Presentation is loading. Please wait.

Presentation is loading. Please wait.

VLF CABLE TESTING INCLUDING PARTIAL DISCHARGE & TANGENT DELTA

Similar presentations


Presentation on theme: "VLF CABLE TESTING INCLUDING PARTIAL DISCHARGE & TANGENT DELTA"— Presentation transcript:

1 VLF CABLE TESTING INCLUDING PARTIAL DISCHARGE & TANGENT DELTA
7/24/2018 VLF CABLE TESTING INCLUDING PARTIAL DISCHARGE & TANGENT DELTA Michael T. Peschel High Voltage, Inc. Copake, NY. USA 7/24/2018

2 SUBJECTS COVERED Review of DC Issues What Is VLF VLF Applications
7/24/2018 Review of DC Issues What Is VLF VLF Applications IEEE Standards Lab and Field Results How To Perform The Test Myths about VLF Who Uses VLF Selecting a VLF Model Selecting A Cable Test Method VLF Conclusion Tan Delta Testing VLF Partial Discharge Testing 7/24/2018

3 THIS CAN BE PREVENTED 7/24/2018 In-service failures cause great damage to faulted cables and adjacent cables. Not so if failed under a VLF test. 7/24/2018

4 WHY WAS DC USED DC hipots are small, portable, and economical.
7/24/2018 DC hipots are small, portable, and economical. DC originally used with PILC cable and worked well. Same techniques used when HMW, XLPE, EPR, and other solid dielectric cables were installed. Years later DC was found to harm insulation and leakage current measurements are often ineffective for exposing defects. VLF work started. Until recently, AC field testing of cable was not practical. Now it is practical and economical. 7/24/2018

5 DC USE DISCOURAGED 7/24/2018 Worldwide consensus exists among engineering organizations, utilities, and cable manufacturers that typical DC test voltages of 4 – 5 Vo (4 – 5x line-to-ground operating voltage) damage insulation, lead to failures, and leakage currents are often not indicative of insulation integrity. Using lower voltages renders test meaningless. 7/24/2018

6 Avoid DC Voltage On Service Aged, Solid Dielectric Insulation
7/24/2018 DC Voltage Polarizes Cable. Water trees trap space charges – leads to failures. 7/24/2018

7 WHY IS DC HARMFUL? WATER TREES
7/24/2018 Tree shaped channels are found within the insulation of operating cables resulting from the presence of moisture and electrical fields. Prevalent in solid dielectric cables. Eventually leads to the inception of PD. Leads to insulation failure. 7/24/2018

8 Water Trees 7/24/2018 7/24/2018

9 WHY DC IS DAMAGING 7/24/2018 DC hipot output negatively charges up water tree areas. These “trapped space charges” remain after test. When AC is reapplied, there’s a high difference of potential across very little of the insulation. Leads to pd, electrical trees, & cable failure 7/24/2018

10 UTILITIES RESPONSE TO DC CONCERNS
7/24/2018 Typical DC test voltages were/are times V0. At these high voltages, damage is done. Some reduce voltage to 15 kVDC on 15 kV cable. 15 kV is only 30% above the peak AC stress in service. At this voltage, leakage currents are meaningless. Some do nothing, letting cables fail and then repair. Many have adopted VLF AC hipoting to expose bad insulation and accessories. VLF is the best splice checker. 7/24/2018

11 VLF – Very Low Frequency AC
IF NOT DC - THEN WHAT? VLF – Very Low Frequency AC 7/24/2018 Advantages Light Weight. Low Cost. Simple to Use. Results are certain Disadvantages Voltage Waveform in Some Designs – Can’t Use For TD & PD Cable May Fail Under Test. Perhaps Multiple Failures In Severely Deteriorated Insulation 7/24/2018

