Download presentation
Presentation is loading. Please wait.
1
Planning The Electrical System
Safe Adequate for convenience Efficient Expandable May 2007
2
Types of Outlets and Circuits
Lighting Outlets Convenience Outlets Special circuit outlets
3
Branch Circuits Individual Circuits Motors ½ horsepower and larger
All 240 volt equipment Equipment in which operation and/or temperature is critical
4
Small Appliance Circuits
At least two small appliance circuits Must be 20 amp No lighting outlets may be served by small appliance circuits Must not serve any other room in the house Outdoor receptacles may be served by small appliance circuits
5
Laundry Circuits At least one laundry circuit is required by NEC
Must be 20 amp The circuit may not serve any lighting outlets or outlets in any other room in the house
6
General purpose circuits
All lighting outlets must be served with a general purpose circuits All receptacles not on an appliance, laundry, or individual circuit May be 15 or 20 amp
7
Lighting Outlet Requirements
Must have a switch controlled light outlet in each room Stairways At least one lighting outlet is required in Attic Under floor space Utility room basement
8
Receptacle outlet requirements
No point along the floor line in any wall space be more than 6 feet from a receptacle Receptacle outlet must be installed at each counter space in the kitchen and dining area No more than 24 inches from power Must be GFCI Protected Minimum of three circuits on kitchen counter space
9
Receptacle outlet requirements
One bathroom wall receptacle At least one outdoor receptacle At least one laundry room receptacle At least one receptacle in garage At least one receptacle in basement At least one receptacle in hallways 10 feet or longer
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.