1 CORE AREA K. F. Chan (Mr.) MEBS6002

2 DIVERSITY OF ILLUMINANCE
Core area – area of working plane having a boundary 0.5m from the walls Maximum to minimum illuminance not to exceed 5:1 K. F. Chan (Mr.) MEBS6002

3 TASK & SURROUND K. F. Chan (Mr.) MEBS6002

4 UNIFORMITY OF LUMINANCE
UNIVERSITY OF HONG KONG Faculty of Engineering M.Sc.(Eng) in Building Services MEBS 6002 Lighting Engineering UNIFORMITY OF LUMINANCE Luminance ratio task to immediate surround – 3:1 task to general background – 10:1 -- therefore, most modern office furniture are light coloured Task area x 0.5m in front of the observer at the edge of the desk or working surface. Immediate surround – band with a width of at least 0.5m. Typical task luminance range is 40 to 120 cd/m2, and seldom exceeds 200cd/m2 K. F. Chan (Mr.) MEBS6002

5 K. F. Chan (Mr.) MEBS6002

6 ILLUMINANCE VARIATION
Task area – 0.5m x 0.5m Minimum to average not less than 0.8 K. F. Chan (Mr.) MEBS6002

7 UNIFORMITY OF ILLUMINANCE
In general, if the recommended SHR is not exceeded, minimum to average of 0.8 can be achieved In general, if the mid-point ratio calculated according to CIBSE TM5 does not exceed 0.7, uniformity of 0.8 can also be achieved. K. F. Chan (Mr.) MEBS6002

8 SHR K. F. Chan (Mr.) MEBS6002

9 MOUNTING HEIGHT K. F. Chan (Mr.) MEBS6002