Ventilated underground tunnel as a contribution for sustainable refurbishment of buildings affected by rising moisture Jiří PAZDERKA,

Similar presentations


Presentation on theme: "Ventilated underground tunnel as a contribution for sustainable refurbishment of buildings affected by rising moisture Jiří PAZDERKA,"— Presentation transcript:

1 Ventilated underground tunnel as a contribution for sustainable refurbishment of buildings affected by rising moisture Jiří PAZDERKA, Eva HÁJKOVÁ Department of Building Structures, Czech Technical University in Prague,

2 Presentation outline Remediation methods - air cavities
Current design of ventilated underground ducts New technical solution of air ducts Drying efficiency - laboratory test Results and discussion Acknowledgement Research project „Analysis of the Effectiveness of Modern Methods of Rehabilitation of Buildings Affected by Moisture“, no. SGS15/128/OHK1/2T/11.

3 Remediation methods - air cavities
Additional protection of buildings against moisture rising from the subsoil Principle: enable an air flow along the surface of moist structures to ensure sufficient evaporation of moisture from the structure High demands for the durability of materials used in the structures of the air duct

4 Current design of ventilated underground ducts
Conventional air duct based on a masonry structure

5 New technical solution of air ducts
New sustainable solution: A specially shaped concrete block

6 New technical solution of air ducts
Ventilated tunnel (concrete blocks) installed into a historic masonry building

7 Drying efficiency - laboratory test
Scheme of a laboratory model with air duct in a scale of 1 : 2

8 Drying efficiency - laboratory test
Arrangement of laboratory model

9 Drying efficiency - laboratory test
Laboratory test – Timeline months

10 Results and discussion
The final values of the moisture readings w [wt. %] , after 3 month of ventilation using The velocity of the flowing air in the duct 0.05 m/s Decreased of moisture in the masonry by 43 % on average.

11 Results and discussion
The initial values of moisture after 30 days of using the fan

12 Results and discussion
The final values of moisture after 90 days of using the fan

13 Conclusion Effective solution for the additional protection of historic buildings against ground moisture - high durability and simplicity In comparison with contemporary masonry air ducts - more sustainable (higher durability of used structures) Respecting the original appearance of historic buildings without damage to historic masonry Moisture in the masonry decreased by 43 % on average compared to the reference sample

14 Thank you for your attention!


Download ppt "Ventilated underground tunnel as a contribution for sustainable refurbishment of buildings affected by rising moisture Jiří PAZDERKA,"