12 WHAT IS VLF? 7/24/2018 7/24/2018

13 A VLF HIPOT IS SIMPLY AN AC OUTPUT
INSTRUMENT BUT AT A LOWER FREQUENCY. THE LOWER THE FREQUENCY OUTPUT, THE LOWER THE CURRENT AND POWER REQUIRED TO TEST HIGH CAPACITANCE LOADS LIKE CABLES. DON’T OVERCOMPLICATE IT. IT’S A SIMPLE AC WITHSTAND TEST. VLF IS THE EASIEST, CHEAPEST, MOST CERTAIN WAY OF TESTING THE AC INTEGRITY OF A CABLE. 7/24/2018 7/24/2018

14 DROP THE FREQUENCY Very Low Frequency: 0.1 Hz and lower.
By decreasing the frequency, it is possible to test miles of cable with a small and affordable unit. Output frequencies range from 0.1 – 0.01 Hz. IEEE400.2 recognizes frequencies as low as 0.01Hz. At 0.1 Hz, it takes 600 times less power to test a cable, or any other high capacitance load, than at 60 Hz. At 0.01 Hz, 6000 times higher capacitive loads can be tested than at 60 Hz with the same power consumption. 7/24/2018 7/24/2018

15 VLF EXPLAINED Xc = 1 2 x pi x f x C
7/24/2018 Xc = 2 x pi x f x C The lower the frequency, the higher the capacitive reactance, or Xc. The higher Xc , or resistance across the power supply output, the lower the current/power needed to apply a voltage. 7/24/2018

16 60 Hz vs. 0.1 Hz At 60 Hz. a 1 μF cable has an Xc of 2.65 kOhms.
7/24/2018 At 60 Hz. a 1 μF cable has an Xc of 2.65 kOhms. At 22 kV peak, it requires 8.3 amps of current to test. Total power supply rating must be 183 kVA. At 0.1 Hz, the Xc is 1.59 megohms. At 22 kV, the current needed is 14 mA. Total power supply needed is only kVA. 7/24/2018 (22 kV is the typical test voltage for 15 kV cable)

17 60 Hz. vs. 0.1 Hz. 60 Hertz 0.1 – 0.02 Hertz 50 kVAC @ 3 kVA
7/24/2018 60 Hz. vs. 0.1 Hz. 60 Hertz 0.1 – 0.02 Hertz 50 3 kVA Can test ~ 50’ of cable kVA Can test ~ 5 miles of cable 7/24/2018

18 7/24/2018 APPLICATIONS 7/24/2018

19 IEEE STANDARDS EXIST Power Cable Large Rotating Machinery
7/24/2018 Power Cable IEEE & IEEE Large Rotating Machinery IEEE Diagnostic Testing: Tan d Partial discharge 7/24/2018

20 CAN OTHER LOADS BE VLF TESTED?
7/24/2018 Yes, but no standards exist that define the test. Most other loads are low in capacitance, permitting 60Hz AC hipots to be used. Sometimes large insulators are VLF tested if a powerful enough 60Hz hipot is not available. 7/24/2018

21 WHY TEST CABLES WITH AC VOLTAGE?
7/24/2018 Cables are designed to carry AC voltage. They are factory tested with AC voltage. Cables operate under AC voltage stress. Cables should be tested with AC voltage. Why would you not use AC if you could? 7/24/2018

22 Can Now AC Stress Test Cable
7/24/2018 With VLF, utilities, testing services, industrials, and others can now AC stress test cables in the field. Just like with vacuum bottle or rubber glove testing, now a go/no-go AC stress test can be performed on power cable. If a cable can’t hold 2 – 3 times normal voltage, it’s not healthy. Find the problem, make the repair, and move on. At the very least, every newly installed and repaired cable should be VLF tested before energizing, since many failures are due to installation damage, faulty workmanship, stress from in-service failures, or over voltage thumping. 7/24/2018

