WinCC-OA Upgrades in LHCb
2
Control System Scope Different Scope Different Requirements?
Detector Channels Front End Electronics Readout Boards High Level Trigger (Farm) Storage Trigger Experiment Control System DAQ Detector & General Infrastructure (Power, Gas, Cooling, etc.) External Systems (LHC, Technical Services, Safety, etc.) TFC Monitoring
3
Control System Architecture
INFR. TFC LHC ECS HLT LV Dev1 LV Dev2 LV DevN DCS SubDetN DCS SubDet2 DCS SubDet1 DCS SubDet1 LV SubDet1 TEMP SubDet1 GAS … DAQ SubDetN DAQ SubDet2 DAQ SubDet1 DAQ SubDet1 FEE SubDet1 RO FEE Dev1 FEE Dev2 FEE DevN … Status & Alarms Commands Legend: Control Unit … Device Unit Some Stats: ~ datapoints ~ datapoint elements ~8 000 Control Units ~ Device Units
4
Control System Deployment
WinCC-OA: ~170 projects Distributed over ~150 PCs All virtual machines All Linux + Driver Machines Only Drivers and/or Scattered Managers ~30 Windows (ccpc/USB boxes of 4) ~15 Linux (ccpc/Specs boxes of 2) 1 DIP Machine
5
Control System Deployment
Some deployment details Projects in “/localdisk” “/group” (G: in windows) visible everywhere “GlobalProject” in Config of All Projects, ex: pvss_path = "/opt/WinCC_OA/3.11" proj_path = "/group/velo/pvss/fwComponents_VEECS1" proj_path = "/group/online/ecs/PVSSShortcutProjects311/GlobalProject" proj_path = "/localdisk/wincc/VEECS1" Operation via “Shortcuts” Automatically generated, for Windows and Linux, ex: pvss_path = "C:/Siemens/Automation/WinCC_OA/3.11" proj_path = "G:/online/ecs/PVSSShortcutProjects311/CentralRepository" proj_path = "G:/online/ecs/PVSSShortcutProjects311/VELO/VELORepository" proj_path = "G:/velo/pvss/fwComponents_VEECS1" proj_path = "G:/online/ecs/PVSSShortcutProjects311/GlobalProject" proj_path = "G:/online/ecs/PVSSShortcutProjects311/VELO/VEECS1_W“ Repositories (containing panels and libs) generated every night Created from FwComponents => Per sub-detector => LHCbRepository
6
Control System Tools “Shortcut” Project
“Database” of ALL Projects, allows: Generate and manage Shortcuts Generate repositories Execute scripts or import DPs on any group of projects
7
Upgrading… Requirements/Wishes: HW and/or Operating System
Do everything centrally As transparent as possible for all types of users Developers, Operators, etc. As fast as possible HW and/or Operating System Normally comes with new WinCC-OA version -> See later
8
Upgrading… WinCC-OA patches WinCC-OA Major Versions
Try to agree with users to do all in one go (but can be negotiated): Done by Sys-admins: Stop projects (Linux service) -> Install Patch RPM -> ReStart projects WinCC-OA Major Versions Depends on “Upgrade” procedure… Worst case example: (move to virtual machines, slc6, windows to linux and 3.8 to 3.11 at once) Extracted ALL DPs to project's dplist dir Copied all Projects to a central area Prepared a script: create new project, import DPs, copy back folders (in the process fix Windows paths and WinCC-OA novelties) Sys-admins created the machines and installed WinCC-OA Run the script for all projects Ask sub-detectors to check if everything still worked
9
Upgrading… Framework Components LHCb Components
Dump new files (panels, scripts, libs) in “GlobalProject” Import DPs to relevant projects, if needed If necessary restart managers or project (either transparently or in agreement with users) JCOP Framework Components Same as above, but: Need to prepare LHCb FW based on JCOP FW Merge LHCb changes: Trending, Alarm Handling Verify carefully all changes… In general we don’t use the Installation tool except to create New projects and for tests
10
JCOP FW Upgrades Requests:
Please do not load new libraries in the config file Always use #uses Please do not overwrite settings in the dpl file, ex: fwTT_TrendTree.root _FwTreeType "" 0x … _AESProperties_fwAes.Alerts.FilterTypes.AlertSummary _AESProperties 2 If a post-install script is needed for an upgrade would be nice to write it in the release notes If the dpl files have changed would be nice to write it in the release notes Would be nice to have an fwInstallation dpl file or to understand exactly when the DPs are upgraded
11
JCOP FW Upgrades Other “features”:
Normally the time of a new FW release and the time window to install it before start up is very short. So by the time I understand all new “features” and how to merge them with LHCb, there is no time to wait for a new version. So I end up “fixing” my local copy and after is done, I forget to report it back… Until the next release… This applies mainly for fwTrending and Alarm Screen But also for example I changed the “Corporate Color” (I think in 3 different places), plus it’s against the guidelines Ok(ish) for DeviceEditorNavigator (development tool) But not for AlarmScreen (an operation tool), completely different look and feel from all other LHCb Operation panels
12
JCOP FW Upgrades Other “features”: DB Schemas FwConfigurationDB schema
We only find out that the schema needs upgrading long after installation…And very close to LHC startup Then we need to open the ConfDB panel and upgrade each schema (once per sub-detector) The upgrade always fails for some schemas-> need Piotr’s help Oracle Archive schema Every new version brings new problems of compatibility between standard API/CERN API/patch level, etc.
13
JCOP FW Upgrades Other “features”: And Notes:
Problem with WCCOAascii Since WinCC-OA 3.11 and all Linux Ascii Manager never starts while the project is running FATAL, , ASCII export cannot be started, WinCC OA project start possibly in progress. Please try again later. Need to stop project and start only main managers Why? Need help… And Notes: We do use occasionally fwInstallation (without DB) So we need to keep it functional We also use the fwSystemOverview tool for upgrades To stop/restart projects, To restart selected managers, etc.
14
Upgrading… Applications Why do we do it like this? Continuous Process
Modify files in /localdisk (or better in a test project) Test When happy move them to FwComponents (central area) Backups are there for “mistakes”… Why do we do it like this? While DCS part is quite stable DAQ projects change every day… No way (for me) to keep up with proper components So couldn’t impose it on the others… I think fwInstallation needs proper/stable components