Presentation is loading. Please wait.

Presentation is loading. Please wait.

ABB i-bus® KNX Valve Drive Actuator VAA/A

Similar presentations


Presentation on theme: "ABB i-bus® KNX Valve Drive Actuator VAA/A"— Presentation transcript:

1 ABB i-bus® KNX Valve Drive Actuator VAA/A 6.24.1

2 Valve Drive Actuator VAA/A 6.24.1

3 Valve Drive Actuator VAA/A 6.24.1
General Can be used for the control of 24 V thermoelectric valve drives, e.g. TSA/K 24.1 Suitable for installation in heating circuit distribution systems  Safety class II; SELV Control of floor heating systems

4 Valve Drive Actuator VAA/A 6.24.1
Advantages Convenient heating regulation Powered with 230 V AC (mains plug), output 24 V AC Application of triacs ensures silent switching Valve drives are connected with screwless, plug-in / clamping terminals

5 Valve Drive Actuator VAA/A 6.24.1
Technical information 6 channels 4 valve drives per channel up to 13 valve drives per device Channel-by-channel selection of the method of operation between using either on/off or continuous control Monitoring of the communication objects Actuating value with emergency program Forced mode communication objects for each channel Summer mode with valve protection program Calculation of the maximum continuous actuating value Flow control of a boiler Release function for the valve drives after connecting to mains supply All outputs are protected against short circuit and overload Fuse 2A slow-blow Mounting directly on the wall or on a mounting rail

6 Valve Drive Actuator VAA/A 6.24.1
Circuit diagram  230 V mains connection  Connections (1-6) for valve drives  KNX bus connection terminal  Power on indicator, power LED  Fuse indicator, Fuse LED  Channel LED (1-6)  KNX programming button  KNX programming LED  Fuse

7 Valve Drive Actuator VAA/A 6.24.1
Technical data (1) Supply Mains voltage 230 V AC (+10/-15 %), Hz Maximum power consumption 50 W No-load power consumption 3 W Leakage loss 18 W Outputs Number 6 Type Triac Output voltage 24 V AC (+/-20 %), Hz Output current per channel Maximum 1 A Fuse T2A, common for all outputs

8 Valve Drive Actuator VAA/A 6.24.1
Technical data (2) Maximum number of connectable electrothermal valve actuators Number 13 Per channel 4 Connections KNX Bus connection terminal Valve actuator (6) connection Plug-In terminal 1.0…1.5 mm2 stranded 0.5…1.5 mm2 solid Operating and display elements LED green Power on indicator LED red Fuse defective indicator LED red (6) Channel on indicator KNX programming LED Programming mode indicator KNX programming button Assignment of the physical address

9 Valve Drive Actuator VAA/A 6.24.1
Technical data (3) Release function After switch on 10 minutes Valve protection program In summer mode Once a day for 6 minutes Emergency program With bus voltage failure 8 minutes on and 40 minutes off Enclosures IP 20 To DIN EN 60529 Safety class II To DIN EN 61140 Isolation category Overvoltage category III to DIN EN Pollution degree 2 to DIN EN Temperature range Operation -5 °C…+50 °C Storage -25 °C…+60 °C Ambient conditions Maximum air humidity 75 %

10 Valve Drive Actuator VAA/A 6.24.1
Technical data (4) Design Surface mounted device Wall-mounted or on mounting rail Dimensions 70 x 75 x 302 mm (H x W x L) Mounting position As required Weight 1.700 kg Housing, colour Plastic housing, grey Approvals KNX to EN , -2 CE mark In according with the EMC guideline and low voltage guideline Application program Number of communication objects Max. number of group addresses Max. number of associations Valve Drive Actuator 6f 24 V/1.1 20 66

11


Download ppt "ABB i-bus® KNX Valve Drive Actuator VAA/A"

Similar presentations


Ads by Google