23 Other Methods Don’t Get It Done.
7/24/2018 DC Hipot 5 kVdc “Megger” DC Hot stick adaptor 24 hour soak 7/24/2018

24 VLF IT! 7/24/2018 7/24/2018

25 IEEE STANDARDS 7/24/2018 7/24/2018

26 NORTH AMERICAN STANDARDS FOR VLF TESTING
7/24/2018 IEEE overall cable testing standard sanctions VLF testing of cables. IEEE standard for VLF cable testing IEEE covers VLF testing for rotating machinery. Now being updated. Standard for smaller motors/gens. under consideration. Assoc. edison illuminating companies 7/24/2018

27 MOTOR & GENERATOR TESTING
7/24/2018 IEEE Std (1974) Recommended Practice For Insulation Testing of Large AC Rotating Machinery with High Voltage VLF. Refers to Large AC Machines 10 MVA/6 kV & above. Test Waveform: Must be Sinusoidal. Test Frequency: 0.1 Hz. Test Voltage: 1.63x 60 Hz RMS Level 7/24/2018

28 CABLE TESTING IEEE400.2-2004 Recommends test voltage of 2 - 3V0
7/24/2018 IEEE Recommends test voltage of V0 (V0 equals line-to-ground voltage) Test duration is 15 – 60 minutes Best recommendation is for 30+ minutes 7/24/2018

29 IEEE400.2 FIELD TEST VOLTAGES
For Shielded Power Cable Systems Using Sine Wave Output VLF 7/24/2018 Hz Test Voltage System Voltage phase to phase kVrms 5 15 25 35 Installation phase to ground kVrms/kVpeak 9/12 18/25 27/38 39/55 Acceptance phase to ground kVrms/kVpeak 10/14 20/28 31/44 44/62 Maintenance phase to ground kVrms/kVpeak 7/10 16/22 23/33 33/47 Test voltages are generally 2 – 3 time the line-to-ground system voltage. 7/24/2018

30 7/24/2018 IEEE Test Definitions Acceptance Test: A test that demonstrates a degree of compliance of a cable and its accessories with the requirements of the purchaser. Highest test voltage Installation Test: A test made after installation but before a cable system is put into normal operation. The test is intended to show shipping damage or errors in workmanship or damage during installation. Middle test voltage Maintenance Test: A test made during the operation of a cable system and intended to detect deterioration of the system and to check the entire workmanship so that suitable maintenance procedures can be initiated. Lowest test voltage 7/24/2018

31 Cable Test Voltages Determined 2Vo – 3Vo Depending On Cable Size.
7/24/2018 12.5 kV system = 7,217 V0 or line-to-ground. x 3 21.7 kV Maintenance test The peak of the sine wave is the factor driving the inception of partial discharge. Hence, the 22 kV test spec is used for the peak of a sine wave VLF. The test is equivalent to ~ 2x V0 rms. Also, kV/mm insulation varies greatly with cable size. Need at least 2Vo. 7/24/2018

32 WHY 2Vo – 3Vo An abbreviated test or a test too low in
7/24/2018 The IEEE standard says 2 – 3V0 for minutes. Cables routinely see 2x normal voltage due to reflected waves, transients, etc. VLF test voltage must be at least 2x normal line-to-ground. Must use enough voltage for enough time to let the VLF do its job of growing electrical trees to failure. An abbreviated test or a test too low in voltage is worse than no test. 7/24/2018

33 XLPE TREE GROWTH IEEE 400-2001 Test voltage factor (V/Vo rms) 2 3 4
Sine wave VLF rapidly grows electrical trees to failure. 7/24/2018 Test voltage factor (V/Vo rms) 2 3 4 Growth rate at 0.1-Hz sinusoidal test voltage (mm/h)   A 15kV 133% cable has an insulation thickness of 5.9 mm. In a 30 minute test, nearly all defects triggered into pd will grow to failure. 7/24/2018

