EHN 1 CO2 Leaks inside the beam lines
D.Jaillet EN-EA-CT
2
CO2 Leak in H8 (PPE148) Middle June leak of CO2 inside H8 (PPE148)
CO2 gas pipe disconnected to the XCET CO2 manual valve open (Leak flow estimated: ~ 12m3/h) A2 and EDMS v.1(Incident report) PPE 148 :XCET PPE 158 :Panneaux CO2 EDMS : v.1
3
Proposal:ODH-CO2 Hazard in beam lines
ODH Risk assessment(Should be performed): PPE 148 PPE 132 PPE 124 PPE 152 Mitigation measures: Portable/fix detector + Signage of the PPE(Risk of oxygen deficiency-Risk of high CO2 concentration) Flow monitoring Locking the valves (Request to be open) EDMS : v.1
4
Reminder/Recommendation
Personal protective equipment Follow the safety rules Do not touch if you don't know HSE will send a SAFETY BULLETIN about the compression fitting connector Check them If you need help(Gas for experimental area ) Contact EDMS : v.1