1 PRESENTATION ON FIRE AND GAS SYSTEM By Satish Makwana - Instrument Department Date : 04/05/2012

2 Big fire in IOC depot near Jaipur
Why F&G System is required ? Big fire in IOC depot near Jaipur PROPERTY - Loss Cr. Deaths Loss ?.

3 F&G System at Mangala F&G - MPT F&G - WELLPAD FIELD F&G BUILDING F&G
Train # 2 Fire Station All Cellar pits in Wellpad #1 TO 18 Wellpad #1 TO 18 CCB/Ch.Lab/SS 5 Train # 3 SS 1A Train # 4 SS 1B GPA SS 2 VRU SS 3 Export Oil SS 4A Diesel Tank/Flare SS 4B Warehouse

4 When Alarm comes what we have to do first?
Identify Field or Building F&G Alarm? At Fire Station At Control Room Check Building Fire Monitoring Stations Check Field F&G Station Overview Check Field F&G Station Overview Contact Fire Station for Building F&G Identify the Area having Alarm Silence the Alarm Inspect the area find the abnormality Do suitable action for rectification Normalize the system by reset

5 Field F&G Alarms Any of the Flame detectors, Point gas detectors, Open path detectors or Deluge valves operated will generate alarm. Any manual call points if Glass is broken will generate alarm. Any alarm generated will be highlighted on the operator screen and the corresponding zone will become red.

6 Field F&G Trips Two no. of alarm generated in one Zone will be considered as a confirmed fire or gas presence in the zone and will result an alarm and process shutdown (PSD-2) for the particular zone. Confirmed fire or gas alarm in two Zones will result in ESD1 and PAGA (Public address and general alarm system). All the process and power except UPS power will trip.

7 Is Our Building F&G System Reliable?

8 Is Our Build F&G System Reliable?
Date Description Action Taken 3-Feb-12 SS-1A PANEL ROOM MPT-SD M1-145 Activated due to STG970 LAPT Failure SS-1A PANEL ROOM MPT-SD M1-114 SS-1A PANEL ROOM MPT-MSD M1-113 12-Apr-12 SS4BBATT RM DET ACT/MPT-ZAM-81709/M1-109 Heat detector cleaned CHEMICAL BUILDING MPT-ZAM M3-107 Due to drilling dust generated alarm 21-Apr-12 SS2/PANEL EQUIP/MPT-SD-81740/SMOKE DET No information CHEMICAL BUILDING MPT-ZAM M3-108 Fault Heat detector Replaced

9 Is Our Field F&G System Reliable?

10 Workout Done by F&G Team after commissioning
Cleaned and Serviced the detectors to avoid Frequent False alarm coming due to dust (by construction activity) NRV installed in Deluge circuit to avoid False operation of other Deluge valves due to high DP across them HVAC interlocks taken in line Inergen system made ready (still in Manual) Field F&G interlocks lined up The Well pad Building F&G Alarm connected to our F&G CCB Fire station HMI Installed for monitoring Field F&G ESD- 1 taken in line with all relevant more than 35 F & G Tags which were in bypassed condition earlier We have already reduced the AMC cost 50% by taking the building F&G PM jobs .

11 Field F&G Instrumentation
IR3 Flame Detector Open Path Gas Detector OR Line of Sight Gas Detector -12 Point Gas Detector – 6 Deluge Valve – 23 Manual Call Point – 107

12 Location of Field F & G Instruments
Train-2 8 FD , 3 Open path Gas Detector Train-3 8 FD , 3 Open path Gas Detector Train-4 14 FD , 3 Open path Gas Detector VRU 6 FD , 6 Point Gas Detector Export oil tank 4 FD Diesel tank / Flare area 6 FD GPA area 2 FD , 3 Open path Gas Detector

13 IR Flame Detector IR Flame Detector Make : Sharp eye Model no: 20/20SI
The principle of flame detector is based on the detection of IR radiation from the flame and Flame detector will gives Analog output signal to the system. The system will generate an alarm based on the intensity of IR rays

14 Open Path Gas Detector Detector Source
Open path Gas Detector OR Line of sight Gas Detector Make : Spectrex Inc. – SafEye Model : Source - OPS-FI3SE Model : Detector - OP-IF100SE The principle of open path gas detector is based on the absorption of radiation ( IR rays ) caused by the presence of Gases in the medium and the losses of the transmitted IR spectrum is sensed by the Detector. Detector Source

15 Point Gas detector Point Gas detector Make : Crocown Model : Nimbus
Nimbus is a fixed point infrared gas detector for the detection of common hydrocarbon gases in the range 0-100% LEL and provides a 4-20 mA signal proportional to the Gas concentration.

16 Deluge Valve Deluge valve Make : Darling Muesco

17 LINE DIGRAM FOR DELUGE SYSTEM
SOV Manual Drain Needle Valve PSL NRV QB Loop PSH Equipment to be protected Fire water I/L line Deluge valve

18 WORKING PRINCIPLE and OPERATION
Deluge valves are held shut with pressurized water placed in the valve’s priming chamber. Release of water pressure by any of the below mentioned ways from priming chamber will operate deluge valve If the Detection line pressure decreases due to QB rupture Manual Operation from Field Manual Command from DCS Auto Operation Due to Confirmed Fire or Gas Alarm

19 Manual Call Point Manual Call Point Make : MEDC

20 Building F&G Instrumentation
Conventional type smoke/Heat Detectors Smoke detectors -addressable Open Path Beam smoke Detectors -addressable

21 Smoke and Heat detectors
Smoke detectors Make : TYCO Model no

22 Make : tyco model no : mr601tex conventional type smoke/heat detector
Conventional type smoke/Heat detectors Make : tyco model no : mr601tex conventional type smoke/heat detector

23 Beam Detector Beam Detector Make : TYCO
Cairn India – 2007 Beam Detector Beam Detector Make : TYCO Model no : simplex fire ray 50 ru

24 DGFAP (Data Gathering Fire Alarm panel)
Make : Simplex Building Smoke / Heat Detector are connect in DGFAP All Building DGFAP are connect in network loop

25 DGFAP (Data Gathering Fire Alarm panel)
DGFAP Alarms Trouble Alarm Fire alarm All Building DGFAP Connect in ID Net Loop as below Fire station – CCB – SS1A – SS1B – SS2 – SS3 – SS4A – SS4B- SS5 – Ware house-Fire station

26 Our Future Focus One Building F&G Monitoring Station to be installed in CCR All Wellpad building F&G system to be hooked up with our MPT Fire Station through FO and finally to ID net Fire Station , Warehouse , Security Building , Wellpads Graphics to be incorporated. Fire Station and Security building and Wellpads to be configured for alarm History Train # 2 , Train # 3 Beacon alarm incorporation Boiler and STG Area Fire and Gas system Installation and Commissioning

27 ANY QUESTION???? 4 4 4 4 4 4 4

28 THANK YOU

29

30

31

32

33

34 Bird Spikes Installed at Warehouse to avoid false alarm