34 AND LABORATORY RESEARCH
RESULTS FROM FIELD USE AND LABORATORY RESEARCH 7/24/2018 7/24/2018

35 VLF TEST RESULTS 7/24/2018 Numerous case studies show that if a cable passes a proper VLF test, there is a > 95% assurance of no in-service failure in the next few years. Nothing is perfect, but only a few percent possible failure rate post VLF testing is very good. Far better by multiples than with other testing methods. If a cable can hold 2 – 3 times normal voltage for 30-60 minutes, it’s good for years. 7/24/2018

36 XLPE TESTING STATISTICS
7/24/2018 TNB in Malaysia 35kV 2.1 V0 for 60 min. 17,435 VLF tests performed – 2,179 cable failures Minutes to failure Failures % of total 0 - 12 1472 67.62 469 21.54 129 5.93 107 4.92 89.16% 2.78% of tested cables failed later in service. (Many cables were PILC) Tests conducted 2001 – Continue to buy VLF and test all cables. 7/24/2018

37 XLPE TESTING STATISTICS
7/24/2018 Japan: Furukawa, Chubu & Tokyo Electric Research done to determine test voltage and duration versus expected life. Results were: A 33 kV cable tested at 60 kV 0.1 Hz has a 97% probability of no failure for 3 years. 7/24/2018

38 Germany produced some of the first
VLF products more than 20 years ago. German standard: 3Vo rms for 60 minutes. 7/24/2018 7/24/2018

39 Most US users test at the IEEE recommended voltages for 30 minutes.
7/24/2018 7/24/2018

40 The World View Of VLF DC not recommended by cable companies
7/24/2018 DC not recommended by cable companies for cables > 5 years & in moist environments IEEE 2 – 3Vo for minutes 30+ 3Vo recommended. Germany 3Vo for 60 minutes Japan Vo for 15 minutes Malaysia 3Vo for 60 minutes Over 60 countries have purchased the HVI VLF 7/24/2018

41 HOW TO PERFORM A VLF TEST
7/24/2018 7/24/2018

42 TEST PROCEDURE VLF testing is easier than DC testing.
7/24/2018 VLF testing is easier than DC testing. Isolate cable ends like with DC testing, although no cleaning and bagging is necessary. Remove all arrestors, capacitors, transformers, etc. Connect VLF HV lead to conductor & ground to shield. After selecting appropriate test frequency, apply voltage There are no leakage currents to read. Test is go/no-go If cable holds, test is over. Cable is good for years. If cable fails, make repairs and repeat test, or replace. If second insulation failure occurs, maybe stop testing and replace. Most models can test all three phases at once, saving time. 7/24/2018

43 VLF Test Hookup Per IEEE400.2
7/24/2018 Some VLF units have no return wire. HV output and ground cables only. 7/24/2018

44 CABLES INCLUDED WITH TWO PIECE MODEL
7/24/2018 CABLES INCLUDED WITH TWO PIECE MODEL Ground hook HV output from tank 2 test leads for capacitance measurement Cable connectors hook or clamp Phase jumpers 7/24/2018 Interconnect with grounds Scope bnc

45 7/24/2018 VLF-4022CM 7/24/2018

46 OPERATING INSTRUCTIONS
7/24/2018 OPERATING INSTRUCTIONS 1. Select Frequency 3. Rotate to zero (Zero start intl’k) 6. Rotate to raise voltage 5. Press HV On 4. Press Main Power 2. Turn to mA 7/24/2018

47 WHAT IS CABLE FAILURE INDICATION?
7/24/2018 Thermal overload on panel will trip Voltmeter will indicate breakdown Current will spike 7/24/2018

48 FAULT LOCATING NECESSARY
7/24/2018 When VLF testing, cable failures will occur. Someone has to find them. Testing contractors will need to use fault locators and should want to for increased billing. Thumpers, or VLF/thumpers must be purchased. 7/24/2018

