less than in continental Europe. Redundant Fiber Optic link to continental Europe with 50ms latency. 3 3
4
Electrical consumption in Data Centers
IT systems 38%-63% Air Conditioning 23%-54% UPSes 6%-13% Lighting 1%-2% Two areas to focus on savings Energy costs grow between 10% to 25% annually 4
5
The challenge of Free Cooling in Iceland
MODULAR DATA CENTER The challenge of Free Cooling in Iceland Ideal location for Free Cooling: temp year round does not exceeds 24ºC. However, very high content of sulphur in the ambience. A study by IBM showed that direct air free cooling (even with EPA filter) damaged processors after 6 months. Direct air intake in Iceland is not possible. An alternative technology must be used. 5 5
6
Natural Free Cooling… not only in Iceland
MODULAR DATA CENTER Natural Free Cooling… not only in Iceland MNFC can provide Free Cooling up to 24ºC. 89% of hours in Madrid are below 24ºC (we can achieve PUE 1,11). With std. Chiller Free Cooling (CW 7ºC/12ºC) we can only use 25% of the year-hours! Savings in a 500KW IT load Data Center can be of up to € 250k / year! ROI is around 18 months! The improvement is extraordinary even in non-nordic locations! 6 6
7
MODULAR DATA CENTER Cooling Container IT Container Power room 7 7
8
MNFC® System: Main Advantatges
MODULAR DATA CENTER MNFC® System: Main Advantatges No Cross Contamination 80% efficiency Low pressure drop 100% Sensible cooling transfer No moving parts No energy required No single points of failure No Maintenance Patent P
9
MODULAR DATA CENTER Technology
10
MODULAR DATA CENTER Cooling Operation 15ºC 40ºC 31ºC 22ºC
11
MODULAR DATA CENTER Functioning Example
12
Natural Free Cooling® Operational Range
MODULAR DATA CENTER Natural Free Cooling® Operational Range External temperatures < 19ºC temperature at the cold corridor is 24 ºC or lower with no support of traditional cooling 19 ºC < External temperatures < 24 ºC temperature at the cold corridor is 24 ºC or lower WITH evaporative cooling External temperatures > 24ºC chilled water cooling
13
MODULAR DATA CENTER Hours Available
14
PUE and Cooling Efficiency
MODULAR DATA CENTER PUE and Cooling Efficiency
15
NATURAL FREE COOLING container SERVICES room:
MODULAR DATA CENTER PHASE 1 deployed: IT container: 17 14kW/rack NATURAL FREE COOLING container SERVICES room: EATON UPS, model 9390M, 2 x 160 kVA (2n) 2 x Genset 225 kVA (n+1) ATS, Main Switch Boards
16
SERVICES room MODULAR DATA CENTER EATON 9390M UPS Main advantages:
Scalability and modular for future growth Turn key solution, service and maintenance ECONOMODE : internal by-pass and 2% power loss
17
MODULAR DATA CENTER
18
MODULAR DATA CENTER Scalable power infrastructure PHASE 1 PHASE 2
19
MODULAR DATA CENTER
22
MODULAR DATA CENTER Not just a sketch , but a reality.
23
MODULAR DATA CENTER
24
MODULAR DATA CENTER
25
PMDC 40´ Standard: Servers Container configuration
MODULAR DATA CENTER PMDC 40´ Standard: Servers Container configuration
26
PMDC 40´ Compact: Container configuration
MODULAR DATA CENTER PMDC 40´ Compact: Container configuration
27
Central&East Europe Sales Director
MODULAR DATA CENTER Thank you Pablo Fernandez Central&East Europe Sales Director 27