Control Response Patterns
Engr. R. L. Nkumbwa Copperbelt University 2010
2
System Metrics and Time-Domain Analysis
Time Response Poles and Zeros Transient Response 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
3
System Metrics So, What are System Metrics?
When a system is being designed and analyzed, it doesn't make any sense to test the system with all manner of strange input functions or to measure all sorts of arbitrary performance metrics. Instead, it is in everybody's best interest to test the system with a set of standard, simple, reference functions. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
4
Control Systems 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
5
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
6
System Metrics Once the system is tested with the reference functions, there are a number of different metrics that we can use to determine the system performance. So, what are the examples of such metrics? 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
7
Time-Response Analysis
Since time is used as an independent variable in most control systems, it is usually of interest to evaluate the state and the output responses with respect to time or simply, the Time-Response. In control system design analysis, a reference input signal is applied to a system and the performance of the system is evaluated by studying the system response in the time-domain. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
8
Time-Response The time-response of a control system is usually divided into two parts namely; the Steady-State Response and the Transient Response. In other words, the output response of a system is the sum of two responses: the forced response (steady-state response) and the natural response (zero-input response). 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
9
Time-Response of an Elevator
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
10
Transient Response Defined as the part of the time response that goes to zero as time goes to infinity. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
11
Steady-State Response
Defined as the part of the total response that remains after the transient has died out. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
12
Poles and Zeros The poles of a transfer function are:
(1) The values of the Laplace transform variable, s , that cause the transfer function to become infinite, or (2) Any roots of the denominator of the transfer function that are common to roots of the numerator. The zeros of a transfer function are: (1) The values of the Laplace transform variable, s , that cause the transfer function to become zero, or (2) Any roots of the numerator of the transfer function that are common to roots of the denominator. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
13
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
14
Response blueprint A pole of the input function generates the form of the forced response. A pole of the transfer function generates the form of the natural response. A pole on the real axis generates an exponential response. The zeros and poles generate the amplitudes for both the forced and natural responses. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
15
Natural response Forced response Eng. R. L. Nkumbwa @CBU 2010
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
16
Standard Input Signals
All of the standard inputs are zero before time zero. All the standard inputs are causal. So, what is causal? Causal: A system whose output does not depend on future inputs. All physical systems must be causal. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
17
Standard Input Signals
There are a number of standard inputs that are considered simple enough and universal enough that they are considered when designing a control system. These inputs are known as a unit step, a ramp, and a parabolic input functions. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
18
Unit Step Function A unit step function is defined piecewise as such:
The unit step function is a highly important function, not only in control systems engineering, but also in signal processing, systems analysis, and all branches of engineering. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
19
Unit Step Function 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
20
Ramp Input Function A unit ramp is defined in terms of the unit step function, as such: r(t) = tu(t). It is important to note that the ramp function is simply the integral of the unit step function: 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
21
Ramp Input Function 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
22
Parabolic Input Function
A unit parabolic input is similar to a ramp input: Notice also that, the unit parabolic input is equal to the integral of the ramp function: 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
23
Parabolic Input Function
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
24
Steady State To be more precise, we should have taken the limit as t approaches infinity. However, as a shorthand notation, we will typically say "t equals infinity", and assume the reader understands the shortcut that is being used. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
25
Steady State When a unit-step function is input to a system, the steady state value of that system is the output value at time t = ∞. Since it is impractical (if not completely impossible) to wait till infinity to observe the system, approximations and mathematical calculations are used to determine the steady-state value of the system. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
26
Steady State Most system responses are asymptotic, that is, the response approaches a particular value. Systems that are asymptotic are typically obvious from viewing the graph of that response. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
27
Step Response The step response of a system is most frequently used to analyze systems and there is a large amount of terminology involved with step responses. When exposed to the step input, the system will initially have an undesirable output period known as the transient response. The transient response occurs because a system is approaching its final output value. The steady-state response of the system is the response after the transient response has ended. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
28
Step Response It is common for a systems engineer to try and improve the step response of a system. In general, it is desired for the transient response to be reduced. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
29
First-Order Systems 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
30
Initial Conditions are zero
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
31
First-Order Systems Response
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
32
System Response Response to initial condition K (1 − e−t /τ )
System response. K = gain Response to initial condition 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
33
Unit Step Response 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
34
Unit Step Response The time constant can be described as the time for to decay to 37% of its initial value. Alternately, the time is the time it takes for the step response to rise to 67% of its final value. The reciprocal of the time constant has the units (1/seconds), or frequency. Thus, we call the parameter a the exponential frequency. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
35
Time Constant 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
36
Second-Order Systems Response
ζ = 0 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
37
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
38
Step Response Vs. Pole Location
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
39
System Response 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
40
Target Value The target output value is the value that our system attempts to obtain for a given input. This is not the same as the steady-state value, which is the actual value that the target does obtain. The target value is frequently referred to as the reference value, or the "reference function" of the system. In essence, this is the value that we want the system to produce. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
41
Example of an Elevator When we input a "5" into an elevator, we want the output (the final position of the elevator) to be the fifth floor. Pressing the "5" button is the reference input, and is the expected value that we want to obtain. If we press the "5" button, and the elevator goes to the third floor, then our elevator is poorly designed. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
42
Time-Domain Specifications
So, what are Time-Domain Specifications? 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
43
Time-Domain Specifications
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
44
Rise Time Is the amount of time that it takes for the system response to reach the target value from an initial state of zero. Rise time is defined as the time for the waveform to go from 0.1 to 0.9 of its final value. Rise time is typically denoted tr, or trise. This is because some systems never rise to 100% of the expected, target value and therefore, they would have an infinite rise-time. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
45
Settling Time After the initial rise time of the system, some systems will oscillate and vibrate for an amount of time before the system output settles on the final value. The amount of time it takes to reach steady state after the initial rise time is known as the settling time Which is defined as the time for the response to reach and stay within, 2% (or 5%) of its final value. Damped oscillating systems may never settle completely. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
46
Settling time 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
47
Peak Time The time required to reach the first or maximum peak.
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
48
Percent Overshoot The amount that the waveform overshoots the steady-state or final value at the peak time, expressed as a percentage of the steady-state value. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
49
Pole-Zero Plots 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
50
Step Response as Poles Moves
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
51
Example of a Refrigerator
The refrigerator has cycles where it is on and when it is off. When the refrigerator is on, the coolant pump is running, and the temperature inside the refrigerator decreases. The temperature decreases to a much lower level than is required, and then the pump turns off. When the pump is off, the temperature slowly increases again as heat is absorbed into the refrigerator. When the temperature gets high enough, the pump turns back on. Because the pump cools down the refrigerator more then it needs to initially, we can say that it "overshoots" the target value by a certain specified amount. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
52
Exercise Find peak time, percent overshoot, and settling time from pole location. 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
53
Exercise 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
54
Solution 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
55
Effects of adding a Zero
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
56
5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010
57
Time-Domain Analysis Do further research on this topic please.
Consider researching on Positional error constants 5/25/2018 5:01:12 AM Eng. R. L. Nkumbwa @CBU 2010