49 7/24/2018 COMMON VLF MYTHS 7/24/2018

50 VLF IS DESTRUCTIVE TO INSULATION.
7/24/2018 NOT TRUE. Cable is factory tested at voltages far higher than field VLF levels. VLF is destructive to existing defects that are severe enough to be triggered into partial discharge during the test. That’s the point of the test – light up defects and let them grow to failure. Minor defects and good insulation are not effected. 7/24/2018

51 VLF AGGRAVATES DEFECTS THAT FAIL LATER IN SERVICE
7/24/2018 Only if the test is not properly performed, like any testing method. The proper VLF voltage must be applied for a long enough time to permit defects triggered into pd to grow to failure. An improper test is worse than no test at all. The same can be said for 60Hz hipoting, pd testing, and other tests. If done wrong, problems could result. If done correctly - positive results. 7/24/2018

52 VLF IS REALLY ALTERNATING DC
7/24/2018 Not true. At 0.1 Hz there are polarity reversals every 5 seconds. Even at 0.01Hz there are reversals every 50 seconds. That does not compare at all to a 15 minute, constantly negative output DC hipot test. Space charges and traveling waves are not developed in insulation during a VLF test. The IEEE recognizes frequencies down to .01Hz as ok. 7/24/2018

53 VLF EFFECTIVENESS IS UNPROVEN
7/24/2018 Very wrong. Tell that to the hundreds of users over more than 15 years that have tested tens of thousands of cables with great success. Tell that to the IEEE, CEA, EPRI, cable companies, and many international organizations that have all endorsed VLF. A VLF instrument is just a low frequency AC hipot. Simple product – simple test – simple physics. There is nothing to not work. 7/24/2018

54 ONLY 0.1 HZ IS A VALID TEST 7/24/2018 The IEEE standard recognizes frequencies down to 0.01Hz. While it is true that most of the worldwide research over the last 20 years into testing levels and durations has been done at 0.1Hz, that does not mean lower frequencies are ineffective. It’s a tough argument to make that 60 Hz is ok, DC is ok for a lot of things including new cable, 0.1Hz is ok, but 0.05Hz is not? .1Hz 60Hz .05Hz DC 7/24/2018

55 ONE WAVEFORM OUTPUT IS BETTER THAN ANOTHER
7/24/2018 Of the three major VLF vendors, two output waveforms are offered: sine wave & cosine-rectangular (trapezoidal). Both work well to VLF hipot cable, although the sine wave output grows electrical trees faster - see IEEE400. -However - A sine wave VLF is better suited for use as a voltage source for tan delta and partial discharge testing, both desirable add-ons to VLF testing. Also, a sine wave is necessary for motor/generator testing per IEEE433. 7/24/2018

56 WHO USES VLF 7/24/2018 7/24/2018

57 UTILITIES TESTING SERVICES INDUSTRIALS CONTRACTORS
Other methods of cable testing have their place, but VLF is embraced worldwide as the easiest, most effective, most economical method of cable testing. Over 800 VLF units have been shipped from High Voltage, Inc. over the last eight years, delivered to 54 countries and many US locations. Other VLF products have shipped from other vendors for even longer. 7/24/2018 The following slides are just a few examples of the worldwide acceptance of VLF. Previous slides showed the IEEE, EPRI, CEA, and the European acceptance, via their recommendations and/or standards for VLF testing. 7/24/2018

58 COUNTRIES USING HVI VLF
7/24/2018 HVI has shipped over 800 VLF products to the following: USA Canada Taiwan Indonesia So. Korea Australia Saudi Arabia England Costa Rica Bolivia Israel So. Africa Singapore Hong Kong Belgium Puerto Rico Holland New Zealand Japan Malaysia Russia Spain Slovak Republic Czech Republic China UAE Vietnam Panama Jordan Germany Cyprus Honduras Lithuania Thailand Mexico India Bulgaria Fiji Venezuela Finland Greece Qatar Argentina Norway 7/24/2018

