Implementation of Radioactive tracer 85Kr for Ventilation Rate Measurements in Dairy Barns
2011 ASABE Annual Meeting M. Samer, W. Berg, M. Fiedler, H.-J. Müller, M. Gläser, C. Ammon, C. Loebsin, O. Tober, P. Sanftleben, R. Brunsch
2
Introduction Investigation of emissions from livestock buildings is important as these pollutants affect the health of farmers and the surrounding environment Emission monitoring enables judgments on the effectiveness of mitigation strategies and controls on emission targets Quantifying gaseous emissions from naturally ventilated animal buildings is a particularly difficult task and associated with large uncertainties One aspect is to measure the ventilation rate and then to quantify the gaseous emissions
3
Microclimatic and climatic conditions were measured and recorded
Methodology The ventilation rates were determined by two methods: tracer gas technique and CO2-balance Fifteen field experiments were carried out to study the ventilation rate in a naturally ventilated dairy barn located in North Germany during 3 consecutive winter seasons During each field experiment, continuous measurements of gaseous concentrations (NH3, CO2, CH4, and N2O) were carried out Microclimatic and climatic conditions were measured and recorded
4
Side view of the investigated barn The investigated dairy barn
Plan view of the investigated barn
5
The following factors were tested:
Methodology The following factors were tested: 85Kr line release source vs. 85Kr point release source, average α-values vs. sum impulses, selected radiation counters vs. all radiation counters The results were compared with each other by developing a linear regression model and carrying out Pearson correlation analysis The differences between the reference method and the eight factor combinations were tested using the ANOVA model
6
The results showed that the best factor combinations were:
Line release source considering the impulses recorded by selected radiation counters and implementing the sum method of all impulses, where high R2 value of 0.82 and reliable parameter estimate of 1.00±0.19 were found Point release source considering the impulses recorded by all radiation counters and implementing the sum method of all impulses, where high R2 value of 0.91 and reliable parameter estimate of 1.19±0.15 were found
7
Factor Combinations Difference to Reference (h-1) a1b1c2 a1b1c1 a2b1c2 a2b1c1 a1b2c2 a1b2c1 a2b2c2 a2b2c1 a1 85Kr line release source b1 Average α-values c1 Selected radiation counters a2 85Kr point release source b2 Sum impulses c2 All radiation counters Differences of air exchange rates of the eight factor combinations to the reference method
8
Results The average hourly gaseous emissions through the different winter seasons, subject to the reference method, were 2.9, 14.5, 1785, and 1.6 g h-1 AU-1 for NH3, CH4, CO2, and N2O, respectively The average daily gaseous emissions were 70, 347, 42853, and 37.5 g d-1 AU-1 for NH3, CH4, CO2, and N2O, respectively
9
Sum of impulses lead to better results than the average α-values
Conclusions Sum of impulses lead to better results than the average α-values Considering all readings of the radiation counters is more representative for air movement Point release source shows better results than the line release source during winter measurements