Presentation is loading. Please wait.

Presentation is loading. Please wait.

Wigner Datacenter cooling system upgrade

Similar presentations


Presentation on theme: "Wigner Datacenter cooling system upgrade"— Presentation transcript:

1 Wigner Datacenter cooling system upgrade
HEPIX 2017 Spring, Budapest Gábor Szentiványi Systems engineer Wigner Datacenter

2 Agenda Datacenter and cooling system structure Cooling problem
Solution Future plans Nem kell részletezni

3 Datacenter and cooling system structure
4 computer rooms 1200 kW heat load, unevenly distributed 2 cooling circuits, 7 chillers each 2 manifolds with 4-4 main pumps 40-42 LCPs per computer room

4 Cooling problem See previous site reports from Domokos Szabo and Szabolcs Hernath Coolant flow in manifolds was not designed well 7 chillers teamwork with one built in master Just control system not regulation Also separeted mode software problems Manual control since 2015 Badly planned system Control system is the past, now we have regulation

5 Solutions Data collecting from the system New regulation system
Regulation by the power consumption Superior master PLC New software for chillers New operation mode Still manageable on our old EBI system Not enough sensors, had to extend Data from all 4 seasons Speak about the regulation

6 Solutions (cont.) 1 chiller test 3 chiller test (now)
Cooling circuit no 2 test Upgrade whole cooling system Valós helyzet elmesélése

7

8 Future plans With the new operation mode we can optimize our PUE
LCP regulation optimization Raising the temperature Safety -> efficiency LCP flow sensors need upgrade, valves Vs fans +2 °C temperature -> -5% energy (from Carnot)

9 Thank you!


Download ppt "Wigner Datacenter cooling system upgrade"

Similar presentations


Ads by Google