59 SELECTING A VLF MODEL 7/24/2018 7/24/2018

60 The above chart only covers ratings to 35kV. VLF
WHAT SIZE CABLES ARE TO BE TESTED? Do you do Install, Acceptance & Maintenance testing? 7/24/2018 From IEEE400.2 System Voltage phase to phase kVrms 5 15 25 35 Installation phase to ground kVrms/kVpeak 9/12 18/25 27/38 39/55 Acceptance phase to ground kVrms/kVpeak 10/14 20/28 31/44 44/62 Maintenance phase to ground kVrms/kVpeak 7/10 16/22 23/33 33/47 The above chart only covers ratings to 35kV. VLF testers exist that can test cables rated up to 230kV. 7/24/2018

61 WHAT CABLE LENGTHS ARE TO BE TESTED?
VLF units are rated by the uF of load they can test. 7/24/2018 Example: 15 kV XLPE 750mcm 220 mils ~ .1uf/1000’ Model VLF-25CM kV Peak μf Load Can test up to 4000’ of 15 kV cable depending on size. Perfect NETA model 7/24/2018

62 POPULAR MODEL USED BY TESTING CONTRACTORS.
Can test cables rated to 25 kV. 7/24/2018 Model VLF-4022CM kV Peak μf Load μf Load μf Load 70 lbs lbs Example: 15 kV XLPE 750mcm 220 mils ~ .1uf/1000’ At 0.1 Hz can test ~ 2 miles. At 0.02 Hz can test ~ 10 miles. 7/24/2018

63 MODEL SIZES AVAILABLE (all vendors included)
7/24/2018 Voltage ratings from 20 kV – 200 kV Load ratings from 0.4 uF – 50 uF For a 15 kV cable, 0.4 uF can test ~ 4000’ Some models can test > 30 miles of cable 7/24/2018

64 WILL IT BE USED FOR TAN DELTA
& PD TESTING? 7/24/2018 Sine wave output is needed to use VLF as a voltage source for td and pd testing. IEEE433 for VLF testing rotating machinery requires a sine wave output. Leave all your future testing options open by buying a sine wave VLF. 7/24/2018

65 Other Models 90 kV peak Up to 2.75 uF 120 kV peak up to 5.5 uF
7/24/2018 90 kV peak Up to 2.75 uF 120 kV peak up to 5.5 uF 60 kV peak up to 5.5 uF 200 kV soon available 65 kV peak up to 22 uF 7/24/2018

66 Complete URD Cable Care System Combination VLF AC Hipot
VLF THUMPER 7/24/2018 Complete URD Cable Care System Combination VLF AC Hipot and Thumper VLF Output: kVAC peak Load Rating: Hz ~ 1.5 miles of 15 kV cable Discharge: – J VLF Cable Burning Mode Radar Ready 7/24/2018

67 SELECTING A CABLE TEST METHOD
7/24/2018 SELECTING A CABLE TEST METHOD 7/24/2018

68 CABLE TEST METHODS AC Power Frequency. AC Series & Parallel Resonant.
7/24/2018 AC Power Frequency. AC Series & Parallel Resonant. DC Hipot. Very Low Frequency (VLF) AC Hipot. Tan Delta, Partial Discharge, And Other Diagnostic Methods. 7/24/2018

69 SEVERAL METHODS – WHAT TO USE?
7/24/2018 Ideally, VLF, Tan Delta, and Partial Discharge should all be used. However, there are real world factors affecting the decision. 1. Type of test results desired 2. Ease of use 3. Cost of equipment There is no one perfect method that does it all. A variety of approaches is needed to meet all the requirements encountered. 7/24/2018

70 WHAT’S THE GOAL? Verify new installation? Verify repaired cable?
7/24/2018 Verify new installation? Verify repaired cable? Verify critical cable? Help to prioritize cable replacement or injection? 7/24/2018

71 WHAT’S THE SITUATION? Direct buried – must pinpoint problem to repair
7/24/2018 Direct buried – must pinpoint problem to repair Cable in conduit or trench - replaceable Cable in raceways – visible and easily replaceable How old is cable What is the failure history How easy is it to repair Is there alternate feed should failure occur during test Is fault location and repair available? How much downtime can be tolerated? 7/24/2018

