Download presentation
Presentation is loading. Please wait.
Published byibrahim naqsh Modified over 7 years ago
1
CONFIDENTIAL Technical Seminar on Application and Technical Specification 21 June 2016 Rezza Arif Bin Mustapa Kamal Senior Engineer Project And Application Department
2
HVAC Systems (Heating, Ventilating and Air Conditioning) Applied Product Systems (AP) Unitary Product Systems (UP) Chilled Water Air Cooled Scroll Modular Water Cooled Absorption Centrifugal Screw Scroll Direct Expansion (DX) Air CooledWater Cooled Split MultiSingle Packaged Split Packaged Classification of Air Conditioning System
3
Factors affecting the decision to select Unitary or Applied systems include: Installed Cost Energy consumption Space requirements Freeze prevention Precision Building height, size, shape System cooling and heating capacity Centralized maintenance Stability of control Individual tenant billing Classification of Air Conditioning System
4
What Is Air Conditioning? Fundamentals of Air-Conditioning
5
What is Air Conditioning? Air Conditioned Space temperature, humidity, cleanliness & distribution to meet the requirements of the conditioned space. It is defined as “the process of treating air so as to control simultaneously its Fundamentals of Air-Conditioning
6
What Is Air Conditioner? Fundamentals of Air-Conditioning
7
Air-conditioners are fundamentally built on the principle of refrigeration cycle which consists mainly the following components :- What is Air Conditioner? Evaporator Compressor Condenser Expansion Device Fundamentals of Air-Conditioning
8
Evaporator (Fan Coil Unit) The evaporator cools the air in the room by evaporating the refrigerant that passes through it. Heat is then removed from the room and is carried away by refrigerant gas …. What is the function of the evaporator? Fundamentals of Air-Conditioning
9
With continuous supply of refrigerant to an open system, it is inefficient and costly. ….. therefore we need a closed system Ref Air flow Fundamentals of Air-Conditioning
10
Basic Refrigeration System A B C D EVAPORATOR COMPRESSOR EXPANSIONDEVICE CONDENSER High pressure side Low pressure side Discharge line Suction line Liquid line Fundamentals of Air-Conditioning
13
Compressor Condenser Evaporator / Heat Exchanger Expansion device AIR COOLED CHILLER SYSTEM FCU AHU Water pump Chilled water P Fundamentals of Air-Conditioning
14
Evaporator B A Warm air Vaporrefrigerant Mixture of liquid and vapor refrigerant Function: Cool air Water condensate flows down – Absorb heat from the air that passes thru and transfer to the refrigerant and carried away Fundamentals of Air-Conditioning
15
Compressor Function: Low pressure vapor refrigerant from evaporator High pressure vapor refrigerant to condenser C B – Refrigerant is being compressed from low pressure & temperature to a pressure & temperature high enough to be condensed Fundamentals of Air-Conditioning
16
Condenser D C Warm air Liquid refrigerant to TXV Vapor refrigerant from compressor Function: Cool ambient air – Heated refrigerant gas from compressor enter the condenser, heat is being rejected to the atmosphere when cooler ambient air pass thru it Fundamentals of Air-Conditioning
17
– Throttle the refrigerant flow causing sudden drop of high pressure to low pressure where a flash expansion occurs that turns liquid to convert into vapor state Expansion Device (TXV) AD Function: Mixture of liquid and vapor refrigerant to evaporator Liquid refrigerant from condenser Fundamentals of Air-Conditioning
18
expansiondevice condenser evaporator compressor Basic Refrigeration Cycle 41.0°F[5.0°C] 51.0°F[10.6°C] D G C B E F 121.5°F[49.7°C] A 110°F[43.3°C] Fundamentals of Air-Conditioning
19
expansiondevice condenser enthalpy evaporator compressor Refrigeration Cycle – R410A 130-150 psig pressure D G C B E F 350-450 psig A Fundamentals of Air-Conditioning
20
Two types of heat Sensible Heat Addition of Heat = change in temperature Basics of Heat Load Calculation
21
Two types of heat Latent Heat Addition of Heat = change in state Basics of Heat Load Calculation
22
Classification of cooling load Load components can be classified into 3 categories: 1)Skin Load 2)Internal Load 3) Other Load Basics of Heat Load Calculation
23
Skin load for a space Ceiling & Roof / Upper Rooms Infiltration Glass Wall Ground / Lower Rooms Partitions / Inner Walls Ventilation Basics of Heat Load Calculation
24
Internal Load for space Equipment/ Appliances Lights People Lights Basics of Heat Load Calculation
25
Other load for space Duct Leakage Heat Gain Fan Heat Basics of Heat Load Calculation
26
heat load components in a space Basics of Heat Load Calculation
28
Equivalent Temperature difference method Heat Gain is given by: –Q = Rate of heat transfer [W] –A = Area of surface [m 2 ] –U = Thermal transmittance [ W/m 2 K] –ΔT = Temperature difference of wall surface(T o – T i ) Q = A x U x ΔT Basics of Heat Load Calculation
29
Equivalent Temperature difference method External WallsInternal Walls Roofs Ceilings Partitions Floors Q = A x U x ΔT Can be used to measure heat load for: Glass Note: This equation is used to calculate ONLY transmission gain Basics of Heat Load Calculation
30
Formula for u- value calculation Basics of Heat Load Calculation
31
Formula for u- value calculation Basics of Heat Load Calculation
32
Componentsb/KR [m 2 K/W]Density [kg/m3]Weight [kg/m2] Outside air film-- 12mm cement plaster 115mm brick wall 12mm cement plaster Indoor air film-- Total R:Total Weight: Example U-value calculation 115mm Brick wall + Finishes (Both Sides) 12mm thick cement plaster 0.120 0.044 0.012/0.533 0.115/0.807 1760 1568 0.023 0.143 0.023 18.82 202.4 0.352240.04 U = 1/R = 1/0.352 = 2.841 W/m 2 K
33
Solar Gain - Glass Solar gain is given by: – Q = Rate of heat transfer [W] – A = Area of glass [m 2 ] – SF = Solar Factor [W/m 2 ] – SC = Shading coefficient of glass window Q = A x SF x SC Basics of Heat Load Calculation
34
Solar factor selection Reference Glass is 3 mm thick ordinary glass set in aluminium frame
35
Shading coefficient selection External Shading Devices: 1)Horizontal Projection 2)Vertical Projection 3)Egg-crate Lourves
36
Infiltration load Infiltration load is given by: – Q i = Infiltration heat load [W] – Q is = Sensible infiltration heat gain [W] – Q il = Latent infiltration heat gain [W] – V = Infiltration air volume [m 3 /h] – ΔT = Temperature difference of outdoor and indoor air – Δ X= Absolute humidity difference of outdoor and indoor air Q i = Q is + Q il Q is = 0.33 x V x ΔT Q il = 833 x V x Δ X
37
Cooling load calculation Summing up all of the heat load components: –Skin Load Wall, glass, floor, roof and ceiling transmission heat gain Glass solar heat gain Infiltration heat gain –Internal Load People heat Appliances Lighting –Other Load Duct leakage Heat Gain Basics of Heat Load Calculation
38
Heat load calculation form
42
Tables for heat load calculation
43
Heat load calculation form Tables for heat load calculation
44
Heat load calculation form
45
Rule of thumb
46
QUESTIONS?
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.