72 EXAMPLES OF SITUATION vs. METHOD
7/24/2018 New Install: Diagnostic test not appropriate, the insulation is good. VLF it to make sure there are no installation flaws. Old suspect cable: There may be many defects, don’t VLF. Use TD to see how degraded cable is. If modest degradation, then PD possibly followed by VLF. Critical cable in conduit: PD test to expose location and severity of defects. If no PD tester available, VLF. Direct buried, hard to repair: TD test to evaluate condition to prioritize cable injection or replacment. Prioritization for replacement or injection: If a comparative condition assessment test is desired, tan delta is the easiest method. Post repair test: VLF repaired cable to make sure it holds – no further damage caused by over voltage thumping. 7/24/2018

73 NO SHORT AND EASY ANSWER.
SO, WHAT TO DO? NO SHORT AND EASY ANSWER. Depends on money and available people. A combination of methods is needed: some easy and economical (VLF) and some more complicated and more expensive (TD & PD), and each yielding different but important data about your cable. 7/24/2018 7/24/2018

74 IT ALL STARTS WITH A VLF 7/24/2018 Fact: As more industrial customers, utilities, and specifying engineering companies spec VLF testing, per IEEE400.2, you will need a VLF. Fact: In addition to performing VLF AC stress tests, a VLF hipot is the foundation for other tests, like partial discharge and tan delta. You need VLF for pd and td. To learn the most about the health of your cable, all three tests, if economically and logistically feasible, are recommended. If not all possible, VLF should be the fallback, or nothing in old cable systems. 7/24/2018

75 7/24/2018 SUMMARY & CONCLUSION 7/24/2018

76 VLF TESTING SUMMARY 7/24/2018 Has the virtues of DC test equipment (low cost, small size, light weight, easy to use) but is AC. Does not have the negative consequences of DC. Requires 1/600 – 1/6000 of the kVA of power frequency. Can be used for breakdown tests and predictive tests such as Tan Delta and Partial Discharge. (sine wave VLF units) Internationally accepted Standards exist and more are in the process of issuance. 7/24/2018

77 CONCLUSION The surest way to verify the AC integrity of any load is perform an AC stress test. It’s easy and certain. The load holds voltage or fails. VLF testing is easily performed with minimal training. Worldwide standards and decades of history exist. Some VLF models are very portable and affordable. VLF makes Tan Delta and Partial Discharge diagnostic testing easier and more economical. 7/24/2018 7/24/2018

78 CONCLUSION VLF is suitable for use on cables and rotating machinery.
7/24/2018 VLF is suitable for use on cables and rotating machinery. IEEE, VDE, CEA, EPRI, other country’s engineering organizations, cable manufactures, and major utilities all recommend VLF. Hundreds of users worldwide have embraced VLF VLF It! It’s economical, easy, and sure. 7/24/2018

79 OTHER CABLE TEST METHODS USING VLF
7/24/2018 7/24/2018

80 YOU HAVE YOUR VLF. WHAT ELSE CAN YOU DO?
7/24/2018 Accessorize. Add on a Tan Delta measurement instrument. Partial Discharge detection instrument. 7/24/2018

81 Dissipation Factor or Loss Angle Measurement For Power Cables
TANGENT DELTA or TAN δ 7/24/2018 Dissipation Factor or Loss Angle Measurement For Power Cables Non Destructive Testing To Determine Insulation Quality (Similar to Power Factor Testing) 7/24/2018

82 TAN DELTA MEASUREMENT Using VLF @ 0.1 Hz
7/24/2018 Evaluates overall condition of cable (rather than localized problems as with PD measurement) Absolute values, variations, and trending of values are of interest for predicting insulation integrity Tan Delta is more easily measured at VLF (magnitude increases as frequency decreases) Requires VLF sinusoidal applied test voltage Excellent way to evaluate Water Trees Useful to help prioritize replacement, injection and helps to determine what additional test may be useful

83 CHARACTERISTICS OF WATER TREES
7/24/2018 Addition of a parallel R-C Component Water trees increase resistive current through insulation The R component is voltage dependent (non–linear I = V/R) Tan Delta values increase with increasing voltage

84 Simplified Cable Model and Phasor Drawing Tan Delta = IR/ IC - measured in radians
7/24/2018 With perfect insulation, a cable is a near perfect capacitor, with a 90° phase shift between voltage and current. Less than 90° indicates insulation degradation. Cables can be rated good, marginal, or bad. Not extremely precise but valuable for prioritizing cable replacement or injection. Also helps to determine what further tests may be worthwhile.

85 TAN DELTA VS. VOLTAGE NEW AND AGED XLPE CABLES
7/24/2018 Aged cable non-linear tan delta #s versus voltage New cable linear tan delta #s versus voltage

86 TAN DELTA NUMBERS VERSUS INCREASING VOLTAGE
& RATIO OF 2Vo/Vo 7/24/2018 7/24/2018

87 7/24/2018 Dissipation Factor – Tan Delta From IEEE Std Field experience shows these number to be too low. 7/24/2018

88 TAN DELTA LOSS ANALYZER
7/24/2018 60kV model Used with VLF as voltage source HV Divider Signal analyzer/controller 7/24/2018

89 TAN DELTA TESTING Advantages Disadvantages
7/24/2018 Advantages Less destructive than VLF, DC, or 60 Hz testing Helps to prioritize cable replacement and/or injection Easier to use and interpret than other diagnostic methods Disadvantages Can be destructive if cable very degraded Gives overall condition of cable, not singularities Not best for mixed type cable runs More useful with historical data 7/24/2018

90 VLF PARTIAL DISCHARGE TESTING
7/24/2018 7/24/2018

91 “SEE” UNDERGROUND CABLE FAULTS
7/24/2018 A PD detection system can show you the location and severity of insulation and accessory defects. Using a VLF as the voltage generator to apply voltages up to 2Vo, long cables can be tested with portable equipment. 7/24/2018

92 OFF-LINE VS. ON-LINE PD TESTING
7/24/2018 Off-line testing using a VLF permits over voltage analysis. Can measure PDIV and PDEV up to 2Vo. On-line pd testing can only detect pd at operating voltage, missing defects with a PDIV of 101% and above of operating voltage, yet cables routinely see twice normal voltage due to reflected waves, transients, switching surges, etc. Off-line testing may be less convenient, but the information gained is far more valuable. 7/24/2018

93 A 100 lb VLF can do the job of a 2000 lb 60Hz series resonant unit.
0.1Hz vs. 60Hz PD TESTING 7/24/2018 Both frequencies initiate pd at defect locations. Both can measure PDIV, PDEV, magnitude, and location. The benefit of VLF is smaller size, lower weight, far lower cost, and can test longer cables. A 100 lb VLF can do the job of a 2000 lb 60Hz series resonant unit. 7/24/2018

94 THE BEST OF EVERYTHING 7/24/2018 Start with a VLF tester to perform AC withstand testing. Add a Tan Delta accessory for evaluating the overall condition of a cable to help prioritize replacement, injection, or to determine what other tests might be helpful. Add a Partial Discharge accessory to map the location and severity of pd in the insulation and splices, or to Perform all three tests to get the most complete profile possible of your cable. 7/24/2018

95 Mike Peschel - High Voltage, Inc.
7/24/2018 Thank You Mike Peschel - High Voltage, Inc. 7/24/2018

96 7/24/2018 7/24/2018


Download ppt "VLF CABLE TESTING INCLUDING PARTIAL DISCHARGE & TANGENT DELTA"

Similar presentations


Ads by Google